Synchronization
option
Operator’s
Manual
Doosan reserves the right to change any of the above
Page 29 of 32
1910 NEL 3 P>>
Non essential load trip
1980 GB Ext. tripped
Generator breaker tripped from outside
2130 GB sync failure
Generator breaker synchronization failure
2140 MB sync failure
Mains breaker synchronization failure
2150 Phase seq error
Phase rotation different between mains/busbar and generator
2160 GB open fail
Generator breaker opening failure
2170 GB close fail
Generator breaker closing failure
2180 GB pos. fail
Generator breaker position unclear
2200 MB open fail
Mains breaker opening failure
2210 MB close fail
Mains breaker closing failure
2220 MB pos. fail
Mains breaker position unclear
2560 GOV reg. fail
Speed control not working
2630 Deload error
Deload not working
2680 AVR reg. fail
Voltage regulation not working
3410 Low fuel 47
Low fuel level Check in the software
3150 High cont. 84
High containment level
3160 Dig. Input 85
3170 GB tripped 86
Generator breaker tripped
4480 Low fuel warning
Low fuel warning
4490 fuel overfill
Fuel overfill
4540 Run feedb. fail
Running signal missing
4560 Hz/V failure
Voltage / frequency out of range
4570 Start failure
Doesn’t start
4580 Stop failure
Doesn’t stop
4960 U< aux. term. 1
Battery undervoltage
4970 U> aux. term. 1
Battery overvoltage
7520 Ext. Comm. Error
7570 EI comm. Error
CAN J1939 communication out of order
7580 EIC warning
CAN J1939 common warning
7590 EIC shutdown
CAN J1939 common shutdown
7600 EIC overspeed
CAN J1939 overspeed
7610 EIC coolant t. 1
CAN J1939 coolant temperature
7620 EIC coolant t. 2
CAN J1939 coolant temperature
7630 EIC oil press. 1
CAN J1939 oil pressure
7640 EIC oil press. 2
CAN J1939 oil pressure
7650 EIC oil temp. 1
CAN J1939 oil temperature
7660 EIC oil temp. 2
CAN J1939 oil temperature