dormakaba 8600 EMF Installation Instructions
08281020
03-2020
8600 EMF
10
Testing
Operation
Covers
IMPORTANT: THE UNIT MUST BE TESTED AFTER THE INSTALLATION, BY THE END USER, TO ASSURE
THAT THE DOOR CLOSER UNITS FUNCTION PROPERLY WHEN THE ALARM SYSTEM IS ACTIVATED.
THE ENTIRE SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER THE INITIAL INSTALLATION TEST,
IN CONJUNCTION WITH THE TESTING OF THE FIRE ALARM SYSTEM. THE END USER IS ALSO
RESPONSIBLE FOR THE ADJUSTMENTS AND MAINTENANCE TO RETAIN THE SYSTEM IN WORKING
ORDER.
NORMAL: The closer unit’s solenoid will be
energized across a normally closed
alarm contact from 24VDC, 24VAC
or 120VAC power supply based on
unit voltage.
FIRE ALARM:
When the alarm sounds, the
alarm contact will open and
interrupt current to the solenoid
which releases the hold open
allowing the door to close and latch.
ELECTRICAL SPECIFICATION:
Voltage input - 24VDC + 10% - 15%
24VAC + 10% - 15%
Maximum input current - 24VDC 166mA
24VAC 166mA
5.4 Operation
5.5 Covers
Fig.13
COV
FC
FCSL
FMC
5.3 Unit testing