Dometic 620615.321 Скачать руководство пользователя страница 11

11

FIG. 21

Upside
Down
Foam
Divider

Base Pan

Ceiling

Place Foam Divider in
(14-1/4" x 14-1/4" (±1/8")
Ceiling Opening against Base
Pan Bottom

Do Not Peel Tape Off
Adhesive

Foam Divider Ceiling
Level 

(±1/4")

 Tear Off

Excess

FIG. 22

Foam Divider

Adhesive

Peel Off Paper - Center Divider - Stick To
Rear Flange On Ceiling Template

c.

Install Ceiling Template

Peel the paper off of the foam divider and
stick it in place on the center of the rear
flange of the return air opening on the ceil-
ing template. See FIG. 22.

If bolts are left loose there may not be ad-
equate roof seal or if over tightened, damage
may ocur to the air conditioner base or ceiling
template. Tighten to specifications listed in
this manual.

CAUTION

Start each mounting bolt through the ceil-
ing template and up into the unit base pan
by hand.

EVENLY tighten the bolts to a torque of
40 to 50 inch pounds. This will com-
press the roof gasket to approximately
1/2". The bolts are self locking so over
tightening is not necessary. See FIG.
16.

d.

Use Aluminum foil tape (not supplied) to seal

the ends of the foam divider to the sides of the
opening. Make sure the area behind the flange
on the ceiling template is sealed. See FIG. 23.

Make Sure To Seal
Behind Flange

2. Center Discharge Duct Application Installation

Note: If using non-center duct installation, refer to all Non-
Center Duct Installations Section 1on page 10.
Important: A duct adapter (not supplied) must be installed
between the unit discharge and the customer installed cen-
ter duct. This duct adapter must be approved by Dometic.

a. Check gasket alignment of the air conditioner

over the roof opening and adjust if necessary.
Unit may be moved from below by slightly lift-
ing. See FIG. 12.

Remove return air cover, ceiling template,
foam divider and air filter from the 3308120
carton.

Locate the four  8" x 1/4 x 20 unit mounting
bolts, junction box cover and Romex con-
nector in the 3107180.006 bolt kit.

Pull down the unit's electrical cord and fas-
ten the junction box with screws to the fram-
ing in the front of the 14-1/4" x 14-1/4" (±1/
8") opening. See FIG. 14 & 15.

Install the Romex connector in the junc-
tion box.

b.

Installing Foam Divider

Cut notch in the center section of the foam
divider to fit (approximately 2 x 8 inches)
snugly around duct. See FIG. 24.

FIG. 23

Use Aluminum Foil Tape To Seal The
Foam Divider To The Sides Of 14-1/4"
x 14-1/4" (±1/8") Ceiling Opening

Route Wires
Through Slot

Catch Flange In Groove Of
Return Air Cover

Improper installation and sealing of foam di-
vider will cause the compressor to quick cycle
on the cold control. This may result in fuse or
circuit breaker opening and/or lack of cool-
ing.

CAUTION

FIG. 24

Foam
Divider

Mark And Cut 2" x 8"
Opening For Center Duct

Tape Covered
Adhesive

620615, 620625 & 620626 Installation & Operating Instructions

Содержание 620615.321

Страница 1: ...s manual must be read and un derstood before installation adjust ment service ormaintenanceisper formed This unit must be installed by a qualified service technician Modification of this product can b...

Страница 2: ...at gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening D Condensation...

Страница 3: ...ating Rated Load Locked Rated Load Locked Speed Static R 22 Oz Wire Size Protection Weight Generator BTU HR Amps Rotor Amps Rotor Max Min Max Min User Pounds Size Cooling Amps Amps W C Supplied 1Unit...

Страница 4: ...of vent is available or another location is desired the following is recom mended a For one unit installation The air conditioner should be mounted slightly forward of center front to back and centere...

Страница 5: ...ditionerandmustbe finished in accordance with NFPA Standard 501C Section 2 7 2 Do Not Cut RoofStrucure OrRafters Good Rafters Supported By CrossBeams Good Location Between Roof Rafters 2 RoofVentRemov...

Страница 6: ...nate configura tions and methods must be approved by the Dometic Corporation in writing The following instructions are based upon the use of Dometic Return Air Kits 3105007 XXX 3105935 XXX or 3308120...

Страница 7: ...serve the following general rules in determiningthelocationandsubmitlocationto Dometicforapproval Locate the Receiver 54 above the floor NEVERexposeittodirectheatfromlamps sun or other heat producing...

Страница 8: ...by slightly lift ing See FIG 12 b Remove return air cover and ceiling template from the 3105007 XXX or 3105935 XXX kit car ton FIG 12 Center Unit From Below Roof Gasket Flat Four Conductor Cable RJ 1...

Страница 9: ...Below Roof Gasket FIG 14 DC Power Supply Receiver Leads Furnace Furnace Tstat Con nection From A C EVENLY tighten the bolts to a torque of 40 to 50 inch pounds This will compress the roof gasket to ap...

Страница 10: ...tor in the junc tion box b Installing Foam Divider Locate the foam divider and insert it corner to corner in the 14 1 4 x 14 1 4 1 8 opening with the adhesive tape up Do not remove paper to expose adh...

Страница 11: ...er duct installation refer to all Non Center Duct Installations Section 1on page 10 Important A duct adapter not supplied must be installed between the unit discharge and the customer installed cen te...

Страница 12: ...the return air open ing above the center duct before ceiling tem plate c Install Ceiling Template Apply a piece of foam weather stripping not supplied to the upper side of ceiling tem plate to make a...

Страница 13: ...assure they don t vibrate off d Push the wires into the box e Install the cover onto the junction box I Decorative Cover Installation Installing unit with 3105007 XXX or 3105935 XXX Return Air Cover...

Страница 14: ...e red positive 12VDC supply wire See FIG 23 b Connect the black wire from the air conditioner and the black wire from the filter indicator light with the black negative 12VDC supply wire See FIG 23 No...

Страница 15: ...uct System Only Depth 2 0 In Min 2 0 Max Width 8 0 In Min 8 0 In Max Total Duct Length 15 0 Ft Min 40 Ft Max Duct Length Short Run 1 3 Total Length Register Requirements Number Required Per Run 4 Min...

Страница 16: ...er Required Roof Rafters Roof Rafters Note Duct Size is Inside Dimensions Note Duct Size Is Inside Dimensions Short Duct Run Minimum 1 3 Total Duct Length Short Duct Run Minimum 1 3 Total Duct Length...

Страница 17: ...tery symbol will appear in the dis play window b When the low battery condition exists and the remote sends a signal to the receiver it may be possible for the control system to go to the default sett...

Страница 18: ...played a High Speed continuous fan operation b Low Speed continuous fan operation 3 The receiver will beep when each change is com pleted The GREEN LED will light H Room Temperature Display 1 Press th...

Страница 19: ...batteries are installed the clock will display 0 00 b Clock shows only military time c Push the clock button the clock display should blink I FEEL I FEEL d Press and hold the UP or DOWN but ton to set...

Страница 20: ...NO TO 115 VAC 1O 60 Hz TO 115 VAC 1O 60 Hz HEAT ACCESSORY WHT BLK BLK ELEMENT LIMIT 3 1 SWITCH WHT BLK OL WHT FREEZE BLK BLK NOT AVAILABLE ON SOME ON SOME MODELS T5 T6 T9 T10 T7 T8 COUPLERS IN LINE I...

Отзывы: