10

Installing unit with 3308120.XXX Genesis Air Fil-

tration System Return Air Kit. For unit with
3105007.XXX or 3105935.XXX Return Air Kit, see
page 8.

Micro-Therm Filter System

Micro-Therm Filter System

FILTER
RESET

FILTER
RESET

CLEA

N

FILTE

R

CLEAN
FILTER

Return Air
Cover

FIG. 20

Grill

Foam
Divider

Ceiling
Template

Slider

Filter

Handle

1.

All Non-Center Duct Installations

Note: The Genesis Air Filtration System can be installed on
the units that use a center discharge duct through the 14-1/
4" x 14-1/4" (±1/8") opening. Installing units with the center
discharge duct go to page 11 "Section 2" Center Duct In-
stallation.

a.

Check gasket alignment of the air conditioner
over the roof opening and adjust if necessary.
Unit may be moved from below by slightly lift-
ing. See FIG. 12.

Remove return air cover, ceiling template,

foam divider and air filter from the 3308120
carton.

Locate the four 8" x 1/4" x 20 unit mount-

ing bolts, junction box cover and Romex
connector in the 3107180.006 bolt kit.

Pull down the unit's electrical cord and fas-

ten the junction box with screws to the fram-
ing in the front of the 14-1/4" x 14-1/4" (±1/

8") opening. See FIG. 14 & 15.

Install the Romex connector in the junc-

tion box.

b.

Installing Foam Divider

Locate the foam divider and insert it corner
to corner in the  14-1/4" x 14-1/4" (±1/8")
opening with the adhesive tape up. (Do not
remove paper to expose adhesive). The
foam divider should be level with the ceiling
(±1/4"). Tear off the excess at the pre-cut
perforations in divider. See FIG. 21.

Note: The adhesive on the insulation is extremely sticky.
Be sure the part is located where desired before pressing
into place.

d. With slight pressure then push the divider plate

against the double sided tape on the ceiling
template.

e. Locate the 1/8" x 7" x 18" self -adhesive insula-

tion supplied with the return air kit. Remove the
backing paper from the insulation and carefully
stick onto the ceiling template divider panel.
See FIG. 19.

Excess width is intended to seal the di-
vider plate to the sides of the 14-1/4" x 14-
1/4" (±1/8") opening. This is to help pre-
vent cold air discharge from circulating into
the air conditioner return air opening.

If the insulation is too high, stick excess
height of insulation to the air conditioner
base pan. Do not cover up unit rating plate.

FIG. 18

Improper installation and sealing of divider
plate will cause the compressor to quick cycle
on the cold control. This may result in fuse or
circuit breaker opening and/or lack of cool-
ing.

CAUTION

FIG. 19

620615, 620625 & 620626 Installation & Operating Instructions

Содержание 620615.321

Страница 1: ...s manual must be read and un derstood before installation adjust ment service ormaintenanceisper formed This unit must be installed by a qualified service technician Modification of this product can b...

Страница 2: ...at gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening D Condensation...

Страница 3: ...ating Rated Load Locked Rated Load Locked Speed Static R 22 Oz Wire Size Protection Weight Generator BTU HR Amps Rotor Amps Rotor Max Min Max Min User Pounds Size Cooling Amps Amps W C Supplied 1Unit...

Страница 4: ...of vent is available or another location is desired the following is recom mended a For one unit installation The air conditioner should be mounted slightly forward of center front to back and centere...

Страница 5: ...ditionerandmustbe finished in accordance with NFPA Standard 501C Section 2 7 2 Do Not Cut RoofStrucure OrRafters Good Rafters Supported By CrossBeams Good Location Between Roof Rafters 2 RoofVentRemov...

Страница 6: ...nate configura tions and methods must be approved by the Dometic Corporation in writing The following instructions are based upon the use of Dometic Return Air Kits 3105007 XXX 3105935 XXX or 3308120...

Страница 7: ...serve the following general rules in determiningthelocationandsubmitlocationto Dometicforapproval Locate the Receiver 54 above the floor NEVERexposeittodirectheatfromlamps sun or other heat producing...

Страница 8: ...by slightly lift ing See FIG 12 b Remove return air cover and ceiling template from the 3105007 XXX or 3105935 XXX kit car ton FIG 12 Center Unit From Below Roof Gasket Flat Four Conductor Cable RJ 1...

Страница 9: ...Below Roof Gasket FIG 14 DC Power Supply Receiver Leads Furnace Furnace Tstat Con nection From A C EVENLY tighten the bolts to a torque of 40 to 50 inch pounds This will compress the roof gasket to ap...

Страница 10: ...tor in the junc tion box b Installing Foam Divider Locate the foam divider and insert it corner to corner in the 14 1 4 x 14 1 4 1 8 opening with the adhesive tape up Do not remove paper to expose adh...

Страница 11: ...er duct installation refer to all Non Center Duct Installations Section 1on page 10 Important A duct adapter not supplied must be installed between the unit discharge and the customer installed cen te...

Страница 12: ...the return air open ing above the center duct before ceiling tem plate c Install Ceiling Template Apply a piece of foam weather stripping not supplied to the upper side of ceiling tem plate to make a...

Страница 13: ...assure they don t vibrate off d Push the wires into the box e Install the cover onto the junction box I Decorative Cover Installation Installing unit with 3105007 XXX or 3105935 XXX Return Air Cover...

Страница 14: ...e red positive 12VDC supply wire See FIG 23 b Connect the black wire from the air conditioner and the black wire from the filter indicator light with the black negative 12VDC supply wire See FIG 23 No...

Страница 15: ...uct System Only Depth 2 0 In Min 2 0 Max Width 8 0 In Min 8 0 In Max Total Duct Length 15 0 Ft Min 40 Ft Max Duct Length Short Run 1 3 Total Length Register Requirements Number Required Per Run 4 Min...

Страница 16: ...er Required Roof Rafters Roof Rafters Note Duct Size is Inside Dimensions Note Duct Size Is Inside Dimensions Short Duct Run Minimum 1 3 Total Duct Length Short Duct Run Minimum 1 3 Total Duct Length...

Страница 17: ...tery symbol will appear in the dis play window b When the low battery condition exists and the remote sends a signal to the receiver it may be possible for the control system to go to the default sett...

Страница 18: ...played a High Speed continuous fan operation b Low Speed continuous fan operation 3 The receiver will beep when each change is com pleted The GREEN LED will light H Room Temperature Display 1 Press th...

Страница 19: ...batteries are installed the clock will display 0 00 b Clock shows only military time c Push the clock button the clock display should blink I FEEL I FEEL d Press and hold the UP or DOWN but ton to set...

Страница 20: ...NO TO 115 VAC 1O 60 Hz TO 115 VAC 1O 60 Hz HEAT ACCESSORY WHT BLK BLK ELEMENT LIMIT 3 1 SWITCH WHT BLK OL WHT FREEZE BLK BLK NOT AVAILABLE ON SOME ON SOME MODELS T5 T6 T9 T10 T7 T8 COUPLERS IN LINE I...

Отзывы: