BACnet Points of Control, BACnet Node ID

BACnet Gateway: Directions & Applications

page 8

lighting controls

BACNET Control Points

The WNG-2133 BACnet Gateway has 1000 control points. Extensive lighting control networks may require 
more, due to the vast amount of data required to represent as many as to 255 groups overall and 72 points 
per panel. To overcome this constraint, multiple WNG-2133 Gateways of complementary configurations can 
be used. The best distribution of points is to group relays together by node. This would be done by bit-
mapping each relay to an existing data structure.

Multiple WNG-2133's can be utilized within a system. 
Each profile has been created to maximize the 1000 
points available.

BACnet to LonWorks Self-configured System

Self-configured systems up to 12 scanners: 
Use one WNG-2133 Gateway.

Self-configured systems with more than12 scanners:       
Use two WNG-2133 Gateways,

 WNG-2133-NP1-10G  &  

WNG-2133-NP11-30

.

BACnet to LonWorks WNG-2150 System

WNG-2133-NP1-10G - BASE UNIT: 
Controls 10 scanners 1-10 PLUS all groups.

WNG-2133-NP11-30:
Controls 20 scanners 11-30 (Needs WNG-2133-NP1-10G).

WNG-2133-NP31-50:
Controls 20 scanners 31-50 (Needs WNG-2133-NP1-10G).

WNG-2133-NP51-70:
Controls 20 scanners 51-70 (Needs WNG-2133-NP1-10G).

BACnet to MC-6000 System

WNG-2133-MC05-11:                                                      
CPU5-11, Grp0-52, MC-6210 incl.

WNG-2133-MC12-18:                                                   
CPU12-18, Grp 53-104, MC-6210 incl.

WNG-2133-MC19-25:                                                 
CPU19-25, Grp 105-156, MC-6210 incl.

WNG-2133-MC-G500:                                                          
Grp 1-500 ONLY, MC-6210 incl.

WNG-2133 Profile Listing

Changing the BACnet Node ID:
Uploading, Editing and Downloading 
the config.csv File

To upload the config.csv File from the WNG-
2133 to your PC

1.  From the main menu select <

U>

 to go to the upload 

screen.

2.  Begin the uploading by selecting <

U> 

.

To edit the config.csv File on your PC

1.  Locate the files where the Ruinet.exe executable resides.

2.  Select and launch the NOTEPAD program to edit the file. 

(Using any other program may corrupt the file).

3. Within the 

config.csv

 

 file, locate the 

Server Side 

Connections - BACnet IP

 area . Adjust the number under 

the 

Node_ID 

line. This should appear as shown below:

  

//====================================

//                       
//  

Server Side Connections -BACnet IP

//   

Nodes
Node_Name, Node_ID, Protocol
WNG-2133_GTW1,

11

, BACnet_IP

//===================================

To download the edited File to the WNG-2133

1.  From the main menu select <

D>

 to go to the download 

screen.

2.  Begin the download by selecting <

D>

.

Содержание WNG-2133

Страница 1: ...WNG 2133 BACnet Gateway Instruction Manual...

Страница 2: ...ory Pre Assembled W 2000 Systems 4 Installation Factory Pre Assembled MC 6000 Systems 5 Setting the IP Address 6 Douglas Network Groups Status and Control 7 BACnet Points of Control Changing the BACne...

Страница 3: ...nd plugs into the socket on the right side side view Data Signal Connection Douglas W 2000 System Wink LED Pin Douglas W 2000 System Service LED flashes as diagnostic aid Pressing the Service pin tran...

Страница 4: ...oggle to select type of Douglas system that is to be connected to the BACnet system Pressing left side selects the MC 6000 System pressing right side selects the W 2000 System Data Signal Douglas MC 6...

Страница 5: ...el 24VAC 100mA Class 2 Low Voltage devices Input Input is a BACnet IP network signal BACnet IP connection medium is Ethernet Communication format is native BACnet IP Follow the wiring specifications i...

Страница 6: ...r to be switched by the same group input An output relay can also be in more than one group 9 SELF CONFIGURED SYSTEMS Use the keypad on each scanner to assign the output relays to each group input 9 W...

Страница 7: ...he group switching devices switch or timer to the input cards If you are connecting 24V switching devices other than a default Douglas switch or time clock you will have to first configure their input...

Страница 8: ...net 9 Configure your PC IP address to communicate with the new IP Address and the new Subnet Mask Make sure the IP Address of the PC is the Gateway entered into the WNG 2133 10 Start Ruinet The device...

Страница 9: ...Group Control is via a smart ANALOG value per group represented When used with a MC 6000 System 3 Off 4 On With the W 2000 it has the full functionality of the LonWorks SNVT_Scene The values entered i...

Страница 10: ...ntrols 20 scanners 11 30 Needs WNG 2133 NP1 10G WNG 2133 NP31 50 Controls 20 scanners 31 50 Needs WNG 2133 NP1 10G WNG 2133 NP51 70 Controls 20 scanners 51 70 Needs WNG 2133 NP1 10G BACnet to MC 6000...

Страница 11: ...n command This example shows the WNG 2133 as IP 10 33 12 23 and the BBMD on the other subnet as IP10 33 11 21 bdt ini FST Customer Douglas Lighting Configured By CBR Copyright c 2000 2002 WNG 2133 Tec...

Страница 12: ...gram if necessary HID lighting used in FLICK WARN group TIME OUT not working Inappropriate input switching device used make sure input is only ON during TIME OUT period use timer as input instead of s...

Страница 13: ...nstructions on page 8 check wiring Faulty wiring check programming re program if necessary Faulty wiring Scanner LEDs all OFF Scanner not receiving power check 24VAC power Scanner corrupt replace scan...

Страница 14: ...t Relays numbered by panel output 1 Type Remarks Remarks Remarks 2 Type Remarks Remarks Remarks 3 Type Remarks Remarks Remarks 4 Type Remarks Remarks Remarks 5 Type Remarks Remarks Remarks Panel Addit...

Страница 15: ...t Relays numbered by panel output 1 Type Remarks Remarks Remarks 2 Type Remarks Remarks Remarks 3 Type Remarks Remarks Remarks 4 Type Remarks Remarks Remarks 5 Type Remarks Remarks Remarks Panel Addit...

Страница 16: ...Notes BACnet Gateway Directions Applications page 14 lighting controls...

Страница 17: ...Notes BACnet Gateway Directions Applications page 15 lighting controls...

Страница 18: ...repair or at the company s option to replace products as aforesaid provided same are returned upon authorization Transportation Prepaid to the company s Burnaby CANADA office within the said period De...

Отзывы: