Installation
30
Instruction manual DR-RS
3
is
3.9.3
Fitting flue gas discharge and air supply for DR-RS 85 and 105
The air supply duct
and flue gas discharge duct
emerge separately from the top box, as shown in
. They must be
connected to the concentric wall flue terminal (see
) or roof flue
) via a transition piece.
n
Remark
Hamworthy prescribes the use of a roof or wall-mounted concentric terminal,
of a type approved for the water heater. See paragraphs
wall flue terminal for DR-RS 85 and 105
. Use of an incorrect roof or wall-mounted
terminal can cause the installation to malfunction.
The following requirements must also be fulfilled:
•
The maximum chimney length allowed (A+B+C) is 7 metres.
•
The maximum number of 45° or 90° bends allowed is 2.
•
If you make use of horizontal piping, then this must slope towards the water
heater with a minimum of 5 mm per metre running length!
•
The transition piece, to convert the air supply and flue gas discharge from
parallel to concentric, must be placed immediately before the roof or wall flue
terminal.
•
The duct length of the air supply must be approximately the same as that of
the flue gas discharge chimney.
•
Make sure that the chimney discharges into an area where this is permitted
for this category of water heater.
and
for example
installations.
Figure 3.7
Parallel connections on DR-RS 85 and 105
IMD-0252
a
air supply
b
flue gas discharge
a
b