background image

11

I.  Wiring The System (Low Voltage Connec-

tions)

 

1.  CCC, CCC 2 & Digital Thermostat

Note:

 

If optional solar panel is to be installed, do so at this 

time.  Follow installation instructions packaged with solar 

panel.

a.  Connect  the  previously  run  12  VDC  supply  

wire  to  the  red  and  black  wires  protruding 

from the 14-1/4" x 14-1/4" (±1/8") roof open-

ing.

b.  Connect the previously run furnace thermo

-

stat wires (if applicable) to the blue wires pro

-

truding from the 14-1/4" x 14-1/4" (±1/8") roof 

opening.  The  polarity  of  these  connections 

does not matter.

c.  Terminate  the  previously  run  4  conductor 

communication  cable(s)  protruding  into  the 

14-1/4" x 14-1/4" (±1/8") roof opening. The 

cable(s) must be terminated with a telephone 

RJ-11-6C4P connector. Refer to the crimp 

tool manufacturer for crimping instructions. 

See FIGS. 4 & 5.

Important:

 RJ-11-6C4P connectors must be installed 

with the same polarity on each end. Standard telephone 

cables will not operate the controls.

d.  Plug  the  communication  cable(s)  into  the 

telephone coupler(s) in the 14-1/4" x 14-1/4" 

(±1/8") roof opening. If more than one zone 

is used on the CCC and CCC 2 models, the 

second coupler will be used to join each ad

-

ditional zone.

 

 

e.   Plug the indoor temperature sensor cable (if 

applicable) into the matching connector pro

-

truding from the return air opening.

f.  Energy Management System (CCC an CCC 

2 Only). If applicable, connect the previously 

run Energy Management System wires to the 

yellow wires protruding from the 14-1/4" x 14-

1/4" (±1/8") roof opening. The polarity of this 

connection does not matter.

 

2.  Analog Thermostat

 

a.  Connect  the  previously  run  12  VDC  supply 

wire  to  the  red  and  black  wires  protruding 

from the units return air opening. Connect 

+12 VDC to the red wire; –12 VDC to the 

black wire. 

 

b.  Connect the previously run furnace thermo

-

stat  wires  (if  applicable)  to  the  blue/white 

wires protruding from the units return air 

opening.  The  polarity  of  these  connections 

does not matter.

PROPERTY DAMAGE HAZARD. Disconnect 

the positive (+) 12 VDC terminal at the sup-

ply battery. Failure to obey this warning may 

cause damage to equipment.

 

c.   Connect red/white wire protruding from the 

units return air opening to the seven wire 

cable ther7.5 terminal.

 

d.  Connect the green wire protruding from the 

units return air opening to the seven wire ca-

ble thermostat “GND” terminal.

 

e.  Connect the yellow wire protruding from the 

units return air opening to the seven wire ca-

ble thermostat “COOL” Terminal.

 

f.  Connect the tan wire protruding from the 

units return air opening to the seven wire 

cable thermostat “FAN” terminal.

 

g.  Connect  the  blue  wire  protruding  from  the 

units return air opening to the seven wire 

cable thermostat “HI FAN” terminal.

 

h.  Connect the orange wire protruding from the 

units return air opening to the seven wire 

cable  thermostat  “HS/HP”  terminal  (if  appli

-

cable).

 

i.  Connect the white wire protruding from the 

units return air opening to the seven wire ca-

ble thermostat “FUR” terminal (if applicable).

3.  LCD Thermostat

a.  Connect the previously run +12 VDC supply 

wire to the red wire protruding from the units 

return air opening.

b.  Connect the previously run –12 VDC supply 

wire  to  both  the  black  wire  protruding  from 

the units return air opening and to the wire of 

the three wire cable that goes to the thermo

-

stat 12V– terminal.

c.  Connect the previously run furnace thermo

-

stat wires (if applicable) to the blue wires pro

-

truding from the units return air opening.

d.  Connect the red/white wire protruding from 

the units return air opening to wire of the 

three wire cable that goes to thermostat 12V+ 

terminal.

e.  Connect the orange wire protruding from the 

units return air opening to wire of the three 

wire cable that goes to thermostat COMMS 

terminal.

J.  Air Distribution Box Installation

Important: 

The inner walls of the ADB go inside the 

walls of the ceiling template during installation.

 

1.  Working from the rear looking forward with the 

rear tipped down, place the air distribution box in

-

ner walls against the inside of the ceiling template 

walls. Slide the air distribution box backwards un

-

til it touches the template. Raise the air distribu

-

tion box to the ceiling. See FIG. 19.

Содержание 641415.30 series

Страница 1: ...ilt In Optional 3106486 XXX 641732 Digital Board Built In N A 641735 Digital Board Built In N A 641835 CCC 2 Board Built In Optional 3311931 XXX 641932 LCD Board Built In N A 641935 LCD Board Built In N A Heat Pump 651515 CCC Board Built In Optional 3106486 XXX 651516 CCC Board Built In Optional 3106486 XXX 651815 CCC 2 Board Built In Optional 3311931 XXX 651816 CCC 2 Board Built In Optional 33119...

Страница 2: ...tio and window awnings will reduce heat gain by removing the direct exposure to the sun They also add a nice area to enjoy company dur ing the cool of the evening D Condensation Note The manufacturer of this unit will not be responsible for damage caused by condensed moisture on ceilings or other surfaces Air contains moisture and this moisture tends to condense on cold surfaces When air enters th...

