Sensor for approach detection at industrial doors

  In order to comply with the safety requirements of  

EN 60650-1 and UL508, the sensor must be operated 
with safety extra-low voltage (SELV).  
The total output power must not exceed 100 W under 
any circumstances. Use for example T2, 5A fuse to 
ensure compliance.

Delivery package

1 Sensor

Connection cable

Screws for mounting (in the housing)

1  

Self-adhesive mounting template

Mounting instructions

Elements



 

LED (red/green) 

 Potentiometer

 

IR receiver 

 Connector

 

IR transmitter 

 Antenna

 

DIP switches

 

1 2

OPEN

3 4 5 6

1

7

4

5

6

2

3

  Components can be damaged by electrostatic energy!  

Do not touch any electronic components. 
Do not use metal tools.

Preparation

Insert the screwdriver into 
the opening provided from 
behind, carefully lift up the 
cover, fold upwards and 
remove. 

  Do not open 

the housing from the top. 

Turning the antenna 

(to change the antenna characteristics)

 

Remove the antenna 
carefully using two fingers 
and insert in the antenna 
orientation for the required 
detection area.

  Do not bend the contacts. 

Do not touch the surface of the antenna.

Antenna characteristics

A wide or narrow detection area can be set with the turnable 
antenna.
Installation height 

2.20 m

Detection area angle 

30°

Detection area size 

Max

Wide

Width:
Depth:

4.50 m
2.00 m

Narrow

Width:
Depth:

2.00 m
4.50 m

Installation information 

•  Protect the sensor from 

rain

*

.

•  Avoid moving objects 

in the detection area 
(fans, plants, etc.).

•  Do not cover the sensor. 

Mount the sensor only 
behind suitable covers.

•  Moving drive components 

affect the sensor.

•  Avoid fluorescent lights in 

the detection area. 

•  The installation conditions 

may limit the program-
ming options and the 
functions of the sensor.

     

     

*  DORMA recommends 

installing a weather cap 
for outdoor applications

Accessories

Remote control 
Rain protection cover

Mounting 

Attach the self-adhesive 
template and drill according 
to the hole pattern.
Guide the cable through the 
opening provided.
Fasten the baseplate using 
the screws (screws are in 
the housing).
Can be mounted on the  
ceiling using the rain protec-
tion cover. 

Connecting the sensor

Connect the cable  
to the terminal as follows:



 

white  = GND

 

brown = 

12 - 36 V DC/  

 

  12 - 28 V AC

 

green  = COM

 

yellow  = NO/NC 

1
2
3
4

Replacing the cover

Attach the cover on the top  
and press down until it snaps  
into place.

click