Proper duct installation is critical to proper operation of the
furnace. When installing ducts, use materials rated for continuous
use at 200°F.

Each 4-inch duct opening provides 12 in

2

 of discharge area.

Provide an extra 12 in

2

 of non-closeable duct discharge area for

each closeable register used.

Ducting into dead air space with no return air, such as holding
tank areas, does not count toward achieving minimum discharge
requirements.

Adjust ducting installation to obtain an air temperature rise of
100°F-130°F. Also see air flow check section.

FLEXIBLE DUCTING 

Follow ducting configurations shown.

Avoid sharp bends, deep sags or crushed ducts.

Stretch all ducts thoroughly and run them directly to outlets,
keeping number of angles of bends to a minimum.

Remove knockout plate from desired outlets. If a knockout is
removed accidently cover plates can be purchased.

Unused knockouts MUST be covered.

Attach a duct adapter by inserting flange over casing hole, locking
the tab into casing slot and turning adapter 90°

Attach and secure four-inch flexible duct to adapter(s)

Run duct(s) to desired location within RV, secure to register(s)

AIR FLOW CHECK 

Appliance is tested to a temperature rise as specified on the
Rating Plate. After installation of the furnace and duct system is
completed, adjustment to obtain proper temperature rise should
be made.

The table below is a reference to maintain maximum operation of
the appliance when checking temperature rise is not possible.
Airflow measurements made at each registers the total reading
should not be less than what is shown in table below for each
BTU size.

If readings are below the table values airflow can be improved by
adding ducts or reducing/eliminating restrictions in the system.

16,000 

20,000 

25,000 

30,000 

35,000 

3000 fpm 

3000 fpm 

3500 fpm 

4000 fpm 

5500 fpm 

 Total fpm= feet per minute readings 

FURNACE INSTALLATION 

Remove furnace from box

Remove vent assembly supplied with furnace

DO NOT mix assemblies with other units, each model has a
specific vent baffle size to operate correctly, see sticker on vent
assembly.

Remove knockouts in locations that will be used and install
adapters.

The furnace should always be installed level (front to back, side to
side) to prevent water build up into the interior of the vent area.

If units are installed using the small outside vent system, access
to the inside of the coach must be provided directly in front of the
unit to remove for servicing suggested opening size 17

” wide by

8.5

” height.

Secure unit with two brackets and screws provided at the rear of
the unit through holes provided.

Attach flexible ducting over duct adapters and secure.

Run ducting to locations keeping bends and excess ducting to a
minimum and secure to registers.

Connect wiring to furnace see wiring connection section.

Connect gas line see gas connection section.

SIDEWALL CUTOUT 

Maximum exterior wall thickness 0” to 2-1/2”. Optional vent kit  can be 
purchased to extend the vent to a 3” wall thickness on small vent 
installations. 

WALL CUTOUTS  

(Standard door square corner 

and Flush Door requires 3/4” radius 

corners) 

Side Wall Cutout 

Small Vent 

3-1/2

” Dia.

Max

Standard Door 

(horizontal or 

vertical) 

17

” Max 

7-1/2

” Max

Flush Door 

(horizontal or 

vertical) 

18-1/4

” Max

9-1/8

” Max

DO NOT oversize hole 

– over sizing can result in water leakage.

Zero clearance around air intake cutout for best sealing condition.

Содержание AFM Series

Страница 1: ...nt furnace with venting system serving another appliance DO NOT vent furnace to an outside enclosed porch area DO NOT use for temporary heating of buildings or structures under construction Protect bu...

Страница 2: ...20 WC 10 WC 10 WC 10 WC 10 WC Amperage AMPS 4 2 4 2 7 5 7 5 11 1 Watts 50 50 90 90 132 Power Supply Volt DC 12 12 12 12 12 Return Air 80 in2 80 in2 80 in2 80 in2 80 in2 Minimum Return Air 65 in2 65 i...

Страница 3: ...h 2 clearance full length of the unit Furnace efficiency rating is a thermal rating determined under continuous operating conditions independent of any installation Efficiency rate is given at 76 mini...

Страница 4: ...ow for each BTU size If readings are below the table values airflow can be improved by adding ducts or reducing eliminating restrictions in the system 16 000 20 000 25 000 30 000 35 000 3000 fpm 3000...

Страница 5: ...t assembly is important for proper exhausting of fumes and proper function of furnace NOTE RTV type sealant must be applied to the bezel and casing at the bottom right side to prevent possible water w...

Страница 6: ...TOUTS 1 Remove bottom discharge plate or side these ducting option must be connected to a floor ducting system 2 The drawing shows the use of a gasket and plenum plate for attaching furnace to the flo...

Страница 7: ...o furnace in parallel with battery This provides consistent voltage to furnace increasing component life filtering power surges and AC spikes All units are supplied with a power switch which is to be...

Страница 8: ...ghts the burner DO NOT try to light the burner by hand 7 If burner does not light repeat Steps 1 through 5 8 If after three 3 attempts with no ignition shut down the unit and contact your dealer or a...

Страница 9: ...9...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...12...

Страница 13: ...13 Figure 1 Large Paddle Kit 31093 Figure 2 Small Paddle Kit 31094 Figure 3 Valve Kit 31098 Figure 4 Valve Kit 31096 Figure 5 Valve Kit 31097 Figure 6 Electrode Adjustment...

Страница 14: ...ni aucune autre personne n a le pouvoir de changer de modifier ou de supprimer les instructions contenues dans ce manuel AVERTISSEMENT viter les blessures et la mort Une mauvaise installation adaptat...

Страница 15: ...N 18 Porte STANDARD INSTALLATION 18 Rincer la porte INSTALLATION 19 SYST MES DE CONDUITS DUR 19 D charge de plancher D coupe 19 RACCORDEMENT AU GAZ 19 BRANCHEMENTS LECTRIQUES 20 INSTALLATION DE THERMO...

Страница 16: ...les conduits et conduits inad quat pourraient causer chauffage m diocre et ou faire du v lo sur la limite de temp rature lev e d gagements Retour au d but C t s Arri re Bas de visser des t tes Souffl...

Страница 17: ...uter directement aux points de vente nombre de maintien des angles des virages au minimum Cesser les plaque knockout prises d sir es Si un coup de gr ce est supprim accidentellement couvercles peuvent...

Страница 18: ...3 1 2 po de diam tre trou dans la paroi lat rale de l entra neur Installateur devra prot ger le four et les composants des outils de construction et des d bris lors de l installation 3 Insert fournea...

Страница 19: ...ur c t 5 Connecter le tuyau de gaz la valve et branchez la fiche de ligne de gaz dans l ouverture du bo tier 6 Le cadre de la porte doit serr contre le flanc ext rieur pour viter les fuites d eau 7 En...

Страница 20: ...Type 20 3 Stranded only 18 6 Stranded only 16 8 Stranded only 14 15 Stranded only 12 20 Stranded only 10 30 Stranded only 8 40 Stranded only 6 55 Stranded only 4 75 Stranded only 2 100 Stranded only...

Страница 21: ...rr te avant l allumage du cycle arr tez d unit et contactez votre revendeur ou une Agence de service local v hicules de loisir 3 Apr s 1 minute le ventilateur peut tre ex cut pas cette poque d placez...

Отзывы: