Fusion Hybrid Gas Condens
30
7.2
Selecting the module setpoint temperature
To ensure a correct functioning of module, it is essential to select a heating temperature in the
module. The
boiler temperature
setting is carried out using the heating temperature adjustment
buttons (
and
)
The temperature appears on the display with the boiler temperature indicator. The adjustment of the
value is confirmed once the light of the screen is turned off.
The selectable boiler setpoint temperature range is 25-80ºC. The
Fusion Hybrid Gas Condens
module
is a condensing supporting module, so, In order to obtain maximum boiler performance and energy
savings, it is advisable to select a setpoint temperature of 60-70 ºC, providing this is permitted by the
heating system installed and the insulation conditions of your home.
In addition, the maximum module temperature can be limited to 47ºC through parameter
P21
,
activating the operation at low temperature.
7.3
Operating in “auto” mode
This will be the default operating mode of the
Fusion Hybrid Gas Condens module
. In this mode, the
operation will be managed by the
DUAL CLIMA
heat pump, as indicated in the instruction manual of
the heat pump according to configuration
P27 = 3
. See
“Configuration of auxiliary or supporting
energy sources”
.