background image

13

FIG. 22

Electronic Control Box

Dip 

Switches

FIG. 23

Dip Switches

Zone 2

Ext. Stage

Zone 3
Zone 4

Stage
Heat Strip
Heat Pump
Furnace
Dehumidify

Gen Start

a.  Ext. Stage - Ext. Stage is not used on this 

unit. Leave in the "OFF" position.

b.  Zone selection - Each CCC 2 thermostat can 

have up to 4 zones. When only one unit is in-

stalled it becomes Zone 1 and no dip switch 

setting is required. Each additional unit must  

be assigned a zone (2 through 4). Each unit 

must have a different zone setting.

c.  Stage selection - Stage is not used on this 

unit. Leave in the "OFF" position.

d.  Heat Strip - Heat strip is not used in these 

models. Leave in the "OFF" position.

e.  Heat Pump - On heat pump models the #7 

dip switch is in the "ON" position from the 

factory. Non heat pump models leave in the 

"OFF" position.

f.  Furnace - If a Furnace/Aqua heat system 

has been connected to this unit, the furnace 

dip switch must be placed in the "ON" posi-

tion.

g.  Dehumidify - Dehumidify is not used on this 

unit. Leave in the "OFF" position.

5.  Plug the indoor temperature sensor cable (if ap-

plicable) into the P4 (white) 2 pin matching con-

nector in the electronic control box.

6.  Connect the previously run Energy Manage-

ment System wires (if applicable) to the yellow 

wires in the 6 wire harness. The polarity of these 

connections does not matter.

7.  If an Automatic Generator Start (AGS) kit is in-

stalled, follow installation instructions furnished 

with AGS kit.

K.  120 Vac Power Supply Connection

 

ELECTRICAL SHOCK HAZARD. 

Make sure 120 Vac power is disconnected from 

RV. Failure to obey this warning could result in 

death or serious injury.

 

ELECTRICAL SHOCK HAZARD. 

Provide grounding in compliance with all appli-

cable electrical codes. Failure to obey this warn-

ing could result in death or serious injury.

1.  

Route the previously run 120 Vac power supply 

wire through the strain relief and into the junc-

tion box. Tighten strain relief making sure not to 

damage wires. Leave enough wire inside junc-

tion box to connect to unit 120 Vac wires.

2.  Connect white to white; black to black; and green 

to green or bare copper wire using appropriate 

size connectors.

3.  Tape the connectors to the supply wire to ensure 

they don't vibrate loose.

4.  Push the wires into the electronic control box.

L. 

System Configuration

Now that the system is installed, it is necessary to do a 

system configuration.

1. 

Electronic Control Configuration

Depending on the equipment options installed 

by the RV manufacturer, the appropriate dip 

switches will need to be switched to the "ON" 

position. Placing the switch in the "ON" position 

selects that option. See (FIG. 22) & (FIG. 23) & 

(FIG. 24).

Dip switches are in the "OFF position 

when shipped from the factory except heat 

pump models. On these models the ap-

propriate dip switch is in the "ON" position 

from the factory. They are visible through 

the opening in the electronic control box. 

See (FIG. 23).

INSTALLATION INSTRUCTIONS

Содержание 3311931.000-20

Страница 1: ...All initial installations must be approved by Dometic Corporation Roof Top Unit Used With 3105007 XXX OR 3105935 XXX Return Air Grille Description Blizzard NXTTM Model Electronic Control Kit Thermostat Optional Indoor Temperature Sensor Air Conditioner CCC 2 Controls H540315 H540316 3312020 000 3314082 000 CCC 2 Blk 3314082 011 CCC 2 Wht 3311931 000 20 3311931 012 40 3311931 020 60 LCD SZ Controls...

Страница 2: ...ion 13 L System Configuration 13 M Installing Return Air Cover 14 N CCC 2 System Only Reset Checkout 14 O CCC 2 System Only Furnace Aqua Temperature Differential Setting 14 GENERAL INFORMATION 15 A Heat Gain 15 B Condensation 15 WIRING DIAGRAMS 16 A Simple RV Wiring Diagram 16 B Unit Wiring Diagrams 17 C Electronic Control Kit Wiring Diagrams 17 INTRODUCTION This air conditioner hereinafter referr...

Страница 3: ... and injuries A Recognize Safety Information This is the safety alert symbol It is used to alert you to potential physical injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death B Understand Signal Words A signal word will identify safety messages and property damage messages and will indicate the degree or level of hazard seriousness indicates a hazardou...

Страница 4: ... Time Delay Fuse or Circuit Breaker Required B Roof Requirements A 14 1 4 x 14 1 4 1 8 square opening hereinafter referred to as roof opening is required for installing this unit This opening is part of the return air system of the unit and MUST be finished in accordance with NFPA 1192 Roof construction with rafters joists support frames on a minimum of 16 inch centers Minimum of 2 inches and maxi...

Страница 5: ...enter Line Of Unit Roof Opening 13 7 8 40 30 4 18 4 b Maintain structural integrity Otherwise damage to product and or RV could occur The roof must be designed to support 130 pounds when RV is in motion Normally a 200 lb static load design will meet this re quirement c Check inside the RV for return air grille here inafter referred to as RAG obstructions i e door openings room dividers curtains ce...

Страница 6: ...ld oc cur NEVER create a low spot on RV roof Otherwise water will pool and could cause a leak The opening created must be framed to provide adequate support and prevent air from being drawn from the roof cavity Framing stock 3 4 or more in thickness must be used Remember to provide an entrance hole for power supplies indoor temperature sensor if applicable ther mostat communication cable and furna...

Страница 7: ...s route a dedicated 12 Vdc supply wire 18 22 AGW to zone 1 and zone 3 roof open ing a This supply wire must be located in the front portion of the roof opening b Make sure that at least 15 of supply wire extends into the roof opening 3 Thermostat Communication Cable a CCC 2 Thermostat I Route a 4 conductor communication ca ble from the roof opening to the thermo stat mounting location using the sh...

Страница 8: ...mostat Location 1 CCC 2 system without an optional indoor tem perature sensor and LCD SZ system a The proper location of the thermostat is very important to ensure that it will provide a com fortable RV temperature Observe the follow ing rules when selecting a location Locate the thermostat 54 above the floor Install the thermostat on a partition not on an outside wall NEVER expose the thermostat ...

Страница 9: ... Remove the unit from the carton and discard carton 2 LIFTING HAZARD Use proper lifting technique and control when lifting product Failure to obey this caution could result in injury Place unit on roof 3 Do NOT slide unit Otherwise damage to gasket on bottom of unit may occur b Route the communication cable through the 2 diameter hole in the wall required for the thermostat See FIG 8 c Optional In...

Страница 10: ...s manual will use a four 4 bolt pattern for installing the RAG kit These bolts and the electronic control box cover are furnished in the CCC 2 control kit 4 Reach up into the return air opening and pull the unit electric cord down for later connection See FIG 15 FIG 15 Gasket Furnace Wires Electrical Cord 120 Vac Power Supply Control Cables 5 Hold the ceiling template up to the roof opening Make s...

Страница 11: ... is too high stick excess height of the insulation to the unit base pan Do not cover up unit rating plate f Place the electronic control box on the ceil ing template with the white 6 pin plug on the curb side of the RV Do NOT attach at this time FIG 16 Front Of Vehicle Tighten To Compress Gasket To 3 4 Roof Gasket Screws 6 Installation Of Divider Plate a Measure the ceiling to roof thickness If di...

Страница 12: ... wires in the 6 wire harness Con nect 12 Vdc to the red wire 12 Vdc to the black wire 2 Connect the previously run furnace wires if ap plicable to the blue wires in the 6 wire harness 3 Terminate the 4 conductor communication cable s protruding from the roof opening The cable s must be terminated with a telephone RJ 11 6C4P connector Refer to the crimp tool manufacturer for crimping instructions R...

Страница 13: ...s in stalled follow installation instructions furnished with AGS kit K 120 Vac Power Supply Connection ELECTRICAL SHOCK HAZARD Make sure 120 Vac power is disconnected from RV Failure to obey this warning could result in death or serious injury ELECTRICAL SHOCK HAZARD Provide grounding in compliance with all appli cable electrical codes Failure to obey this warn ing could result in death or serious...

Страница 14: ...ferential of either 1 degree F or 2 degree F See FIG 26 1 To set the differential simultaneously press the PROGRAM button and the up button on the CCC 2 thermostat diF1 will appear in the display while the buttons are pressed See FIG 26 To set the 2 degree differential simul taneously press the PROGRAM button and the down button diF2 will appear in the display while the buttons are pressed FIG 26 ...

Страница 15: ... a head start on the expected high outdoor ambient will greatly improve its ability to maintain the desired indoor temperature For a more permanent solution to high heat gain acces sories like Dometic outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy company during the cool of the evening GENERAL INFORMATION B Condensation The manu...

Страница 16: ...16 A Simple RV Wiring Diagram OPTIONAL FIG 27 WIRING DIAGRAMS ...

Страница 17: ...ms 1 H540315 H540316 Wiring Diagram FIG 28 C Electronic Control Kit Wiring Diagrams 1 3312020 000 CCC 2 Electronic Control Kit Wiring Diagram FIG 29 2 3313189 000 3313189 015 LCD SZ Electron ic Control Kit Wiring Diagram Cool Furnace FIG 30 ...

Отзывы: