BACnet Points of Control, BACnet Node ID
BACnet Gateway: Directions & Applications
page 8
lighting controls
BACNET Control Points
The WNG-2133 BACnet Gateway has 1000 control points. Extensive lighting control networks may require
more, due to the vast amount of data required to represent as many as to 255 groups overall and 72 points
per panel. To overcome this constraint, multiple WNG-2133 Gateways of complementary configurations can
be used. The best distribution of points is to group relays together by node. This would be done by bit-
mapping each relay to an existing data structure.
Multiple WNG-2133's can be utilized within a system.
Each profile has been created to maximize the 1000
points available.
BACnet to LonWorks Self-configured System
Self-configured systems up to 12 scanners:
Use one WNG-2133 Gateway.
Self-configured systems with more than12 scanners:
Use two WNG-2133 Gateways,
WNG-2133-NP1-10G &
WNG-2133-NP11-30
.
BACnet to LonWorks WNG-2150 System
WNG-2133-NP1-10G - BASE UNIT:
Controls 10 scanners 1-10 PLUS all groups.
WNG-2133-NP11-30:
Controls 20 scanners 11-30 (Needs WNG-2133-NP1-10G).
WNG-2133-NP31-50:
Controls 20 scanners 31-50 (Needs WNG-2133-NP1-10G).
WNG-2133-NP51-70:
Controls 20 scanners 51-70 (Needs WNG-2133-NP1-10G).
BACnet to MC-6000 System
WNG-2133-MC05-11:
CPU5-11, Grp0-52, MC-6210 incl.
WNG-2133-MC12-18:
CPU12-18, Grp 53-104, MC-6210 incl.
WNG-2133-MC19-25:
CPU19-25, Grp 105-156, MC-6210 incl.
WNG-2133-MC-G500:
Grp 1-500 ONLY, MC-6210 incl.
WNG-2133 Profile Listing
Changing the BACnet Node ID:
Uploading, Editing and Downloading
the config.csv File
To upload the config.csv File from the WNG-
2133 to your PC
1. From the main menu select <
U>
to go to the upload
screen.
2. Begin the uploading by selecting <
U>
.
To edit the config.csv File on your PC
1. Locate the files where the Ruinet.exe executable resides.
2. Select and launch the NOTEPAD program to edit the file.
(Using any other program may corrupt the file).
3. Within the
config.csv
file, locate the
Server Side
Connections - BACnet IP
area . Adjust the number under
the
Node_ID
line. This should appear as shown below:
//====================================
//
//
Server Side Connections -BACnet IP
//
Nodes
Node_Name, Node_ID, Protocol
WNG-2133_GTW1,
11
, BACnet_IP
//===================================
To download the edited File to the WNG-2133
1. From the main menu select <
D>
to go to the download
screen.
2. Begin the download by selecting <
D>
.