Fusion Hybrid Gas Condens
56
18
ADAPTING THE BOILER TO OTHER GAS TYPES
As described on the date plate, the module
Fusion Hybrid Gas Condens
is adjusted by default to run
on Natural Gas. In case of working with another type of gas, it will be necessary to change the gas.
To do this, access the
"Technical Menu"
and modify parameter
P02
.
Press the buttons
and
RESET
simultaneously until the circle is
completed to access the
"Technical Menu"
.
Select parameter
P02.
Select the parameter value
P02.
:
Natural Gas:
P02
= 0
Propane Gas:
P02
= 1
Press
RESET
to save the entered value.
Disconnect the module. Wait 20 seconds and reconnect it to confirm
that the gas has been made changed.
The screen displays the type of gas selected.
Adapting the gas type must be carried out by a qualified professional, authorised by
DOMUSA TEKNIK.
It is necessary to adjust the combustion after changing the gas.