5
It is the responsibility of the installer of this
system to ensure structural integrity of the
Vehicle roof. Never create a low spot on the
roof where water will collect. Water standing
around the unit may leak into the interior
causing damage to the product and the Vehi-
cle.
D. Wiring Requirements
1. 220 - 240 VAC Supply Wire
Route a copper, with ground, 220 - 240 VAC sup-
ply wire from the time delay fuse or circuit breaker
box to the roof opening. The proper size wire can
be determined from chart on page 3.
Note:
If vent fan was removed, the existing wire may be
used provided it is of proper size, location and correctly
fused.
a. This supply wire must be located in the front
portion of the 362 mm x 362 mm (± 3 mm)
opening.
b. The power MUST be on an appropriately sized
separate time delay fuse or circuit breaker. The
proper protection can be determined from chart
on page 3.
c. Make sure that at least 380 mm of supply wire
extends into the roof opening. This ensures an
easy connection at the junction box.
d. Wiring methods must comply with all national
and local wiring codes and/or regulations.
e. Protect the wire where it passes into the open-
ing with approved method. See paragraph "d"
above.
Note:
These power supply connections may be replaced
with type Y attachments if done by qualified personal.
This unit weighs approximately 45 Kilograms.
To prevent back injury, use a mechanical hoist
to place unit on roof.
Do not slide the unit. This may damage the
roof gasket attached to the bottom and may
create a leaky installation.
FIG. 6
FRONT
E. Placing Unit On The Roof
1. Remove the unit from the carton and discard car-
ton.
2. Place the unit on the roof.
3. Lift and place the unit over the prepared opening
using the gasket on the unit as a guide. See FIG.
6.
4. Place the air distribution box kit inside the Vehicle.
This box contains mounting hardware for the unit
and will be used inside the Vehicle.
This completes the outside work. Minor adjustments can
be done from the inside of the Vehicle if required.
F. Installing The Unit
1. Remove air distribution box and mounting hardware
from carton.
2. Check for correct alignment and adjust the unit as
necessary (Roof gasket centers over the 362 mm
x 362 mm (± 3 mm) opening.
FIG. 5
Do Not Cut
Roof Structure
Or Rafters
Good-Rafters
Supported By
Cross Beams
Optional Metal
Frame
Frame Opening So It
Won't Collapse When
Bolting Down Unit
Leave Access For
Power Supply Wiring
381 mm Min. At
Front Of opening
19 mm Min.
Lift And Place
Do Not Slide