INSTALLATION AND OPERATING INSTRUCTIONS 

 

FUSION HYBRID GAS CONDENS 

 

 

 

Содержание Fusion Hybrid Gas Condens

Страница 1: ...INSTALLATION AND OPERATING INSTRUCTIONS FUSION HYBRID GAS CONDENS ...

Страница 2: ...ilities or without experience and knowledge provided that they have been given appropriate supervision or training regarding the use of the device in a safe manner and that they understand the dangers involved Children should not play with the device Cleaning and maintenance should be carried out by the user should not be carried out by children without supervision Incorrect installation of these ...

Страница 3: ...24 6 STARTING UP THE BOILER 25 6 1 PRIOR WARNINGS 25 6 2 FILLING THE DOMESTIC HOT WATER TANK 25 6 3 FILLING THE HEATING CIRCUIT 25 6 4 GAS CONNECTION 25 6 5 ELECTRICAL CONNECTION 27 6 6 START UP 27 6 7 INSTALLATION HAND OVER 28 7 OPERATION 29 7 1 SWITCHING ON THE MODULE 29 7 2 SELECTING THE MODULE SETPOINT TEMPERATURE 30 7 3 OPERATING IN AUTO MODE 30 7 4 OPERATION WITH THE DHW SELECTOR 27 31 7 5 O...

Страница 4: ...ERLOCKS 50 15 1 TEMPERATURE SAFETY INTERLOCK 50 15 2 BURNER INTERLOCK 50 15 3 LOW PRESSURE INTERLOCK 50 16 MODULE MAINTENANCE 51 17 COMBUSTION ADJUSTMENT 53 17 1 MEASUREMENT VALUES 53 17 2 ADJUSTMENT PROCESS 54 18 ADAPTING THE BOILER TO OTHER GAS TYPES 56 19 ELECTRODE POSITION 57 20 CIRCULATING PUMP FLOW CURVES FOR HEATING 58 20 1 OPERATING STATUS OF THE CIRCULATION PUMP 58 21 DIAGRAMS AND MEASURE...

Страница 5: ...t or moderate damage if they are not avoided 1 2 Other symbols The following symbols are used in the instructions to draw your attention to important information This indicates a risk of damage due to breakdown and damage to persons and or property This indicates important additional information connected with correct module functioning 1 3 Safety warnings DANGER A gas leak could give rise to expl...

Страница 6: ...ains supply To do this you may separate or remove the fuses or cut off the mains supply firstly checking that the module is not still switched on Cut off the gas flow and make sure it is not restored until you give authorisation For propane boilers Before installing the boiler you must be sure that the gas tank has been drained As a rule the propane supplier is responsible for suitably draining th...

Страница 7: ...manufacturer shall not be considered liable under any circumstances for damage caused by unsuitable erroneous or improper use Improper installation or placement of equipment or accessories may cause electrocution short circuit leakage fire or other damage to the equipment Use only accessories or optional equipment manufactured by DOMUSA TEKNIK and specifically designed to work with the products pr...

Страница 8: ...ustion chamber 3 Primary manometer 4 Condensate siphon 5 3 way valve G1 6 3 way valve E1 7 Stainless steel DHW tank 8 DHW expansion vessel 9 Heating expansion vessel 10 Air inlet 11 Fan 12 Gas valve 13 Pump 14 3 way valve G1 15 DHW safety valve 16 Filling disconnector 17 Drain valve 18 Safety valve 19 Primary drain valve ...

Страница 9: ...used to decrease the desired boiler temperature 24 RESET button When the boiler is in lock out mode the RESET button is pressed to reset the lock out and restore Standard operation When modifying any of the parameters press the RESET button to complete the screen cycle and save the changes 25 Navigation increase button It is used to navigate through the different menus 26 Navigation decrease butto...

Страница 10: ...splays the module temperature 31 Heating mode operation display It indicates that the heating mode is activated 32 Heating demand display It flashes when there is heating demand 33 Comfort mode operation display It indicates that the comfort mode is activated 34 Reset request display It is displayed when the boiler needs to be reset 35 Digital manometer It displays the heating circuit pressure 36 ...

Страница 11: ...therefore hazardous The manufacturer shall not be considered liable under any circumstances for damage caused by unsuitable erroneous or unreasonable use Remove all the packaging and check that the contents are complete In case of doubt do not use the boiler Contact your supplier Keep the packaging elements out of reach of children as they can be dangerous When you no longer wish to use the module...

Страница 12: ...e minimum insulation thickness of the pipes should be 19 mm 0 039 W mK preferably comprising a closed cell insulation or a vapor barrier In outdoor areas exposed to the sun the insulation must be protected from the effects of degradation Drain valves and suitable devices should be fitted for the correct removal of air from the circuit during the filling stage A water filter must be installed in th...

Страница 13: ... parallel with the internal pump of the C4 machine To install this support pump please carefully follow the instructions belows First remove the support pump shim and its insulator In the place of the support pump shim 3 the support pump must be installed in the direction indicated in the figure If the Fusion Hybrid Gas Condens module is used in the cooling mode in addition to heating it is essent...

Страница 14: ...installation make sure that both the module and the Dual Clima heat pump are disconnected from the mains The Fusion Hybrid Gas Condens module features a series of motorised diverting valves and DHW and Heating support activation signals that are sensed by the DUAL CLIMA heat pump To do this electrical cables with a minimum section of 0 5 mm2 must be passed from the terminal strip of the DUAL CLIMA...

Страница 15: ...allel with the heat pump circulation pump between terminals C4L and N of the DUAL CLIMA heat pump These cables will be connected to the same terminals see figure Then these cables must be connected from the terminal strip of the DUAL CLIMA heat pump to the inside of the Fusion Hybrid Gas Condens module on terminals 28 and 29 Finally the support circulation pump C4 will be connected to terminals 26...

Страница 16: ...rovided following the steps indicated below 1 Access the module and remove the access cover to the tank sheath unscrewing the cover fixing nut 2 Insert the sensor into the bulb sheath provided in the tank Be sure to insert the sensor bulb until it stops against the bottom of the bulb sheath 3 Reassemble the access cover to the tank screwing the fixing nut 4 Connect the probe to the electrical conn...

Страница 17: ...carefully follow the following steps 1 Open the door of the Fusion Hybrid Gas Condens module and loosen the butterfly nuts located on the back of the door as indicated in the figure 2 Remove the support cap from the control panel moving it upwards 3 Remove the protective foam insert 4 Place the control panel removed from the DUAL CLIMA heat pump in its place 5 Reassemble the control panel cover in...

Страница 18: ...ion between 0 5 1 25 mm2 DANGER When carrying out any work on the electrical installation always make sure that both the module and the Dual Clima heat pump are disconnected from the mains Provide a sufficient length of cable inside the module in order to facilitate the opening of the front 4 8 Configuring the Heat Pump To properly configure and manage the operation of the DUAL CLIMA heat pump ple...

Страница 19: ...ion grilles 60 B Under a cornice or drainpipes 30 C Under a gutter 30 D Under a balcony 30 E From vertical or horizontal pipes 30 F From internal and external corners of the building 30 G From the ground roof or balconies 250 H From the side opposite to a marquee when no other outlet is installed 60 I From the wall with the pipe to the front wall 120 J From openings e g doors windows under the roo...

Страница 20: ...intake ducts The gas removal and air intake ducts must be protected from snow accumulation All accessories used for combustion product removal and air intake should be those supplied by DOMUSA TEKNIK However it is also possible for type C63 evacuations to use other manufacturers accessories for air inlet and gas evacuation as long as they are duly certified with their corresponding CE marking and ...

Страница 21: ... the coaxial removal system and the dual flow removal system Carefully study the diagrams representing the different types of removal and select the one that best suits the conditions of your installation To choose the removal accessories required for each installation please refer to the list of accessories on the DOMUSA TEKNIK price list Maximum total length Type Pipe diameter mm Orientation Max...