Страница 3: ...15 80X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641915C85X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641916 30X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C35X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916 80X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C85X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641932 30X 11 000 10 5 53 0 3 5 ...

Страница 4: ...Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of center front to back and centered from side to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be inst...

Страница 5: ...3 a This supply wire must be located in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b The power MUST be on an appropriately sized separate time delay fuse or circuit breaker The proper size protection can be determined from the chart on page 3 c Make sure at least 15 of supply wire extends into the roof opening This insures an easy connection at the junction box d Wiring MUST comply with...

Страница 6: ...enerator Start Kit CCC and CCC 2 Only a If an Automatic Generator Start AGS kit will be installed an additional 4 conductor com munication cable must be routed from the last unit to the location of the AGS kit Follow AGS kit instructions for installation E Choosing Thermostat Location 1 CCC and CCC 2 WITHOUT Indoor Temperature Sensor Analog Digital and Single Zone LCD Thermostat The proper locatio...

Страница 7: ...allation e CCC 2 Thermostat Installation i Carefully separate the thermostat base plate from the thermostat cover Insert a small screw driver into the slot on bot tom of thermostat and disengage the tab See FIG 8 FIG 7 CCC 2 Thermostat Rear View Wall Disengage Tab CCC 2 Thermostat FIG 8 ii Insert the 4 conductor communication cable through the hole in base plate Align thermostat base plate with ho...

Страница 8: ... Orange wire to the HS HP terminal White wire to the FUR terminal if appli cable f Inspect all connections to make sure they are tight and not touching any other terminals or wires g Push the wires back through the base into the wall Place cover on the thermostat and push until an audible click is heard 5 SZLCD Thermostat Note The wire colors listed for the three conductor cable match the wire col...

Страница 9: ...Power Supply 2 Remove air distribution box and mounting hard ware from the air distribution box kit carton 3 Remove wire tie holding center of rear aluminum bracket to plastic template 4 Reach up into the return air opening and pull the unit electrical wires down for later connection 5 Mount the junction box with screws to the framing in front of the 14 1 4 x 14 1 4 1 8 opening See FIG 15 Return A...

Страница 10: ... Trim Duct 1 2 to 1 Below Ceiling Template Ceiling Template Mounting Bolt Mounting Bolt Front Do Not Disturb Thermostat Bulb PROPERTY DAMAGE HAZARD If bolts are left loose there may not be an adequate roof seal or if over tightened damage may occur to the unit base or ceiling template Tighten to torque specifications listed in this manual Install 2 Screws In Tabs Duct Adapter Screw Holes Must Line...

Страница 11: ...tive 12 VDC terminal at the sup ply battery Failure to obey this warning may cause damage to equipment c Connect red white wire protruding from the units return air opening to the seven wire cable thermostat 7 5 terminal d Connect the green wire protruding from the units return air opening to the seven wire ca ble thermostat GND terminal e Connect the yellow wire protruding from the units return a...

Страница 12: ...er s Guide Reconnect the 12 VDC and 120 VAC power sup plies Check fan speeds cooling mode heat pump mode and furnace mode if connected If features do not work disconnect the 12 VDC and 120 VAC power supplies and verify that all wiring is correct K System Configuration Reset Check Out CCC and CCC 2 Thermostat Only Now that the system is installed it is necessary to do a system configuration reset a...

Страница 13: ...ional zone a Ext Stage Ext Stage is not used on this unit Leave in the OFF position b Zone selection Each CCC 2 thermostat can have up to 4 zones When only one unit is installed it becomes Zone 1 and no dip switch setting is required Each additional unit must be assigned a zone 2 through 4 Each unit must have a different zone setting c Stage selection Stage is not used on this unit Leave in the OF...

Страница 14: ...ator coil This is indicated by very cold out put at very low air speed and the icing can be seen through the hole network with the filters re moved If this should occur inspect the filter and clean if dirty Make sure air vents are open and not obstructed Units have a greater tendency to frost when the outside temperature is relatively low This may be prevented by adjusting the ther mostat control ...

Страница 15: ...15 FIG 25 WIRING DIAGRAM 6414 Series OPTIONAL ...

Страница 16: ...0 12 20 7 7 7 5 7 2035 6625 75 86 233 5 9 21 8 7256 21 72 7 67 7 5 6 1625 5 725 5 1 5 1 8 7 6 5 2 7 7 02725 5 51 51 7 50 3 66 51 1 237 5 37 5 5 67 57 9 9 2 6 851 2 6 851 51 1 225 7 03 6 1625 32 5 02 8 2 5 7 03 287 225 6 1625 3 02 6 21 620 127 86 7 5 0 17 5 0 7 6 7 7 6415 Series ...

Страница 17: ...5 1 725 5 1 72 767 7 6833 9 851 851 9 5 7 5 25 200 9 8 8 9 72 767 7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 641915 641916 Series 641932 641935 Series ...

Страница 18: ... 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6 1625 62 5 25 57 7 5 1 725 86 02725 12 20 8 5 5 5 6 1625 9 86 233 5 2 21 8 7256 21 51 57 7 1 87 1 767 7 72 9 8 8 9 200 25 5 5 7 9 851 851 9 6833 767 7 72 725 5 1 5 1 3 66 75 6518 Series ...

Отзывы: