L6L
2. Assembly
11
2.6 Assembly of flat casing
Flush cabling
Once the preparatory work is complete, the pre-assembly
plate can be fitted to the wall.
To do this, the three holes for the fixing screws must be
drilled according to the drilling template included.
Before drilling, ensure that you will not be
able to damage any cables or similar located
underneath the plaster.
The cables are laid through the knock-out sections on the
pre-assembly plate.
The data cables (RS485/DCW) must be stripped from
approx. 15mm after the wall opening.
The shielding is shortened to approx. 10mm and clamped
underneath the clips.
The clips are intended for connecting the data line shielding
and are not used for strain relief.
The wires are then shortened to the required length and
connected to the screw terminals (on the terminal printed
card). The transformer is only fitted for the 230V models.
The cables are then inserted through the rear wall of the
terminal and the terminal is screwed onto the pre-assembly
plate using the three fixing screws.
Area for
cable outlet
Contour of pre-assembly plate
ø6
164.5
142.5
27.7
approx. 1500
Lower casing edge
Top edge of finished floor
ø6
ø6
Transformer