Installation
18
Instruction manual DR-RS
3
is
3.3.1
Humidity and ambient temperature
The boiler room must be frost-free or be protected against frost.
shows the environmental conditions that must be adhered to, for correct
functioning of the electronics present in the water heater to be guaranteed.
3.3.2
Maximum floor loading
In connection with the water heater’s weight, take account of the maximum floor
loading, see
3.3.3
Working clearances
For access to the water heater it is recommended that the following
clearances are observed (see
):
•
AA: around the water heater’s control column and cleaning openings: 100
cm.
•
BB: around the water heater itself: 50 cm.
•
Above the water heater (room to replace the anodes):
-
100 cm if using fixed anodes or
-
50 cm if using flexible anodes.
Table 3.1
Humidity and ambient temperature specifications
Humidity and
ambient
temperature
Humidity
max. 90% RH at +40°C
Ambient temperature
Functional: 0
≤
t
≤
60°C
Table 3.2
Weight specifications related to maximum floor loading
Weight of the water heater filled with water
DR-RS 25
DR-RS 40
DR-RS 65
DR-RS 85
DR-RS 105
5
54
kg
557 kg 560 kg 585 kg 585 kg