background image

6

Important: 

When more than one unit is being in-

stalled (additional zones) with the CCC and CCC 2 

thermostat, an additional 4 conductor communica-

tion cable must be routed to each additional unit 14-

1/4" x 14-1/4" (±1/8") roof opening. Make sure at least 

15" of wire extends into the roof opening. See FIG. 25.

b.  Analog Thermostat

i. Route a 7 conductor cable, 18 to 22 AWG, 

from the 14-1/4" x 14-1/4" (±1/8") to the  

thermostat mounting location. 

Review sec-

tion E "Choosing Thermostat Location" 

before routing cable.

 Make sure 15" of 

the wire extends into the roof opening and 

6" of wire extends from the wall at the ther-

mostat mounting location.

 

c.  LCD Thermostat

i. Route a 3 conductor cable, 18 to 22 AWG, 

from the 14-1/4" x 14-1/4" (±1/8") roof open-

ing to the Single Zone LCD (hereinafter re-

ferred to as SZLCD) thermostat mounting 

location. 

Review section E "Choosing 

Thermostat Location" before routing 

cable. 

Make sure that at least 15" of the 

wire extends into the roof opening and 6" 

extends from the wall at the thermostat 

mounting location.  

5.  If  system  includes  a  gas  furnace,  route  two  18 

gauge thermostat wires from the furnace to the 

roof  opening of the unit that will control it. If more 

than one furnace is to be used, route the second 

set of thermostat wires to the second unit. Make 

sure that 6" of wire extends into the opening.

 

6.  Energy Management System (CCC and CCC 2 

Only)

a.  If an Energy Management System (load shed 

feature)  is  to  be  used  with  the  control,  two 

wires must be routed to the roof opening of 

the zone to be managed. The signal required 

for  this  function  is  normally  an  open  relay 

contact. When the EMS calls for the com-

pressor to shut off, the relay contacts should 

close. Make sure at least 15" of the EMS wire 

extends into the roof opening.

 

7.  Automatic Generator Start Kit (CCC and CCC 2 

Only)

a.  If an Automatic Generator Start (AGS) kit will 

be installed, an additional 4 conductor com

-

munication  cable  must  be  routed  from  the 

last unit to the location of the AGS kit. Follow 

AGS kit instructions for installation.

E. Choosing Thermostat Location

 

1.  CCC and CCC 2 (

WITHOUT

 Indoor Temperature 

Sensor), Analog, Digital, and  Single Zone LCD 

Thermostat.

 

 

The proper location of the thermostat is very im

-

portant to ensure that it will provide a comfort-

able RV temperature. Observe the following rules 

when selecting a location.

a.  Locate the thermostat 54" above the floor.

b.  Install the thermostat on a partition, not on an 

outside wall.

c. 

NEVER

 expose the thermostat to direct heat 

from lamps, sun or other heat producing 

items.

d.  Avoid locations close to doors that lead out-

side, windows or adjoining outside walls.

e.  Avoid locations close to supply registers and 

the air from them.

Note:

 On CCC and CCC 2 System installations 

WITH

 op-

tional indoor temperature sensor, the thermostat may be 

mounted  anywhere  that  is  convenient  in  the  RV. Try  to 

avoid hard to reach and hard to see areas.

F.  Thermostat, Indoor Temperature Sensor, 

And Thermostat Cable Installation

Note:

 A 2" hole in the wall is required at the CCC 2 ther-

mostat location. A 3/8" hole in the wall is required at the 

CCC, Digital, Analog, and LCD thermostat location. 

 

1.  CCC Thermostat.

a.  The  previously  run  communication  cable  (4 

conductor  telephone  cable)  must  be  termi

-

nated with two (2) RJ-11-6C4P telephone 

connectors. Refer to the crimp tool manu-

facturer for crimping instructions. See FIGS.  

4 & 5.

Important:

 RJ-11-6C4P connectors must be in-

stalled as shown in FIGS. 4 & 5.

 

b.  Carefully  remove  the  base  plate  from  the 

CCC thermostat. This may be accomplished 

by  inserting  a  small  screwdriver  under  the 

tab on the bottom edge of the front cover and 

gently prying. See FIG. 6

FIG. 4

FIG. 5

Flat Four Conductor Cable

RJ-11-6C4P

Pin 1

Black

Black Red

Red Green

Green

Yellow

Yellow

Содержание 641415.30 series

Страница 1: ...ilt In Optional 3106486 XXX 641732 Digital Board Built In N A 641735 Digital Board Built In N A 641835 CCC 2 Board Built In Optional 3311931 XXX 641932 LCD Board Built In N A 641935 LCD Board Built In N A Heat Pump 651515 CCC Board Built In Optional 3106486 XXX 651516 CCC Board Built In Optional 3106486 XXX 651815 CCC 2 Board Built In Optional 3311931 XXX 651816 CCC 2 Board Built In Optional 33119...

Страница 2: ...tio and window awnings will reduce heat gain by removing the direct exposure to the sun They also add a nice area to enjoy company dur ing the cool of the evening D Condensation Note The manufacturer of this unit will not be responsible for damage caused by condensed moisture on ceilings or other surfaces Air contains moisture and this moisture tends to condense on cold surfaces When air enters th...

Страница 3: ...15 80X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641915C85X 13 500 12 6 63 0 2 6 8 5 19 0 20 Amp 3 5 KW 5 0 KW 641916 30X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C35X Hi Cap 12 3 61 0 3 3 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916 80X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641916C85X Hi Cap 13 4 63 0 2 6 8 5 23 0 20 Amp 3 5 KW 5 0 KW 641932 30X 11 000 10 5 53 0 3 5 ...

