Technical description

PBC110

8

When the battery is connected and AC power is on, the charger will automatically 
diagnose the battery condition and determine if the battery should engage soft start 
charging or go directly into bulk charging.

Stage

Charging rate 
indicator

Description

Soft start charging

20 %

The battery voltage will increase slowly. When 
it reaches 10.5 V, the charger goes into bulk 
charging. 
If the battery voltage cannot reach 10.5 V within 
two hours, a battery fault is signalled.

Bulk charging

80 %

The battery will be charged up to about 80 %. 
The charger delivers an almost constant current 
of 2 A/5 A/10 A until the battery voltage 
reaches the set value.

Absorption 
charging

80 %

The battery will be charged up to about 95 %. 
The charging current tapers and the charging 
voltage are kept constant at the set value.

Battery analysis

100 % flashing

The charging is interrupted for a short period to 
measure battery voltage. 
If the battery voltage falls too quickly, the bat-
tery is probably faulty.

Recondition 
charging

100 % flashing

Recondition charging balances the batteries 
cells. 
It is used for older batteries or if low voltage is 
detected.

Float charging

100 % 

The float mode allows the charger to effectively 
be left connected to the battery; it safely keeps 
the battery fully charged, ready for use.

Maintenance 
pulse charging

100 % 

This program engages a special charging 
waveform and monitors the battery voltage. If 
the battery voltage drops, a special pulse will 
keep the battery in the optimal state. If the bat-
tery voltage drops significantly, the battery 
charger will switch to bulk charging. 
The maintenance mode allows the charger to 
stay connected to the battery long term. To 
ensure optimal battery performance please 
check the electrolyte level regularly.

Содержание PBC110

Страница 1: ...PBC110 Battery Charger Operating manual EN POWER CONTROL CHARGERS PORTABLE...

Страница 2: ...mbols 2 2 General safety instructions 3 3 Intended use 6 4 Scope of delivery 7 5 Technical description 7 6 Settings 11 7 Charging 12 8 Maintaining and cleaning 14 9 Trouble shooting 15 10 Warranty 16...

Страница 3: ...on when using electrical devices to protect against Electric shock Fire hazards Injury 2 1 General safety D DANGER In the event of fire use a fire extinguisher which is suitable for electrical devices...

Страница 4: ...2 Safety when installing the device D DANGER Never mount the device anywhere where there is a risk of gas or dust explosion CAUTION Ensure that the device is stable The device must be set up in such...

Страница 5: ...upply line and the plug are dry Always disconnect the power supply when working on the device A NOTICE Make sure the air inlets and outlets of the device are not covered Ensure good ventilation 2 4 Sa...

Страница 6: ...charge desulfate and maintain 12V lead acid GEL WET AGM and LiFePO4 batteries with a capacity of 6 Ah to 200 Ah maintenance up to 240 Ah It must not be used on other battery types The battery charger...

Страница 7: ...detects an output short circuit it will stop delivering output current The red LED will be turned on Internal overheat protection The battery charger is equipped with a temperature sensor When the te...

Страница 8: ...oltage are kept constant at the set value Battery analysis 100 flashing The charging is interrupted for a short period to measure battery voltage If the battery voltage falls too quickly the bat tery...

Страница 9: ...nected when no battery is connected the battery charger goes automatically into ECO mode to minimize power consumption 5 4 Parts and connections No in fig 1 Description 1 Output lead with clips 2 Batt...

Страница 10: ...10 10 5 5 Controls No in fig 2 Explanation function 1 Charging rate indicator 2 A 5 A 10 A 2 Battery type indicator LiFePO4 AGM GEL 3 Battery status of charge indicator 4 Battery type selector 5 Charg...

Страница 11: ...ng the battery Fault ON red Output shortcircuit or battery connected with reverse polarity Fault Flash red Battery is faulty charging timed out ON green Both LEDs lighting together indicates the batte...

Страница 12: ...way between the upper and lower fill lines Check the battery label for battery type and capacity Only charge 12 V lead acid GEL WET AGM or LiFePO4 batteries Ensure that the battery charger is not con...

Страница 13: ...clip of the battery charger to the negative battery terminal Then connect the red clip of the battery charger to the vehicle s chassis and far away from the fuel line 7 3 Connect the battery charger...

Страница 14: ...f way between the upper and lower fill lines 8 Maintaining and cleaning A NOTICE Do not use any sharp or hard objects for cleaning since they may damage the device Disconnect the device from mains pow...

Страница 15: ...g termi nals are connected to the correct polarity If not remake the con nection to the battery properly No charging current Fault LED is flashing Battery is severely sulfated Overheat protection mode...

Страница 16: ...ther reasonably foreseeable loss or damage You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure...

Страница 17: ...tages Input 220 240 VAC 50 60 Hz Output voltage 12 V Output current 2 5 10 A Output voltage at no load 0 5 V Minimum start voltage 6 0 V Temperature compensated 24 mV C Size L W H 205 90 52 mm Net wei...

Страница 18: ...e contents of this manual is pro tected by copyright and design law The underlying technical design and the prod ucts contained herein may be protected by design patent or be patent pending The tradem...

Страница 19: ...EN PBC110 Copyright 19...

Страница 20: ...YOUR LOCAL SALES OFFICE dometic 0 0 s YOUR LOCAL DEALER dometic com dealer YOUR LOCAL SUPPORT dometic com contact dometic com 1 01 1 0 4 0 1 1 2 2 1 2 9 0 DOMETIC GROUP AB 3E 0 1 4 4445103028 02 2020...

Отзывы: