Flow Chart for NATIONAL BUILDING CODE
N
Y
LEDR Blinking Fast
Local Alarm On
Remote Alarm On
Buzzer Pulsing
Nuisance Delay
Time Out ?
Dip Switch Setting
Dip1-
On: 15 Seconds
Dip2/Dip3- On/On: 0 Second.
Dip4-
On.
Power On
Locked ?
Door Pushing ?
LEDR Off
LEDG Blinks every 5S.
Local Alarm Off
Remote Alarm On
Y
N
Y
LEDR Blinking Slowly
Local Alarm On
Remote Alarm Off
Buzzer On
Release Delay
Time Out ?
Y
LEDR/G Blinking Alt.
Local Alarm Off
Remote Alarm Off
Lock Release
N
Still Locked ?
N
LEDR On
Local Alarm Off
Remote Alarm Off
Reset to Relock
?
Y
Relock
N
Y
Dip1-
Release Delay 15
seconds only.
Dip2/Dip3- Nuisance delay not allowed
Relock occurs only when Reset
Switch Input from open to close.
NOTE:
NOTE:
N
(for CANADA)
Buzzer Off
Buzzer Off
Flow Chart for BURGLAR ALARM
N
Y
LEDR Blinking Fast
Local Alarm On
Remote Alarm On
Buzzer Pulsing
Nuisance Delay
Time Out ?
Power On
Locked ?
Door Pushing ?
LEDR Off
LEDG Blinks every 5S.
Local Alarm Off
Remote Alarm On
Y
N
Y
LEDR Blinking Slowly
Local Alarm On
Remote Alarm Off
Buzzer On
Alarm Period
Time Out ?
Y
LEDR/G Blinking Alt.
Local Alarm Off
Remote Alarm On
N
Still Locked ?
N
LEDR On
Local Alarm Off
Remote Alarm Off
Reset ?
Y
System Reset
N
Y
Dip1/Dip2-
Remote Alarm Period can
be infinity.
Dip3/Dip4-
Nuisance Delay permitted
up to 6 seconds.
System reset occurs only when
Reset Switch Input is close.
NOTE:
NOTE:
N
Dip Switch Setting
Dip1/Dip2- On/On: 0 Second.
On/Off: 2 Seconds.
Off/On: 4 Seconds.
Off/Off: 6 Seconds
Dip3/Dip4-
On/Off: 15 Seconds.
Off/On: 30 Seconds.
Off/Off: Infinity
On/On: 0 Second.
Buzzer Off
Buzzer Off
Remote