2. OPERATION LOGIC

2.1. CONTROL COMMANDS

Control commands are sent by the connected devices to the corresponding terminals or by outer radio signals. Operation logic 

of the automatic devices depends on advanced menu setting (see table 3.2).

By default:
START command — step-by-step door control logic (two door leaves): opening — stop — closing.
PEDESTRIAN command — step-by-step pedestrian passage control logic (one door leaf): opening — stop — closing.
STOP command — stop of door movement.
OUT(n) — universal output control, where n is an output number.

OPERATION LOGIC

2.2.  DISPLAY INDICATION

The display consists of two eight-segment indicators. They indicate commutation of control board terminals and the state of the 

door, which the board controls.

Table 2.1. Display state

Indicator

Segment

Description

0

0

Lights up when the door is opening

1

Not used

2

Not used

3

Lights up when the door is closing

4

Not used

5

Not used

6

Lights up when the door is stopped

7

Not used

1

0

Lights up when PH_OP contact is closed

1

Lights up when the door is open

2

Lights up when the door is closed

3

Lights up when PH_CL contact is closed

4

Lights up when PED contact is closed

5

Lights up when START contact is closed

6

Lights up when EMRG contact is closed

7

Lights up when radio signals are transmitted by remote controls

2.3 SLEEP MODE

The control board switches to a sleep mode to save energy. If there are no commands for two minutes, the program turns off the 

display indication and power to photocells.

Pressing any control button on the board or giving control commands in sleep mode switches the control board to operation 

mode and executes a control command.

NOTE.

Display indication and photocell power supply are turned off in sleep mode.

Содержание PCB-SW 24

Страница 1: ...SW 24 Control Board 2 6 7 9 Electrical Connections 11 Operation Logic 15 Operator Programming 16 Remote Control Programming 18 DoorHan 06 2020 Programming Instructions v1 1 v1 1 Actual versions pcb v...

Страница 2: ...2 1 1 1...

Страница 3: ...X3 1 M1 1 2 X4 1 M2 2 2 X5 1 START 2 1 2 GND X6 1 PED 2 1 2 GND X7 1 EMRG 2 1 2 GND X8 1 PH_OP 2 PH_CL 3 GND 4 PH_PWR X9 1 S_LAMP 24 DC 2 GND X10 1 OUT_1 OUT1 24 DC 3 3 1 3 2 GND X11 1 E_LOCK 1 3 2 G...

Страница 4: ...4 1 3 3 24 DC 10 3...

Страница 5: ...5 24 DC 10...

Страница 6: ...6 2 2 1 3 2 n n 2 2 2 1 0 0 1 2 3 4 5 6 7 1 0 PH_OP 1 2 3 PH_CL 4 PED 5 START 6 EMRG 7 2 3...

Страница 7: ...3 10 4 15 5 20 6 25 7 30 8 35 9 40 2 P2 2 1 1 2 2 3 3 4 4 5 5 2 P3 Ln P4 0 1 10 2 20 3 30 4 60 5 90 6 120 7 180 8 360 9 420 0 P6 1000 00 3 2 START 15 30 1 2 3 1 P3 3 P Ln 1 4 5 1 6 12 2 7 8 2 9 2 10 1...

Страница 8: ...1 2 2 3 3 4 4 5 5 0 0 6 Y n n 0 7 Y n n 0 8 Y n n 0 9 Y n n 1 0 Y n n 1 1 OUT1 3 3 2 1 2 OUT1 0 0 1 10 2 20 3 30 4 60 5 90 6 120 7 180 8 360 9 420 0 1 3 Y n Y 1 4 1 0 1 5 2 0 1 6 3 0 1 7 4 0 1 8 Y n n...

Страница 9: ...9 3 4 9 8 P rE P rE 4 4 1 R 10 4 2 DOORHAN R 00 100 10 3 4 3 1 3 3 2 1 4 4 4 1 4 1 7 3 2 3 0 3 4 1 4 5 R 4 1 0 1 2 3 1...

Страница 10: ...10 4 4 DOORHAN 1 4 1 2 2 2 1 3 4 5 01 1 1 1 1 2 2 2 2 4 4 3 3...

Страница 11: ...CONNECTIONS 1 1 CONTROL UNIT SCHEMATIC DIAGRAM WARNING Cable wires shall be protected against contact with any rough and sharp parts All connections must be performed only when the power is off ELECTR...

Страница 12: ...ct their NO contacts in parallel 2 GND Safety devices Orange X7 1 EMRG Connection of normally closed NC devices Opening of these terminals constantly generates STOP command see section 2 1 When using...

Страница 13: ...l lock max current over 3A To connect an electromechanical lock use an intermediate relay with the following technical characteristics power supply voltage 24 VDC switching current 10 Connection of el...

Страница 14: ...ion of signal lamp Connection of auxiliary lighting To connect an auxiliary lighting use an intermediate relay with the following technical characteristics power supply voltage 24 VDC switching curren...

Страница 15: ...tor Segment Description 0 0 Lights up when the door is opening 1 Not used 2 Not used 3 Lights up when the door is closing 4 Not used 5 Not used 6 Lights up when the door is stopped 7 Not used 1 0 Ligh...

Страница 16: ...ection 3 1 and choose item P3 3 Press the P button The display will indicate Ln and leaf 1 will start to open 4 When deceleration command is given the door leaf will slow down and a short signal will...

Страница 17: ...0 0 sec 1 10 sec 2 20 sec 3 30 sec 4 60 sec 5 90 sec 6 120 sec 7 180 sec 8 360 sec 9 420 sec 0 1 3 Remote recording of remote controls Y function is on n function is off Y 1 4 Control command type of...

Страница 18: ...ll show the number of recorded remote controls Wait for automatic exit to the opera tion mode Repeat code recording for each remote control if you wish to record several remotes Thus up to 100 remote...

Страница 19: ...s and hold the button 2 of the programmed remote control 2 Without releasing the pressed button 2 press and hold the button 1 3 Release the pressed buttons 4 Press the programmed button the receiver w...

Страница 20: ...duct manufactured by our company and believe that you will be satisfied with its quality For information on purchasing distribution and servicing contact DoorHan central office at 120 Novaya street bl...

Отзывы: