background image

Installation, Operation and Maintenance manual

8

Downflo

®

 Evolution

g.  Do’s and don’ts

  Based upon several hazards a list of do’s and don’ts is given.

 

Perform a regular maintenance by disposing the dust in a regular fashion and 

inspecting the cleaning mechanism on a regular basis at least once a month.

 

Return the installation in its original state after maintenance (fixing, closing 

and bonding and grounding).

 

Check the grounding and bonding at least once a year.

 

The housing of the dust collector should never be changed or painted on the 

inside with a non-conducting coating.

 

Vents should never be blocked or painted.

 

Use the original bursting panel types only.

 

Do not alter the vent area or vent location.

 

Vent ducts should never be altered.

 

Do not tamper with explosion protection systems such as explosion 

suppression and explosion barriers as quick acting valve.

 

Use original equipment as filter cartridges, electrical equipment, rotary valves 

etc..

 

Do not use non-conductive plastic hoses and pipes.

 

Prevent goods and forbid personnel to be near such a vent.

 

Never open the dust collector during operation.

 

After emptying the receiver bin, fix it as in the original state.

 

Keep the working place clean.

 

For any changes in the dust collector, safety system, process, product or dust 

collector location consult the manufacturer.

h.  Applications having a risk of sparks and fires

1.  Good Housekeeping

Accumulation of potentially combustible dust, for example dust layers is 

considered a potential ignition source.  Failure to keep the dust collector 

clean and empty the hopper / dust bins regularly will increase the risk of fires 

and/or explosions.

2.  EU Directive 99/92/EC.

A reinforced and/or vented dust collector must be used when handling dusts 

that have the potential to form an explosive atmosphere.  If a non-reinforced 

and/or non vented dust collected is used on these applications then the end 

user must ensure an equivalent, secure, and fool proof basis of safety, which 

must be clearly documented in the end users Explosion Protection Document 

in line with Article 8 of EU Directive 99/92/EC.

3.  Self Heating Materials

Please note that some materials have the potential to self generate heat and 

hence to become an ignition source, that could result in a fire and / or an 

explosion.  For this reason ferrous and non-ferrous materials should not be 

extracted in to the same dust collector, as when combined they can create 

a violent thermite reaction that would ignite a fire and/or explosion.

Содержание Downflo Evolution DFE 2-12

Страница 1: ...Downflo Evolution Dust Collectors INSTALLATION OPERATION AND MAINTENANCE MANUAL DOC AM04643 01 rev 02 1118 ENGLISH MASTER VERSION...

Страница 2: ...ation 17 Field joining installation 20 Yoke venturi and filter installation 22 Platforms and ladders 23 Control box 24 Compressed air connection 24 Electrical connection 25 Solenoid valves 25 Inlet pl...

Страница 3: ...oining Detail C 22 Figure 11 Stationary platform 23 Figure 12 Inline filter view 24 Figure 13 Compressed air and component installation 25 Figure 14 Inlet plenum 26 Figure 15 High flow inlet plenum 27...

Страница 4: ...ns set out in the operation manual Any functional disorders especially those affecting safety should therefore be rectified immediately Ensure proper training is given to operators before start up The...

Страница 5: ...of Donaldson Torit dust collectors should Take every possible precaution to prevent a fire or explosion from occurring Consult with their insurance carrier or local authorities regarding the hazardou...

Страница 6: ...fety design of the collection system it s safety can be jeopardised However poor and or incorrect maintenance can also jeopardise the safety of the system b Hazards due to change of dust collector des...

Страница 7: ...t collector The filter cartridge porthole or another part of the housing access cover is not fixed correctly and may tear up during an explosion causing a flame jet or fireball Retrofitting metal duct...

Страница 8: ...it as in the original state Keep the working place clean For any changes in the dust collector safety system process product or dust collector location consult the manufacturer h Applications having a...

Страница 9: ...ute The spark trap does not guarantee complete elimination of sparks and does not preclude the possibility of fire or explosion Therefore system redundancy and complementary measures should be taken i...

Страница 10: ...our dust is always below the maximum Kst value defined for your dust collector type Technical and field support are available fromyour local Donaldson Torit representative or distributors to answer yo...

Страница 11: ...cting parts are grounded or bonded and connected to ground Internal coatings do not cause static hazards etc However these measures do not prevent ignition sources due to the process or outside influe...

Страница 12: ...of your dust to be collected has to be considerably lower in case of using vent ducts There also should be taken into account that due to the venting explosion the dust collector is subjected to a rea...

Страница 13: ...renches etc drill pipe sealant Delivery and inspection The dust collector is normally shipped by truck and should be checked for any damage that may have occurred during shipping Note that the burstin...

Страница 14: ...move all packing and strapping A crane is recommended for the unloading transport and installation of the dust collector Connect lifting sling to the lifting lugs with clevis pins and distribute loads...

Страница 15: ...oving crane 6 Apply sealant to hopper flange 7 Lift unit over leg and hopper assembly and lower slowly 8 Secure with bolts washers and nuts supplied 9 Apply sealant around inlet opening 10 Lift inlet...

Страница 16: ...valve OUTSIDE INSIDE CAP outlet DAP inlet dust collector blow off channel roof Figure 3 Inside installation Installation and assembly Anchor the dust collector to the foundations If any of the followi...

Страница 17: ...n the holes in the cross bracing on the rear side of the leg set 4 Recheck the position of the legs and cross bracing against figures Leg Bolting Details and Standard Leg Packs and the drawing 5 Join...

Страница 18: ...il D detail C detail E yoke filter cartridge panel thread forming screw gasket washer flat washer flat washer thread forming screw hex nut hex jam nut clean air plenum sealant detail outlet cover yoke...

Страница 19: ...s should match the number of holes provided in the base plates 10 Anchor diameter is typically 3 mm less than basebplate hole diameter 11 Corrosive environment or outdoor installation may require stai...

Страница 20: ...one side of the joint Follow the sealant pattern exactly as it is shown in Figure Field Joining Installation 4 Lift both units with cranes into position for joining Align the bolt holes in the flanges...

Страница 21: ...ion filter access cover see Figure 10 Yoke venturi and filter installation clean air plenum Figure 8 Field joining Detail A 7 Bolt the modules together using bolts washers and nuts as shown in Details...

Страница 22: ...oles in the tube sheet From the filter section have one person hold the yoke in position while another person installs a flat washer and hex nut on each yoke rod end from the clean air plenum Do not t...

Страница 23: ...ation and assembly instructions are shipped with the platform Dropping the platform can result in personal injury and or property damage Secure the platform assembly to the crane or forklift with stra...

Страница 24: ...ecaution is taken to avoid exceeding this pressure A relief safety valve is required if the connected supply can exceed this pressure A label is also attached to each manifold indicating manifold desi...

Страница 25: ...nameplate ratings of the fan motor Over amperage of manufacturer s recommended service of motor will cause damage If the fan is not premounted connect the fan motor to the control box according wirin...

Страница 26: ...sealant from opening 2 Apply sealant around the opening toward the inside edge of the bolt pattern 3 Align the holes on the inlet collar with the holes in the unit and secure using bolts and flat wash...

Страница 27: ...irty air plenum is used in applications requiring an air management module or when a single inlet serves multiple modules The extended dirty air plenum is supplied with standard service access panels...

Страница 28: ...n place a large quantity of water in the dust collector when activated Provide adequate drainage to remove water Excess water weight can cause the leg structure to collapse Fire control sprinklers are...

Страница 29: ...VENTING SIDE VENTING Figure 19 Bursting panel location 1 Remove protective shipping cover from top of collector underneath is the explosion panel positioned upside down 2 Inspect the panel and ensure...

Страница 30: ...cable and place into position The signalling unit including cable loop must be integrated into the threaded cable connected in such way that the loop is matching the other side of the explosion panel...

Страница 31: ...tion and Maintenance manual 31 Downflo Evolution vent panel angular frame signal cable signal cable thread nut cable loop thread angular frame signal cable cable loop Figure 21 Bursting panel and indi...

Страница 32: ...he burst indicator is a very sensitive device it is recommended to use always a isolation amplifier this gives the best guarantee forTROUBLE FREE electrical functioning of the indicator Typical wiring...

Страница 33: ...tral fire dispatching damper valve actuator if required Explosion panel detection device Explosion panel detection device 1 2 Figure 23 Typical wiring diagram hazardous area Dust outlet connection Whe...

Страница 34: ...Installation Operation and Maintenance manual 34 Downflo Evolution hopper bolt washer nut M10 bolt washer nut M10 gasket gasket rotary airlock transition piece Figure 24 Dust outlet connection...

Страница 35: ...t be checked The system must always be operating when the dust collector is operating Too much airflow can cause electrical failure of the fan motor or dramatically reduce the life of the filter cartr...

Страница 36: ...on the control box see separate manual Interval time normally to be set at 10 seconds Pulse time 100 milliseconds 6 Filter regulator Oil and or water is in the reservoir Switch off and bleed compresse...

Страница 37: ...anged at the same time Dust laden filters may be heavy and difficult to handle Provide appropriate means of access to replace filter cartridges safely in case no platform is installed Generally filter...

Страница 38: ...shape and yoke work together to ensure proper filter alignment during filter installation To assist with alignment an alignment mark at the top of the filter endcap non gasketed end must match with t...

Страница 39: ...Installation Operation and Maintenance manual 39 Downflo Evolution access cover cover knob yoke filter cartridge alignment marker alignment marker Figure 25 Exchanging filter cartridge...

Страница 40: ...rts Lubricate all gaskets and o rings with high quality silicone grease 1 Replace piston diaphragm assembly Locate bleedhole in piston diaphragm opposite to the valve inlet for the best performance 2...

Страница 41: ...allation Hopper discharge open Check that dust container is installed and properly sealed Damper control not adjusted properly Check airflow in duct Adjust damper control until proper airflow is achie...

Страница 42: ...ubing are damaged replace Solid State timer failure Using a voltmeter check supply voltage to the timer board Check and replace the fuse on the timer board if necessary If the fuse is good and input p...

Страница 43: ...ose connections Delta P arrow keys to not work Improper operation Press and hold one of the three setpoint keys to use arrow keys Programming keys disabled Remove the Program Disable jumper from Termi...

Страница 44: ...onditions set out in the Order Acknowledgment or relevant Scope of Delivery Failure to do so may compromise product reliability warranty and safety 5 Other items of equipment not supplied under the Sc...

Страница 45: ...r for the given dust explosion characteristics and collector arrangement as set out in the Scope of Delivery You should ensure that explosions are not allowed to propagate into the dust collector usin...

Страница 46: ...may be necessary to provide a facility to shut down the equipment in the event of an explosion where collectors are fitted with explosion relief panels The signal should be taken from the bursting pan...

Отзывы: