Instruction manual DR-RS
3.12.3
Replacing orifices
1. Detach the protective cap van the control column:
Loosen the 4 screws and remove the protective cap by lifting it upwards. The
electrical section will now be visible.
2. Remove the strain relief
and detach the leads of the spark electrode (
red) and the flame probe (
= black) from the burner control
.
3. Unscrew the connector(s)
of the gas control
.
4. Detach the gas coupling
before the gas control.
5. Remove the ten screws holding the burner tray
in place.
6. Withdraw the burner tray from the water heater.
n
Remark
When exchanging the pilot flame orifice and/of orifices:
Lay the burner tray on its side and approach it from the underside.
Legend:
a
strain relief
b
lead for spark electrode
c
lead for flame probe
d
burner control
e
gas control connector(s)
f
gas control
g
gas coupling
h
burner tray
Figure 3.12
Disassembled gas control