When the battery is connected and AC power is on, the charger will automatically
diagnose the battery condition and determine if the battery should engage soft start
charging or go directly into bulk charging.
Stage
Charging rate
indicator
Description
Soft start charging
20 %
The battery voltage will increase slowly. When
it reaches 10.5 V, the charger goes into bulk
charging.
If the battery voltage cannot reach 10.5 V within
two hours, a battery fault is signalled.
Bulk charging
80 %
The battery will be charged up to about 80 %.
The charger delivers an almost constant current
of 2 A/5 A/10 A until the battery voltage
reaches the set value.
Absorption
charging
80 %
The battery will be charged up to about 95 %.
The charging current tapers and the charging
voltage are kept constant at the set value.
Battery analysis
100 % flashing
The charging is interrupted for a short period to
measure battery voltage.
If the battery voltage falls too quickly, the bat-
tery is probably faulty.
Recondition
charging
100 % flashing
Recondition charging balances the batteries
cells.
It is used for older batteries or if low voltage is
detected.
Float charging
100 %
The float mode allows the charger to effectively
be left connected to the battery; it safely keeps
the battery fully charged, ready for use.
Maintenance
pulse charging
100 %
This program engages a special charging
waveform and monitors the battery voltage. If
the battery voltage drops, a special pulse will
keep the battery in the optimal state. If the bat-
tery voltage drops significantly, the battery
charger will switch to bulk charging.
The maintenance mode allows the charger to
stay connected to the battery long term. To
ensure optimal battery performance please
check the electrolyte level regularly.