Страница 22: ...direction at around 2 3º thus preventing any water and condensation from dripping out Standard removal system Extended removal system Ø80 80 Max length A B C 1 x 90º elbow Max length 30 2 2 27 8 m Ø80 80 Max length A B C D E F 4 x 90º ebows 30 4 x 2 2 21 2 m 80 80 Cod CGAS000086 80 80 Cod CGAS000085 1 m horizontally arranged outlet kit 90º Elbow 80 80 Cod CGAS000084 1m duct 45º Elbow 80 80 Cod CGA...

Страница 23: ...oval pipe in a slightly upwardly inclined direction at around 2 3º thus preventing any water and condensation from dripping out Standard removal system Extended removal system 370mm min Ø80 80 Max length A B C 30 m Ø80 80 Max length A B C 2 x 45º elbows 30 2 x 1 4 27 2 m 80 80 Cod CGAS000086 80 80 Cod CGAS000085 1 m horizontally arranged outlet kit 90º Elbow 80 80 Cod CGAS000084 1m duct 45º Elbow ...

Страница 24: ...ndens module has a Ø80 dual duct system for combustion product removal and air intake To perform the removal of combustion products by means of a Ø60 100 or Ø80 125 coaxial system it must be used an adaptor kit supplied under request Coaxial tuve adaptor kit 80 125 Cod CGAS000221 Coaxial tuve adaptor kit 60 100 Cod CGAS000399 ...

Страница 25: ...ngth A 10 m Ø80 125 Maximum total length A 20 m Ø60 100 Max length A B 1x45º elbow 10 1 0 9 m Ø80 125 Max length A B 1x45º elbow 20 1 0 19m 60 100 Cod CGAS000375 80 125 Cod CGAS000322 60 100 Cod CGAS000318 80 125 Cod CGAS000082 60 100 Cod CGAS000317 80 125 Cod CGAS000081 1 m horizontally arranged outlet kit 90º coaxial elbow 60 100 Cod CGAS000316 80 125 Cod CGAS000080 1m coaxial duct 45º coaxial e...

Страница 26: ...5 Max length A B 1 x 45º elbow 22 1 21 m 60 100 Cod CGAS000380 80 125 Cod CGAS000315 60 100 Cod CGAS000314 80 125 Cod CGAS000082 60 100 Cod CGAS000317 80 125 Cod CGAS000081 1 m vertical arranged outlet kit 90º coaxial elbow 60 100 Cod CGAS000316 80 125 Cod CGAS000080 1 m coaxial duct 45º coaxial elbow Teja negra Cód CGAS000074 Flar roof Sloped roof Teja negra Cód CGAS000075 Coaxial tuve adaptor ki...

Страница 27: ... heat pump The air should also be bled from the rest of the installation using the air bleed valves provided The filling must be carried out slowly thereby facilitating air evacuation from the water circuit Once the installation is full close the disconnector valves The Fusion Hybrid Gas Condens module have a pressure sensor for controlling the pressure of the installation If it drops below 0 05 M...

Страница 28: ... propane a gas regulator suitable for this type of gas must be installed The connection and installation must be made in accordance with the applicable regulations and standards at the time of installation RIGLO DANGER Check the seal and draining of the entire installation as a gas leak could cause serious damage and or death If a propane fired boiler is installed in an interior room or compartmen...

Страница 29: ... place of installation 6 6 Start up In order for the warranty to be valid the module must be started up by an official DOMUSA TEKNIK Technical Assistance Service Before the start up process the followings must be complied with The module must be connected to the mains The installation must be filled with water the pressure must be between 0 1 and 0 15 MPa 1 to 1 5 bar Check the flue is correctly i...

Страница 30: ... Assistance Service will explain to the user how the module functions making any observations they consider relevant The installer is responsible for clearly explaining to the user the functioning of any control or regulation device forming part of the installation but not supplied with the module ...

Страница 31: ...menu of the DUAL CLIMA heat pump is at value 3 and that parameter P26 of the Technical menu of the DUAL CLIMA heat pump is at value 0 This ensures the correct management of the DUAL CLIMA heat pump with the supporting module 7 1 Switching on the module Once the power cable is connected to the power supply the Digital Display 20 will light up When the digital display 20 lights up the screen will di...

Страница 32: ...module is a condensing supporting module so In order to obtain maximum boiler performance and energy savings it is advisable to select a setpoint temperature of 60 70 ºC providing this is permitted by the heating system installed and the insulation conditions of your home In addition the maximum module temperature can be limited to 47ºC through parameter P21 activating the operation at low tempera...

Страница 33: ...ay of the temperature of the DHW tank becomes 69 in a fixed way this being not its real temperature as the complete management of the temperature of the DHW tank is performed by the supporting module 7 5 Operation with the Heating selector 28 For greater comfort in heating by means of the heating selector 28 it is possible to change the operating mode and energy source that will work on the heatin...

Страница 34: ...he heat pump while the support module manages the DHW demand 7 6 Operation with room thermostat The Fusion Hybrid Gas Condens module Avanttia NG boiler includes a connection prepared for the installation of a room chronothermostat or ambient room thermostat see Connection of the room thermostat which allows the management of the boiler s operation depending on the temperature inside your home Opti...

Страница 35: ...nfo Press the buttons and RESET simultaneously until the circle is completed Navigate through the AL In and Co parameters of the Info Menu with the DHW temperature adjustment buttons AL 0 AL 09 Last 10 errors of the boiler In 0 In 10 Information about the boiler Co 0 Co 06 Boiler counters To exit the Menu Info press the buttons and RESET simultaneously until the circle is completed ...

Страница 36: ...emperature ºC In 4 Flue gas sensor temperature ºC In 5 Reserved In 6 Return sensor temperature ºC In 7 Active boiler temperature setpoint ºC In 8 Current power level In 9 Reserved In 10 Water pressure sensor value bar In 11 Current fan power rpm x 100 Co 1 Hours of boiler operation h x 100 Co 2 Hours of burner operation h x 100 Co 3 Number of burner ignitions x 1000 Co 4 Number of boiler alarms Co...

Страница 37: ...y them depending on the desired performance characteristics in the home 9 1 Access to the Technical Menu To access the Technical Menu parameters follow the instructions below Press the buttons and RESET simultaneously until the circle is completed The display shows the parameter 01 and the value of the parameter 00 Please note Do not change this parameter Browse through the Technical Menu paramete...

Страница 38: ...eserved 0 100 P07 Reserved 0 80 18 P08 Maximum heating power adjustment 10 100 80 P09 Maximum DHW power adjustment 10 100 100 P10 Minimum heating power adjustment 0 P08 0 P11 Minimum boiler setpoint temperature adjustment ºC 0ºC P12 25 P12 Maximum boiler setpoint temperature adjustment ºC P11 8ºC 85 P13 Maximum boiler setpoint temperature adjustment ºC 05 65ºC 65 P14 Reserved 0 20 0 P15 Boiler pow...

Страница 39: ... 32 GN 31 GLP P34 Reserved 0 100 50 P35 Reserved 0 100 30 P36 Reserved 0 100 50 P37 Reserved 3 3 3 P38 Anti frost activation temperature adjustment ºC 0 10 5 P39 Heating pump post circulation 1 10 s 0 99 18 P40 Heating activation delay after DHW 1 10 s 0 60 12 P41 Reserved 0 1 0 P43 Reserved 0 30 0 P44 Reserved 0 1 1 P45 Anti legionnaire s disease function ºC 54 55 80 54 P46 Reserved 0 1 1 P47 Tim...

Страница 40: ...ween 3 and 16 minutes The recirculating pump operating mode can also be changed using parameter P48 The operating modes are as follows 1 Standard The circulation pump is activated when the heating demand is enabled and remains active until the end of the post circulation time 2 Continuous The circulation pump remains activated with the 3 way valve in the heating position If the DHW demand is enabl...

Страница 41: ...absence particularly in winter and in areas with a high risk of freezing weather it is recommended NOT to disconnect the module from the electrical mains or the gas supply in order to keep the anti frost function active and prevent possible bursts due to the water in the pipes freezing 12 4 Child protection When this function is activated the buttons are locked after 2 minutes have elapsed since t...

Страница 42: ...matic drain cover is open If the water pressure decreases during the purge procedure use the fill valve to fill the installation until the pressure is adequate The module must be in the OFF mode to perform the purge procedure Press RESET and simultaneously to complete the circle and perform the purge procedure The Air mode appears on the display The module starts the purge function During this pro...

Страница 43: ...odule is set in the test mode The test icon is displayed on the screen The Lo symbol indicates that the module is at minimum power Press until the circle is completed to switch to full power The Hi symbol indicates that the module is at maximum power Press the MODE and RESET buttons simultaneously until the circle is completed to exit the test mode The test mode ends at 30 minutes After this time ...

Страница 44: ...vate and deactivate the Heating mode so that the operating modes of the heating air conditioning system will be remotely and automatically managed AUTO mode from the place where the installed room thermostats are located Terminals 27 28 and 29 are supplied from the factory with a jumper wire connected to each of them so irrespective of the configuration of thermostats to be installed it will be ne...

Страница 45: ...ling mode and one for the common signal Depending on the status of each of the signals the Dual Clima heat pump will manage the Heating Cooling operating modes as follows Heating mode Cooling mode OFF Stand By temp reached TA 32 31 30 TA 32 31 30 TAC TAF 32 31 30 Terminals 27 28 and 29 are supplied from the factory with a jumper wire connected to each of them so in order to install this type of th...

Страница 46: ...ows Heating mode Cooling mode Cooling OFF Stand By temp reached Manual mode TAC TAF 32 31 30 TAC TAF 32 31 30 TAC TAF 32 31 30 TAC TAF 32 31 30 As indicated in the figure if the setpoint temperatures of the room thermostats are selected in such a way that both require simultaneous operation the electronic control of the heat pump will start to operate in Manual mode that is the Heating Cooling Ope...

Страница 47: ...should demand closed circuit signal when the room temperature is higher than the desired temperature setpoint temperature and in turn the thermostat connected to the heating input TAC should demand closed circuit signal when the room temperature is lower than the desired temperature setpoint temperature Terminals 27 28 and 29 are supplied from the factory with a jumper wire connected to each of th...

Страница 48: ...buttons and RESET simultaneously until the circle is completed to access the Technical Menu Select parameter P15 Increase the default number of the module Warning This value varies in each module model Press RESET until the circle is completed to register the value Wait 60 seconds Restore the value of parameter P15 Press RESET until the circle is completed to register the value WARNING Select para...

Страница 49: ... value of parameter P01 01 Press RESET until the circle is completed to register the value Press and RESET simultaneously until the circle is completed to exit the Technical Menu The default values are restored ...

Страница 50: ...d As shown in the following sequence to turn off the module press the MODE button until the circle is completed twice Press the MODE button until the circle is completed Once the radiator in the display 31 Heating mode operation display disapears it is necessary to press the MODE button one more time Press the MODE button until the circle is completed The module goes into the off mode To shut down...

Страница 51: ...nside the module on the lower left hand side of the heat exchanger Connect a flexible tube to this valve and run it to a drain After draining the module close the valve again and remove the flexible tube During the draining process it is recommended to switch off the module and disconnect it from the mains ...

Страница 52: ...it wait until the module temperature drops to 85ºC and press the RESET button 15 2 Burner interlock When this interlock occurs the code E06 and the error indicator symbol appear on the display The burner will switch off and stop heating the installation This occurs as a result of an anomaly in the burner or in the fuel installation To unlock press the RESET button 15 3 Low pressure interlock When ...

Страница 53: ...d combustion chamber The module does not require any special maintenance A yearly cleaning procedure at the end of the heating season will be enough The combustion chamber and burner should not be cleaned using chemical products or steel brushes After any cleaning operation has been carried out it is important to run several ignition cycles to check all the elements are operating correctly After c...

