The opening created must be framed to provide 

adequate support and prevent air from being 

drawn from the roof cavity. Framing stock 407 

mm or more in thickness must be used. Remem-

ber to provide an entrance hole for power sup-

plies, indoor temperature sensor (if applicable), 

thermostat communication cable, and furnace 

wires (if applicable) at the front of the opening. 

See (FIG. 5).

3/4″ Min.

Leave Access For 

Power Supply Wiring

FIG. 5

15" Min. At

Front Of

Opening

Do Not Cut Roof

Structure Or

Rafters

Good-Rafters

Supported By 

Cross Beams

Good Location

Between Roof 

Rafters

Frame Opening So It 

Won't Collapse When 

Bolting Down Unit

19 mm Min. 

C.  Air Distribution Duct Sizing & Design

The installer of this system must design the air distribution 

system for their particular application. Several requirements 

must be met for the unit to operate properly. These require-

ments are as follows:

1. 

 

Make sure ductwork will

 NOT 

bend or collapse during and after installation, 

and that it is correctly insulated and sealed. 

Otherwise, damage to roof structure and ceiling 

could occur.

2.  All discharge air ducts must be properly insu-

lated to prevent condensation from forming on 

their surfaces or adjacent surfaces during op-

eration of unit. This insulation must be R-7 mini-

mum. See (FIG. 6).

Frame

Duct

Duct

Frame

Frame

Roof Opening

Roof Opening

AC Power

Supply Wire

Low Voltage Wires:

12 Vdc

Furnace

Indoor Temperature 

Sensor Cable

Control Wires

Roof

SIDE VIEW

(TOWARD BACK OF RV

Duct

Ceiling

Duct

Insulation

TOP VIEW

(BACK OF RV)

FIG. 6

3.  Ducts and their joints must be sealed to prevent 

condensation from forming on adjacent surfaces 

during operation of the unit.

4.  Return air openings must have 40 square inches 

minimum free area including the filter.

5. 

Return air to the unit must be filtered to prevent 

dirt accumulation on unit cooling surface.

6.  Air Distribution System Installation

a.  Dometic Corporation recommends the basic 

configuration shown in (FIG. 7), for installing 

this system. We have found by testing, that 

this configuration works best in most applica

-

tions. It is the responsibility of the installer to 

review each RV floor plan to determine the 

following:

 

Duct size

 

Duct layout

 

Register size

 

Register location

 

Thermostat location

 

Indoor Temperature Sensor Location

These items must be determined in conjunc-

tion with the Air Distribution Duct System 

Sizing & Design requirements. See "C. Table 

- Air Distribution Duct Sizing & Design" on 

page (5).

Alternate configurations and methods 

may be used which will allow the unit 

to operate properly; however, these 

alternate  configurations  and  methods

 

MUST 

be approved by Dometic Cor-

poration in writing. The following in-

structions are based upon the use of 

RAG Kits 3105007.XXX & 3105935.

XXX.

INSTALLATION INSTRUCTIONS

Содержание 520300.501

Страница 1: ...ic Control Kit Thermostat Optional Indoor Temperature Sensor Air Conditioner LCD SZ Controls 57908 59712 57915 59516 59530 520300 520310 520315 520316 600312 600315 3316155 000 Thermostat Included Wit...

Страница 2: ...NFORMATION 14 A Frost Formation On Cooling Coil 14 B Heat Gain 14 C Condensation 14 D Air Distribution 14 WIRING DIAGRAMS 15 A Simple RV Wiring Diagram 15 B Unit Wiring Diagrams 16 DOCUMENT SYMBOLS In...

Страница 3: ...all safety information and instructions to avoid possible injury or death Read and understand these instructions be fore installing using servicing performing maintenance on this product Incorrect ins...

Страница 4: ...kW 59530 532 N A 8 0 53 0 2 5 5 8 18 5 15 Amp 3 5 kW 5 0 kW 59530 536 N A 7 8 53 0 2 0 5 6 19 0 15 Amp 3 5 kW 5 0 kW 520310 501 9 000 7 8 49 0 3 0 8 5 20 0 20 Amp 2 5 kW 4 0 kW 520315 501 13 500 10 3...

Страница 5: ...n Amount of insulation in walls and roof Geographical location where the RV will be used Personal comfort level required 1 For one unit installation The unit should be mounted slightly forward of cent...

Страница 6: ...e are no obstacles wires pipes etc inside RV s roof floor walls Shut OFF gas supply disconnect 120 Vac power from RV and disconnect positive 12 Vdc terminal from supply battery BEFORE drilling or cutt...

Страница 7: ...ame Duct Duct Frame Frame Roof Opening Roof Opening AC Power Supply Wire Low Voltage Wires 12 Vdc Furnace Indoor Temperature Sensor Cable Control Wires Roof SIDE VIEW TOWARD BACK OF RV Duct Ceiling Du...

Страница 8: ...location See E Choosing Thermostat Location on page 8 4 If system includes a gas furnace route two 18 22 AWG thermostat wires from the furnace to the roof opening of the unit that will control it If...

Страница 9: ...lors listed for the communication cable 3 conductor cable match the wire colors in the unit wire harness and the wire harness at the LCD SZ electronic control box Available wire colors may vary a Remo...

Страница 10: ...et Electrical Cord 120 Vac Power Supply Control Wires 5 Hold the ceiling template up to the roof opening Make sure the large plate faces the rear of the RV See FIG 13 a Start each mounting bolt throug...

Страница 11: ...supplied with the RAG kit Remove the backing paper from the insulation and care fully stick onto the ceiling template divider plate See FIG 16 FIG 16 Foam Tape Place Insulation In Position Do Not Cov...

Страница 12: ...hermo stat wires if applicable to the blue wires protruding from the roof opening or to the 1 4 connectors at the electronic control box using the supplied 1 4 insulated connectors The polarity of thi...

Страница 13: ...eiling tem plate 3 Install cover to template using six 6 supplied 8 x 10 mm blunt point Phillips head screws 4 Re install filter return air grille into return air cov er Align tabs with mating notches...

Страница 14: ...hades blinds and or curtains 3 Keeping windows and doors shut or minimizing usage 4 Avoid the use of heat producing appliances Operation on High Fan Cooling mode will give optimum or maximum efficienc...

Страница 15: ...15 A Simple RV Wiring Diagram OPTIONAL FIG 21 WIRING DIAGRAMS...

Страница 16: ...540 J4 J3 4 3 2 1 J5 FURNACE FURNACE 2 1 12V TSTAT 12V TSTAT PART No 3316300 000 FOR USE WITH AIR CONDITIONER PASSED DIELECTRIC FACTORY WIRING FIELD WIRING FAN LO J2 BLK 2 1 BLU 3 4 N C RED 3 1 4 2 P...

Отзывы: