5

TS 97 FLR-K XEA

2019-08

dormakaba Mounting instructions

Completion of mounting

WN 059876 45532

 

4  OFF  =  without manual release button 

 

 

ON   =  with manual release button 

2. 

Press the reset button.

4.5  Apply voltage

 12 

1. 

Remove the red protection cover from the smoke 
detector unit.

2. 

Turn on the on-site power supply (230 V AC). 

 

‣ The operation indicator flashes green.

4.6  Mount lever arm

 13 

CAUTION

Risk of injury due to unintentional loosening 
of the screw connection on the lever arm

•  Only use the self-locking screw supplied. 

If this screw is loosened during repair or 
maintenance work, the screw must be 
replaced by a new self-locking original 
screw.

Mount the lever arm according to the illustrated 
instructions and the mounting variant.

4.7  Adjust door closer

 14 

Adjust the door closer power.

 15 

1. 

Adjust the closing speed. 

2. 

Adjust the end stop.

4.8  Mount the cladding

  16 - 18 

Carry out the mounting according to the enclosed 
illustrated instructions.

4.9  Set the doorstop

 19 

Set the doorstop according to the mounting variant 
and the structural conditions. The maximum opening 
angle must not be exceeded.

4.10  Function test 

4.10.1  Freewheel function

The door can be opened and closed manually without 
resistance from the door closer.

4.10.2  RMZ automatic door closing

CAUTION

Risk of eye and respiratory injury

•  Follow the application and safety 

instructions on the test gas and the safety 
data sheet.

 20 

1. 

Open the door.

2. 

Spray the test gas on the smoke detector 
according to the manufacturers’ instructions.

 

‣ The operation indicator switches to alarm 

(red).

 

‣ The door closes.

During a manual reset: 

When the test gas has dissipated, press the reset 
button to reactivate the freewheel function.

During an automatic reset:

The freewheel function is activated automatically 30 
seconds after the test gas has dissipated.

5  Completion of mounting

If further structural work is carried out, protect the 
smoke detector from dust.

 21 

1. 

Disconnect the unit from the power supply.

2. 

Fit the provided dust cover.

3. 

Before the final commissioning, remove the 
dust cover and carry out a further function test 
according to chapter 4.10.

5.1  Acceptance inspection

After mounting, an acceptance inspection is to be 
carried out according to the inspection log for hold-
open systems. The acceptance inspection must only 
be carried out by qualified personnel certified for 
this by dormakaba. Observe the instructions in the 
information sheet on the use of hold-open systems. 
The acceptance inspection must be documented in 
the inspection log for hold-open systems.

Содержание TS 97 FLR-K XEA

Страница 1: ...ms 3 2 4 Requirements for the electrical installation by the customer 3 3 Product description 3 3 1 RMZ 3 3 2 DIP switch on the RMZ 3 3 2 1 Terminal assignment of the RMZ 4 3 2 2 The RMZ s operating status display 4 3 3 Optional components 4 3 4 Technical data 4 3 4 1 Door closer 4 3 4 2 RMZ 4 4 Mounting 4 4 1 Mounting variants 4 4 2 Mounting the door closer and slide rail 4 4 3 Make electrical co...

Страница 2: ...y if not averted CAUTION This signal word indicates a situation of potential risk which could lead to minor or slight injury if not averted TIPS AND RECOMMENDATIONS This signal word indicates useful information for efficient and trouble free operation 1 6 Symbols used 1 The picture number in the text document refers to an illustration in the picture section of the mounting instructions 1 2 Step by...

Страница 3: ...Connect the 230 V AC power supply to the RMZ A circuit breaker B 10A B 16A must be present in the supply circuit The circuit breaker also serves as a disconnecting device to disconnect the RMZ from the power supply The transverse section of the mains power supply must only be a max 3 x 1 5 mm NYM Connect the cables for the 24 V DC power supply from the RMZ to the TS 97 FLR K XEA door closer The su...

Страница 4: ...ke switch 24 V DC 50 mA Temperature 20 C 40 C Rel humidity max 93 without condensation 4 Mounting The figures in the picture section of this manual show the mounting for DIN L For DIN R the instructions must be mirror inverted 4 1 Mounting variants The TS 97 FLR K XEA can be mounted DIN L or DIN R on the hinge side or opposite side to the hinge 4 2 Mounting the door closer and slide rail 2 9 Carry...

Страница 5: ...ned and closed manually without resistance from the door closer 4 10 2 RMZ automatic door closing CAUTION Risk of eye and respiratory injury Follow the application and safety instructions on the test gas and the safety data sheet 20 1 Open the door 2 Spray the test gas on the smoke detector according to the manufacturers instructions The operation indicator switches to alarm red The door closes Du...

Страница 6: ...the replacement period has been reached 7 Disassembly recycling and disposal Disassembly is carried out in reverse order to the mounting and must be carried out by qualified personnel DANGER Danger to life through electric current Works on electrical units must only be carried out by qualified electricians Before starting work on electrical units and equipment make sure that it is de energized and...

Страница 7: ...7 TS 97 FLR K XEA 2019 08 dormakaba Mounting instructions Maintenance WN 059876 45532 ...

Страница 8: ...Translation of the original manual subject to change without notice dormakaba Deutschland GmbH DORMA Platz 1 58256 Ennepetal Germany T 49 2333 793 0 F 49 2333 793 4950 www dormakaba com ...

Отзывы: