dormakaba 8600 EMF Installation Instructions
08281020
03-2020
8600 EMF
9
Power supply
Check connections
5.1 Determine power supply
Fig.12
5.1.1 Determine power supply and unit voltage type:
24VAC/24VDC.
CAUTION! DO NOT CONNECT 120-VAC TO A 24 VOLT
UNIT TYPE!!!
5.1.2 Connect power supply wires, one (1) to terminal
block one (1) to bypass switch.
5.1.3 Connect other bypass switch wire to terminal
block. (Terminal block can be removed for easier
wiring).
5.1.4 Slide wiring connection cover over wire
connections.
Wire
connection
cover
Bypass
switch
Terminal
block
Incoming
power
connection
UL listed alarm
control unit or
smoke detector
5
Final steps
1. After installation is completed, check all connections. Apply power to units.
2. Open door so slide block engages with hold open assembly.
3. Advise fire officials prior to testing.
4. Activate system into alarm so the electromagnet releases and the doors close.
5. If the closer is used in conjunction with a detectored unit, trip the test switch of the main closer
detector as explained in the test procedure for that unit. After a short time delay, the hold open
electromagnet of both units will release and the doors will close. Resetting the test switch will allow
the units to return to standby.
5.2 Check connections