Страница 54: ...se for long periods of time we recommend draining all the water from the module Water characteristics In areas with water hardness of over 25 30ºF treated water must be used in the heating installation to avoid any scale deposits on the module It should be noted that even a few millimetres of scale will greatly reduce the boiler s heat conductivity causing a major drop in performance Treated water...

Страница 55: ...mode is available that sets the minimum Lo and maximum Hi power of the boiler for a correct combustion test See Service Mode Make sure that the air intake pipe of the module is fully closed and that the sealing is ensured during calibration NATURAL GAS G20 20 mbar CO2 O2 Maximum power P2 Hi Rated value 9 0 4 8 Tolerance 8 7 9 3 5 4 4 3 Ignition power P1 Rated value 9 0 4 9 Tolerance 8 7 9 3 5 4 4 ...

Страница 56: ... several ignitions Do not touch the module and do not change gas pressure during this time Once the module stabilises the P0 value Minimum power will appear on the display Check the O2 level and use the navigation buttons so that the O2 level is adjusted to the rated values indicated in the table of measurement values Press the button to adjust the heating temperature until the circle is completed...

Страница 57: ...play Check the O2 level and use the navigation buttons so that the O2 level is adjusted to the rated values indicated in the table of measurement values Press the MODE button until the circle is completed The P2 value is registered and the module exits the manual calibration mode ...

Страница 58: ...ess the buttons and RESET simultaneously until the circle is completed to access the Technical Menu Select parameter P02 Select the parameter value P02 Natural Gas P02 0 Propane Gas P02 1 Press RESET to save the entered value Disconnect the module Wait 20 seconds and reconnect it to confirm that the gas has been made changed The screen displays the type of gas selected Adapting the gas type must b...

Страница 59: ...57 19 ELECTRODE POSITION It is important that the electrode is properly located as indicated in the following images ...

Страница 60: ... red green The pump is ready for service but is not functioning The pump will start up again automatically once the error has been solved Low voltage U 160 V Overvoltage U 253 V Check the current supply 195 V U 253 V Pump overheating the engine temperature is too high Check the room and fluid temperature It flashes red The pump is out of order The pump is stopped The pump does not start up automat...

Страница 61: ...ng Return Ø22 1 M IBC Heat pump flow Ø22 1 M RBC Heat pump return Ø22 1 M EG Gas inlet 3 4 M ES Domestic cold water intake 3 4 M SS Domestic hot water outlet 3 4 M VSES DHW safety valve VSC Heating safety valve VC Condensation outlet SH Flue gas outlet Ø80 EA Air inlet Ø80 A B C D E F G H I J K L M N FUSION HYBRID GAS CONDENS 24 1010 1080 1160 1240 1320 1400 1480 1560 1820 560 280 610 1015 1080 FU...

Страница 62: ...36 97 57 97 69 97 36 97 57 50 30 C Efficiency at Maximum Heat Output 105 15 105 45 103 01 105 15 105 45 103 01 Efficiency at 30 load at 36 30 C 108 0 107 70 105 81 108 0 107 70 105 81 Heating Circuit Gas Type G20 G25 G31 G20 G25 G31 Maximum Heat Input Qn PCI kW 24 3 24 3 24 3 24 3 24 3 24 3 Minimum Heat Input Qn PCI kW 3 5 3 5 3 5 3 5 3 5 3 5 Maximum Heat Output 80 60 C Pn kW 23 7 23 7 23 7 23 7 2...

Страница 63: ...dex IP20 IP20 Exhaust Gas Circuit Gas Type G20 G25 G31 G20 G25 G31 Maximum flue Temperature ºC 78 78 Overheat securty flue Temperature ºC 100 100 NOx 6 6 Weighted Value of Nox mg k Wh 40 44 46 40 44 46 Flue Mass Flow Rate 60 80 C Qn Nominal Minimum g s 10 32 1 6 10 78 1 62 9 91 1 18 10 32 1 6 10 78 1 62 9 91 1 18 Flue Mass Flow Rate DHW 60 80 ºC Qn Nominal Minimum g s 14 01 14 04 12 71 14 01 14 04...