Страница 4: ...Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of center front to back and centered from side to side 2 For two unit installations Install one unit 1 3 and one unit 2 3 s from front of RV and centered from side to side It is preferred that the unit be inst...

Страница 5: ...3 a This supply wire must be located in the front portion of the 14 1 4 x 14 1 4 1 8 open ing b The power MUST be on an appropriately sized separate time delay fuse or circuit breaker The proper size protection can be determined from the chart on page 3 c Make sure at least 15 of supply wire extends into the roof opening This insures an easy connection at the junction box d Wiring MUST comply with...

Страница 6: ...enerator Start Kit CCC and CCC 2 Only a If an Automatic Generator Start AGS kit will be installed an additional 4 conductor com munication cable must be routed from the last unit to the location of the AGS kit Follow AGS kit instructions for installation E Choosing Thermostat Location 1 CCC and CCC 2 WITHOUT Indoor Temperature Sensor Analog Digital and Single Zone LCD Thermostat The proper locatio...

Страница 7: ...allation e CCC 2 Thermostat Installation i Carefully separate the thermostat base plate from the thermostat cover Insert a small screw driver into the slot on bot tom of thermostat and disengage the tab See FIG 8 FIG 7 CCC 2 Thermostat Rear View Wall Disengage Tab CCC 2 Thermostat FIG 8 ii Insert the 4 conductor communication cable through the hole in base plate Align thermostat base plate with ho...

Страница 8: ... Orange wire to the HS HP terminal White wire to the FUR terminal if appli cable f Inspect all connections to make sure they are tight and not touching any other terminals or wires g Push the wires back through the base into the wall Place cover on the thermostat and push until an audible click is heard 5 SZLCD Thermostat Note The wire colors listed for the three conductor cable match the wire col...

Страница 9: ...Power Supply 2 Remove air distribution box and mounting hard ware from the air distribution box kit carton 3 Remove wire tie holding center of rear aluminum bracket to plastic template 4 Reach up into the return air opening and pull the unit electrical wires down for later connection 5 Mount the junction box with screws to the framing in front of the 14 1 4 x 14 1 4 1 8 opening See FIG 15 Return A...

Страница 10: ... Trim Duct 1 2 to 1 Below Ceiling Template Ceiling Template Mounting Bolt Mounting Bolt Front Do Not Disturb Thermostat Bulb PROPERTY DAMAGE HAZARD If bolts are left loose there may not be an adequate roof seal or if over tightened damage may occur to the unit base or ceiling template Tighten to torque specifications listed in this manual Install 2 Screws In Tabs Duct Adapter Screw Holes Must Line...

Страница 11: ...tive 12 VDC terminal at the sup ply battery Failure to obey this warning may cause damage to equipment c Connect red white wire protruding from the units return air opening to the seven wire cable thermostat 7 5 terminal d Connect the green wire protruding from the units return air opening to the seven wire ca ble thermostat GND terminal e Connect the yellow wire protruding from the units return a...

Страница 12: ...er s Guide Reconnect the 12 VDC and 120 VAC power sup plies Check fan speeds cooling mode heat pump mode and furnace mode if connected If features do not work disconnect the 12 VDC and 120 VAC power supplies and verify that all wiring is correct K System Configuration Reset Check Out CCC and CCC 2 Thermostat Only Now that the system is installed it is necessary to do a system configuration reset a...

Страница 13: ...ional zone a Ext Stage Ext Stage is not used on this unit Leave in the OFF position b Zone selection Each CCC 2 thermostat can have up to 4 zones When only one unit is installed it becomes Zone 1 and no dip switch setting is required Each additional unit must be assigned a zone 2 through 4 Each unit must have a different zone setting c Stage selection Stage is not used on this unit Leave in the OF...

Страница 14: ...ator coil This is indicated by very cold out put at very low air speed and the icing can be seen through the hole network with the filters re moved If this should occur inspect the filter and clean if dirty Make sure air vents are open and not obstructed Units have a greater tendency to frost when the outside temperature is relatively low This may be prevented by adjusting the ther mostat control ...

Страница 15: ...15 FIG 25 WIRING DIAGRAM 6414 Series OPTIONAL ...

Страница 16: ...0 12 20 7 7 7 5 7 2035 6625 75 86 233 5 9 21 8 7256 21 72 7 67 7 5 6 1625 5 725 5 1 5 1 8 7 6 5 2 7 7 02725 5 51 51 7 50 3 66 51 1 237 5 37 5 5 67 57 9 9 2 6 851 2 6 851 51 1 225 7 03 6 1625 32 5 02 8 2 5 7 03 287 225 6 1625 3 02 6 21 620 127 86 7 5 0 17 5 0 7 6 7 7 6415 Series ...

Страница 17: ...5 1 725 5 1 72 767 7 6833 9 851 851 9 5 7 5 25 200 9 8 8 9 72 767 7 1 7 1 87 51 57 21 21 8 7256 2 86 233 5 9 5 6 1625 5 5 8 20 12 02725 62 5 25 57 7 5 1 725 86 6 5 2 5 8 7 5 67 57 3 5 7 7 5 37 5 237 641915 641916 Series 641932 641935 Series ...

Страница 18: ... 9 37 5 237 5 7 7 5 67 57 3 5 7 8 5 2 5 6 287 225 7 03 6 1625 62 5 25 57 7 5 1 725 86 02725 12 20 8 5 5 5 6 1625 9 86 233 5 2 21 8 7256 21 51 57 7 1 87 1 767 7 72 9 8 8 9 200 25 5 5 7 9 851 851 9 6833 767 7 72 725 5 1 5 1 3 66 75 6518 Series ...

Отзывы: