 WARNING 

CARBON MONOXIDE POISONING 

Properly seal vent assembly to prevent carbon monoxide from entering 
coach. 

DO NOT draw combustion air from living area.

DO NOT vent exhaust air into the living area or an enclosed porch.

 WARNING 

CARBON MONOXIDE POISONING 

Furnace  must  be  installed  and  vented  according  to  these
instructions.

Improper 

installation, 

adjustment,

alteration, 

service 

or 

maintenance can cause injury or property damage. 

Improper installation location may cause furnace to produce negative 
pressure, affecting combustion air or venting of other appliances. 

 WARNING 

CARBON MONOXIDE POISONING 

Properly  seal  door  to  prevent  carbon  monoxide  from  entering
coach.

 

Properly adjust draft cap to prevent carbon monoxide from entering
coach.

 

MODEL NOMENCLATURE 

AF 

25 

Dometic

 

Furnace 

Cabinet 

Size 

Voltage 

Input 

Btu/hr 

Gas 

Type 

Gas 

Location 

Valve 

Model 

Rev 

AF 

M=medium 

D=12 

VDC 

16K 

1=LP 

1=door 

1=Single 

20K 

2=LD (small 

vent) 

25K 

3=door w/ 

rear gas 

fitting 

30K 

4=door 

w/pigtail 

35K 

5=door w/ 

pigtail & rear 

gas fitting 

Contents 

MODEL NOMENCLATURE

 ....................................................... 2

MODEL SPECIFICATIONS

 ....................................................... 2

DIMENSIONS

 ................................................................................... 2

INSTALLATION AND SAFETY CODESError! Bookmark not defined.

INSTALLATION CODES

 ................... 

Error! Bookmark not defined.

GENERAL FURNACE INSTALLATIONS

 .................................. 2

CLEARANCE TO COMBUSTIBLES:

 ............................................... 3

REQUIRED DUCTING

 ...................................................................... 3

REQUIRED DISCHARGE

 ................................................................. 3

FLEXIBLE DUCTING

 

4

AIR FLOW CHECK

 ........................................................................... 4

FURNACE INSTALLATION

 ....................................................... 4

SIDEWALL CUTOUT

 ....................................................................... 4

SMALL VENT INSTALLATION

 ................................................. 5

STANDARD DOOR INSTALLATION

 ........................................ 5

FLUSH DOOR INSTALLATION

 ................................................ 6

HARD DUCT SYSTEMS

 ............................................................ 6

FLOOR DISCHARGE CUTOUTS

 ..................................................... 6

GAS CONNECTION

 .................................................................. 6

ELECTRICAL CONNECTIONS

 ................................................. 7

THERMOSTAT INSTALLATION

 ............................................... 7

OPERATING INSTRUCTIONS

 .................................................. 7

TO SHUT DOWN UNIT

 ..................................................................... 8

IGNITION CONTROL DIAGNOSTIC CODES

 ............................ 8

WIRING AND LADDER DIAGRAM

 ............................................ 8

MODEL SPECIFICATIONS 

Models 

AFMD16 

AFMD20 

AFMD25 

AFMD30 

AFMD35 

Type of 

Gas 

LP 

Propane 

LP 

Propane 

LP 

Propane 

LP 

Propane 

LP 

Propane 

BTU Input 

16,000 

20,000 

25,000 

30,000 

34,000 

BTU 

Output 

12,160 

15,200 

19,000 

22,800 

25,840 

Duct 

Static 

Pressure 

.20” WC 

.10” WC 

.10” WC 

.10” WC 

.10” WC 

Amperage 

(AMPS) 

4.2* 

4.2* 

7.5* 

7.5* 

11.1* 

Watts 

50 

50 

90 

90 

132 

Power 

Supply 

(Volt DC) 

12 

12 

12 

12 

12 

Return Air 

80 in

2

 

80 in

2

 

80 in

2

 

80 in

2

 

80 in

2

 

Minimum 

Return Air 

65 in

2

 

65 in

2

 

65 in

2

 

65 in

2

 

65 in

2

 

(WC = 

WATER

 COLUMN) 

*

15 AMP DECATATED CIRCUIT FOR FURNACE

DIMENSIONS

 

Approx. 

Width 

Height 

Depth 

Weight 

Casing 

16-

1/2”

7” 

20” 

Furnace 

26lbs. 

Boxed 

29 lbs. 

STD Door 

19-

1/4”

9-

3/4”

3/4” 

FLUSH 

DOOR 

19-

3/8”

10-

1/4”

7/32” 

Vent LD 

5-1/2

5-1/2

1-

1/16”

INSTALLATION AND SAFETY CODES 

USA and Canada 

– follow all applicable state and local codes  in

the absence of local codes or regulations, refer to current
standards of:

ANSI/NFPA 1192 Recreational Vehicles Code and ANSI/RVIA LV
Low Voltage Systems in Conversion and Recreational Vehicles

CSA Z240.4, Gas-Equipped Recreational Vehicles and Mobile
Housing

National Fuel Gas Code ANSI Z223.1 and/or CAN/CGA B149

This furnace must be installed in accordance with the
manufacturer’s instructions and the manufactured Home
Construction and Safety Standard, Title 24 CFR, part 3280, or
when such standard is not applicable, the Standard for
Manufactured Home Installations. (Manufactured Home Sites,
Communities and Set-Ups), ANSI A255.1 and/or CAN/CSA-Z240
MH Series M92 Canadian Standard for Mobile Homes.”

ANSI A 255.1 and/or CAN/CSA-Z240.6.2 MH Series, Mobile
Homes

Ground National Electrical Code ANSI/NFPA 70 and/or CSA
C22.1, Part 1

Park Trailers ANSI 1195

GENERAL FURNACE INSTALLATIONS 

All models can be installed in either a horizontal or vertical
mounting position horizontal installed units have the gas line
positioned on top or rear, vertical installed units must have the
vent located at the floor and gas line at right side and rear.

Always install furnace through an exterior wall.

DO NOT install furnace near tilt-out rooms, slide-outs, doors or
other projection that could obstruct furnace exhaust.

Locate furnace near midpoint of coach for single furnace
applications.

Installation must provide accessibility if any repairs are necessary
to the furnace. Failure to meet this requirement will create
additional labor costs that will be the responsibility of the installer.

Содержание AFM Series

Страница 1: ...nt furnace with venting system serving another appliance DO NOT vent furnace to an outside enclosed porch area DO NOT use for temporary heating of buildings or structures under construction Protect bu...

Страница 2: ...20 WC 10 WC 10 WC 10 WC 10 WC Amperage AMPS 4 2 4 2 7 5 7 5 11 1 Watts 50 50 90 90 132 Power Supply Volt DC 12 12 12 12 12 Return Air 80 in2 80 in2 80 in2 80 in2 80 in2 Minimum Return Air 65 in2 65 i...

Страница 3: ...h 2 clearance full length of the unit Furnace efficiency rating is a thermal rating determined under continuous operating conditions independent of any installation Efficiency rate is given at 76 mini...

Страница 4: ...ow for each BTU size If readings are below the table values airflow can be improved by adding ducts or reducing eliminating restrictions in the system 16 000 20 000 25 000 30 000 35 000 3000 fpm 3000...

Страница 5: ...t assembly is important for proper exhausting of fumes and proper function of furnace NOTE RTV type sealant must be applied to the bezel and casing at the bottom right side to prevent possible water w...

Страница 6: ...TOUTS 1 Remove bottom discharge plate or side these ducting option must be connected to a floor ducting system 2 The drawing shows the use of a gasket and plenum plate for attaching furnace to the flo...

Страница 7: ...o furnace in parallel with battery This provides consistent voltage to furnace increasing component life filtering power surges and AC spikes All units are supplied with a power switch which is to be...

Страница 8: ...ghts the burner DO NOT try to light the burner by hand 7 If burner does not light repeat Steps 1 through 5 8 If after three 3 attempts with no ignition shut down the unit and contact your dealer or a...

Страница 9: ...9...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...13 Figure 1 Large Paddle Kit 31093 Figure 2 Small Paddle Kit 31094 Figure 3 Valve Kit 31098 Figure 4 Valve Kit 31096 Figure 5 Valve Kit 31097 Figure 6 Electrode Adjustment...

Страница 14: ...ni aucune autre personne n a le pouvoir de changer de modifier ou de supprimer les instructions contenues dans ce manuel AVERTISSEMENT viter les blessures et la mort Une mauvaise installation adaptat...

Страница 15: ...N 18 Porte STANDARD INSTALLATION 18 Rincer la porte INSTALLATION 19 SYST MES DE CONDUITS DUR 19 D charge de plancher D coupe 19 RACCORDEMENT AU GAZ 19 BRANCHEMENTS LECTRIQUES 20 INSTALLATION DE THERMO...

Страница 16: ...les conduits et conduits inad quat pourraient causer chauffage m diocre et ou faire du v lo sur la limite de temp rature lev e d gagements Retour au d but C t s Arri re Bas de visser des t tes Souffl...

Страница 17: ...uter directement aux points de vente nombre de maintien des angles des virages au minimum Cesser les plaque knockout prises d sir es Si un coup de gr ce est supprim accidentellement couvercles peuvent...

Страница 18: ...3 1 2 po de diam tre trou dans la paroi lat rale de l entra neur Installateur devra prot ger le four et les composants des outils de construction et des d bris lors de l installation 3 Insert fournea...

Страница 19: ...ur c t 5 Connecter le tuyau de gaz la valve et branchez la fiche de ligne de gaz dans l ouverture du bo tier 6 Le cadre de la porte doit serr contre le flanc ext rieur pour viter les fuites d eau 7 En...

Страница 20: ...Type 20 3 Stranded only 18 6 Stranded only 16 8 Stranded only 14 15 Stranded only 12 20 Stranded only 10 30 Stranded only 8 40 Stranded only 6 55 Stranded only 4 75 Stranded only 2 100 Stranded only...

Страница 21: ...rr te avant l allumage du cycle arr tez d unit et contactez votre revendeur ou une Agence de service local v hicules de loisir 3 Apr s 1 minute le ventilateur peut tre ex cut pas cette poque d placez...

Отзывы: