background image

13

FIG. 23

Return Air
Cover

Hole
Plugs

Return
Air Grill

CAUTION

Disconnect the positive (+) 12 volt DC termi-
nal at the supply battery. Damage to equip-
ment could occur if the 12 volt DC is not shut
off.

620412, 620415, 620425 & 620426 Series Installation Instructions

H. Wiring The System

Reach up into the return air opening and pull the re-

maining wires down.

1. Connection Of Low Voltage Wires

Note: 

If solar panel is installed see instructions packaged

with solar panel option.
Note: If using the Genesis Air Filtration System steps "a"
and "b" are to be completed when installing the decorative
cover.
Note: Wire colors listed for the seven conductor cable are the
most common used in the RV industry. Wire Colors may
vary.

a.

Connect the previously run 12 VDC to the red
and black wires protruding from the units return
air opening. C12 VDC to the red wire;
–12 VDC to the black wire.

b.

Connect the previously run furnace thermostat
wires (if applicable) to the blue/white wires
protruding from the units return air opening. The
polarity of these connections does not matter.

c.

Connect red/white wire protruding from the units
return air opening to the seven wire cable
connected at ther7.5 terminal.

d.

Connect the green

 

wire protruding from the units

return air opening to the seven wire cable
connected at thermostat “GND” terminal.

e.

Connect the yellow wire protruding from the
units return air opening to the seven wire cable
connected at thermostat “COOL” Terminal.

f.

Connect the tan wire protruding from the units
return air opening to the seven wire cable
connected at thermostat “FAN” terminal.

g.

Connect the blue wire protruding from the units
return air opening to the seven wire cable
connected at thermostat “HI FAN” terminal.

h.

Connect the orange wire protruding from the
units return air opening to the seven wire cable
connected at thermostat “HS/HP” terminal (if
applicable).

i.

Connect the white wire protruding from the units
return air opening to the seven wire cable
connected at thermostat “FUR” terminal (if ap-
plicable).

This product is equipped with a 3-wire
(grounded) system for protection against
shock hazard. Make sure that the appliance is
wired into a properly grounded 120 volt AC
circuit and the polarity is correct. Failure to do
so could result in death, personal injury or
damage to the equipment.

Disconnect 120 volt AC. Failure to follow these
instructions could create a shock hazard
causing death or severe personal injury.

2. Connection Of 120 Volt Power Supply

a.

Route power supply line through Romex con-
nector into junction box on side away from the
ceiling template. Tighten connector, being care-
ful not to pinch or short wires.

b.

Connect white to white; black to black; and

green to green or bare copper wire using appro-
priate sized twist connectors.

c. Tape the twist wire connectors to the supply

wire to assure they don't vibrate off.

d. Push the wires into the box.
e. Install the cover onto the junction box.

I.

Installing Decorative Inside Cover

Installing unit with 3105007 or 3105935 Return
Air Cover.  For Genesis Air Filtration System
Return Air Kit, see page 14.

1.

Remove the return air grill from the return air cover.

2.

Place the return air cover up to the ceiling tem-
plate.

3.

Install cover to template with #8 x 3/8” blunt point
Phillips head screws provided (6 required).

4.

Reinstall filter return air grill into return air cover.
Align tabs with mating notches and snap into place

5.

Install two hole plugs into screw holes in back of
return air cover. See FIG. 23.

6.

This completes the installation of the air conditioner.
We recommend that power be supplied to the air
conditioner and check for proper operation. Refer to

Содержание 620412.331

Страница 1: ...ld result in personal injury or property damage Lire et comprendre ce manuel avant de proc der l installation desr glages de l entretien ou des r parations L installation de cet appareil doit tre effe...

Страница 2: ...than 5 50 inches thick C The ability of the air conditioner to maintain the desired inside temperature depends on the heat gain of the RV Somepreventativemeasurestakenbytheoccupantsofthe RVcanreducet...

Страница 3: ...length over 24 ft consult the National Electric Code for proper sizing Dometic Corporation gives GENERAL guidelines for generator requirements These guidelines come from experiences people have had in...

Страница 4: ...ions 2 Other Locations When no roof vent is available or another location is desired the following is recom mended a For one unit installation The air conditioner should be mounted slightly forward of...

Страница 5: ...compound around open ing c Seal all screw holes and seams where the roof gasket is located Use a good grade of all weather sealant See FIG 5 d If the opening exceeds 14 3 8 x 14 3 8 it will be necess...

Страница 6: ...GN CHART 620412 620415 620425 620426 Series Installation Instructions 4 Air Distribution System Sizing Design The Installer of this air conditioner system must designtheairdistributionsystemfortheirpa...

Страница 7: ...gisters 4 Min 8 Max Per Unit 14 Sq In Free Area Per Register FRAME 14 1 4 1 8 OPENING AC POWER SUPPLY WIRE DUCT FRAME DUCT ROOF INSULATION DUCT CEILING DUCT 14 1 4 1 8 OPENING INSULATION SIDE VIEW TOW...

Страница 8: ...rect heat from lamps sun or other heat producing items d Avoid locations close to doors that lead out side windows or adjoining outside walls e Avoid locations close to supply registers and the air fr...

Страница 9: ...he RV See FIG 9 Thiscompletestheoutsidework Minoradjustments can be done from the inside of the RV if required G Installing The Air Conditioner Installing Unit with 3105007 or 3105935 Return Air Kit F...

Страница 10: ...bolts are self locking so over tightening is not necessary See FIG 14 2 Installation of Divider Plate a Measure the ceiling to roof thickness If distance is 2 0 3 3 4 remove perfo rated tab from divid...

Страница 11: ...1 Center Discharge DuctAppli cation Installation on page 12 a Check gasket alignment of the air conditioner over the roof opening and adjust if necessary Unit may be moved from below by slightly lift...

Страница 12: ...filter from the 3308120 carton Locate the four 8 x 1 4 20 unit mounting bolts junction box cover and Romex con nector in the 3107180 bolt kit Pull down the unit s electrical cord and fas ten the junct...

Страница 13: ...onnect the orange wire protruding from the units return air opening to the seven wire cable connected at thermostat HS HP terminal if applicable i Connectthewhitewireprotrudingfromtheunits return air...

Страница 14: ...d it in place Connect to gether the wires from the thermostat unit and filter indicator Note If solar panel is installed see instructions packaged with solar panel option a Connect the red wire from t...

Страница 15: ...O 115 VAC 60 Hz 1O TO 115 VAC 60 Hz 1O TO LOW VOLT THERMOSTAT CABLE TO LOW VOLT THERMOSTAT CABLE BLU WHT BLU WHT HEAT ACCESSORY WHT BLK BLK ELEMENT LIMIT 3 1 SWITCH WHT BLK OL FUSE SPLICE CAP SPLICE C...

Отзывы: