Positioning fragrance module (accessible)
– The fragrance modules must be installed outside the wet zone in an area that allows for easy access after installation.
– Ambient temperature 5-30 °C.
– The maximum distance between fragrance modules and ceiling installation enclosure for rain panel is 12 m.
– The maximum vertical height between fragrance modules and ceiling installation enclosure for rain panel is 4 m and must not be exceeded.
– The maximum distance between the fragrance modules and the closest heat source (e.g. steam generator, heating unit) must
not be less than 1 m. A heat shield has to be installed between the heat source and the fragrance modules if the required
distance of min. 1 m cannot be adhered to. The area needs to be well ventilated.
– The fragrance modules and the power supply have to be installed separate from each other.
(Distance: min. 1 m - the power supply cables can be extended on site to max. 2 m). The fragrance modules must not be installed
directly above the electrical installation.
Peripheral equipment
Sub-distribution board
internal dimensions
min. 500 x 500
Fragrance modules
1000 x 210 x 140
overall dimensions
The fragrance modules must not
be installed directly above the
electrical installation.