Страница 64: ...Fusion Hybrid Gas Condens 62 23 ELECRICAL DIAGRAM ...

Страница 65: ...e G1S Heat Pump G1S connection N Heat PUmp Neutral E1L E1L connection of heat pump DHW supporting connection E1N E1N connection of heat pump DHW supporting connection E2L E1L connection of heat pump Heating supporting connection E2N E2N connection of heat pump Heating supporting connection IN1 Input signal from the DHW probe to the heat pump Sacs BC DHW temperature probe C C connection in heat pum...

Страница 66: ...lue gas temperature sensor failure Press RESET Contact SAT if the error persists E 15 Fan error Press RESET Contact SAT if the error persists E 16 Heating return sensor failure Press RESET Contact SAT if the error persists E 17 Difference in heating sensor temperature Press RESET Contact SAT if the error persists E 19 Flow meter failure Press RESET Contact SAT if the error persists E 20 Excess of ...

Страница 67: ... SAT if the error persists E 88 Gas valve management error Press RESET Contact SAT if the error persists E 89 Combustion signal problems Press RESET Contact SAT if the error persists E 90 Inability to regulate combustion Press RESET Contact SAT if the error persists E 92 Air compensation active Press RESET Contact SAT if the error persists E 93 Inability to regulate combustion temporarily Press RE...

Страница 68: ... 24 160 2 CTOR000127 SCREW DIN 912 M8X25 3 RAVA000003 TANK RAVA000004 TANK 24 160 4 SCOB012548 DHW PIPE SCOB013136 Nº Code Description 5 CTOR000092 NUT DIN 934 M8 6 SCHA007431 BRIDGE COVER 7 CTOR000080 FLAT WASHER DIN 9021 M8 8 SEPO003143 COVER FOR ELLIPTIC COVER 9 COTR000006 O RING 108 X 7 EPDM 10 SCON000018 ELLIPTIC COVER 11 SPIN000018 EXPANSION VESSEL FIXING ...

Страница 69: ...FRAME SCHA014272 FRONT SIDE FRAME 160 4 CTOR000117 SCREW DIN 7981 4 8X19 5 SCHA013520 SIDE FRAME SCHA014309 SIDE FRAME 160 6 CTOR000087 SCREW DIN 7981 4 8X9 5 Nº Code Description 7 SCHA013308 RIGIDITY SCHA014250 RIGIDITY 24 160 8 SCHA013374 RIGIDITY FIXING 9 CTOR000077 SCREW DIN 7504 4 2X13 10 SEPO003168 TANK COVER SEPO003256 TANK COVER 24 160 11 SEPO003169 TOP TANK COVER SEPO003257 12 CTOR000073 ...

Страница 70: ...52 PRESSURE TRANSDUCER 19 CFOV000159 GASKET 15X8X2 20 CELC000531 SONDA IDA 21 CFOV000160 GASKET 1 2 22 SCOB013098 HEATING FLOW PIPE 23 SCOB013099 BY PASS PIPE 24 CFER000107 WASHER EPDM 18 5 x 14 x2 Nº Code Description 25 CVAL000074 BY PASS VALVE 26 CFOL000008 COUNTER THREAD BUTTRESS 27 SCHA013205 MIXER CLIP 28 CGAS000388 GAS NOZZLE 29 CCOB000090 GAS PIPE 30 CGAS000392 GAS VALVE 31 CTOR000239 SCREW...

Страница 71: ...ER 1 6 CFOL000074 SLIDING NUT WITH FLANGE 1 7 CFER000008 RED PLUG 1 8 SCHA006693 REAR WASHER 9 CFOL000073 SLIDING NUT WITH FLANGE 10 CFER000007 RED PLUG 11 CFER000331 YELLOW PLUG Burner components FUSION HYBRID GAS Nº Code Description 1 CGAS000404 INSULATION PANEL CLIP 2 CGAS000405 INSULATION PANEL 3 CGAS000397 BURNER 24 kW 4 CGAS000406 DOOR JOINT 5 CAIS000029 BURNER GASKET Nº Code Description 6 C...

Страница 72: ...EAT PUMP FLOW PIPE SCOB013182 HEAT PUMP FLOW PIPE 24 160 SAIS000467 SCOB013085 INSULATION SAIS000506 SCOB013182 INSULATION 16 SCON002288 SIPHON 17 STUR000061 SIPHON CONNECTION Nº Code Description 18 STUR000209 DISCHARGE TUBE COMPLETE 19 STUR000203 WATER COLLECTION TUBE 20 CTOR000073 SCREW 3 9X9 5 21 SCOB013053 SPOOL SAIS000468 SCOB013053 INSULATION 22 CFOL000007 BRASS NIPPLE 1 23 CVAL000009 CHECK ...

Страница 73: ...BOW 3 4 10 CFOL000009 BRASS NIPPLE 1 2X3 4 11 CFOL000006 BRASS NIPPLE 3 4 12 CFOV000158 GASKET 3 4 13 CVAL000010 SAFETY VALVE 7KG 1 2 Nº Code Description 14 CFOL000017 CONNECTING TUBE NIPPLE 1 2 15 CFER000231 CLAMP 8 16 16 STUR000194 FLEXIBLE PVC TUBE 17 CFOL000094 BRASS CROSS 1 2 18 CFOL000005 BRASS NIPPLE 1 2 19 CVAL000017 SAFETY VALVE 1 2 20 CFOV000024 DRAIN VALVE 21 CFOL000032 BRASS FEMALE TEE...

Страница 74: ...Fusion Hybrid Gas Condens 72 FUSION HYBRID GAS 1 2 3 4 5 6 7 8 9 10 11 12 15 14 13 16 17 18 19 15 14 20 22 23 22 23 24 27 29 17 28 31 30 30 29 32 33 34 21 26 22 25 ...

Страница 75: ...N 7985 M5X10 14 CTOE000355 SMALL CLIP PIVOT 15 CTOR000089 NUT DIN 6923 M4 Nº Code Description 16 CFER000317 MOBILE PART HINGE 17 CTOR000253 SCREW DIN 7991 M6X16 18 SEPO003162 HINGE SUPPORT 19 CFER000221 CONCEALED HINGE 20 CFER000126 TORSION CLAMP 21 CFER000261 SRV SPRING CLOSURE 22 CTOR000073 SCREW 3 9X9 5 23 CFER000138 WHITE PLUG 24 SCON002234 FLUE GAS OUTLET AND AIR INPUT 25 CGAS000410 GASKET FL...

Страница 76: ...ING 10 CTOR000091 SCREW 3 2X9 5 11 CELC000041 ROTARY COMMUTATOR 12 SCON002398 DRAWER SCON002479 DRAWER 24 160 13 SCON002400 TERMINAL STRIP 14 RELEAVA005 SUPPLY BOARD 15 CTOR000099 SCREW DIN 7985 M3X4 Nº Code Description 16 CELC000547 THERMOSTAT 60º 17 CTOR000193 SCREW DIN 7985 M4X5 18 CELC000036 WEIDMULLER TERMINAL STRIP 3 19 CELC000042 WEIDMULLER TERMINAL STRIP 12 20 CTOR000221 SCREW DIN 7981 3 2...

Страница 77: ...PWM CABLE 6 CELC000509 GAS VALVE CABLE 7 SOPE000224 LOW VOLTAGE CABLE 8 SOPE000225 COMMUNICATION CABLE 9 CELC000529 CARD COMMUNICATION CABLE Nº Code Description 10 CELC000530 IGNITION CABLE 11 CELC000537 COMBUSTION CHAMBER EARTH CABLE 12 CELC000538 CARD EARTH CABLE 13 CMAZ000147 FUSION HYBRID GAS HARNESS 14 CQUE000036 BRIDGE 15 CELC000521 V3V VALVE CONNECTION CABLE 16 CELC000552 BLUE BRIDGE ...

Страница 78: ...Fusion Hybrid Gas Condens 76 NOTES ...

Страница 79: ...77 NOTES ...