Domotec.ch | 23
P
ARAMETER OVERVIEW
:
PARA-
METER
Operation
Mode:
PiPE
Operation
Mode:
Air = PASC
Description
Factory
settings
Parameters
SP1
SET
Temperature
+3°C
0°C ... +90°C
SP2
Operation
mode
selection
-----
PiPE / Air
SP3
Lowest
ambient
temperature
-
20°C
-
30°C ... 0°C
SP4
Average pipe
diameter level
SP5
Heater
operation in
sensor failure
mode
ON
ON/OFF
SP6
Heater
operation
via external
contactor
No
Yes/No
SP7
Hysteresis
1 K
0 K ... 5 K
SP8
Low
temperature
alarm
0°C
OFF/–40°C
SP9
Higher
temperature
alarm
+65°C
OFF/+65°C
SP10
Alarm sound
status
ON
ON/OFF
SP11
TEST program
OFF
ON/OFF
SP12
KEY LOCK –
Pass code
OFF
OFF/code
036
SP13
RESET
000
Code 012
M
ESSAGES
:
Error
Code
Error
description
Remedy
Er 2.1 Sensor open
1.
Check sensor cable connection
2.
Verify operation of unit
3.
Replace unit if cable ok
and
error still exists
Er 2.2 Sensor short
1.
Check sensor connection
2.
Replace sensor
3.
Replace unit if sensor ok
and
error still exists
Er 3.1
High
temperature
alarm
1. Verify heating system and sensor position
2. Verify menu settings of high temperature alarm
Er 4.1
Low
temperature
alarm
1. Verify heating system and sensor position
2. Verify menu settings of low temperature alarm
Er 6.x Internal error
Replace unit
Error codes will be displayed after a time delay of 10 min.
02
≥
DN
25/1"
01 = Ø
<DN
25 / 1"
02 = Ø
≥
DN25 / 1"
03 = Ø
≥
DN50 / 2"
Содержание Frost-Control DHB 360 C
Страница 3: ...Domotec ch 3 1 2 150 mm 3 Frost Control INSTALLATION INSTALLAZIONE ...
Страница 4: ...4 Domotec ch 4 5 1 2 A B C 6 ...
Страница 5: ...Domotec ch 5 7 8 9 L L L N AC 230 V 37 ...
Страница 6: ...6 Domotec ch 10 11 12 CLICK ...