DIP switches 

 

Back of the PCB 
 

BUS END:

 if ON, the bus is terminated (if 

last device on the line) 
 

USR:

 not used, reserved for future 

applications 
 

INIT:

 if ON on power-up, sets the 

controller into default state and sets bus 
address to 1, baud rate to 9600.  
 
To set EEPROM into factory settings by 
INIT, proceed as follows: 
- connect the device over RS485 to a PC 
with the 

ModComTool

 config tool 

- set INIT to ON 
- apply power (use only the connector 
without bottom) 
- find the controller in the tool (Scan) 
- set INIT to OFF 
- in the ModComTool, open the controller 
window 
- click the Init button in the tool  
- remove and apply power 
 

RoHS notice 

The device contains a non-rechargeable battery which backups the real-time clock and 
part of the memory. After the device is not operable, please return it to the manufacturer 
or dispose of it in compliance with local regulations. 
 

Safety note 

The  device  is  designed  for  monitoring  and  control  of  heating,  ventilation,  and  air 
conditioning systems. It must not be used for protection of persons against health risks 
or death, as a safety element, or in applications where its failure could lead to physical or 
property damage or environmental damage. All risks related to device operation must be 
considered together with design, installation, and operation of the entire control system 
which the device is part of. 

 

 

Содержание UI0 Series

Страница 1: ...x series have been replaced Application systems with fancoils convectors floor and radiator heating AHUs air conditioning units control of boilers DHW heating circuits building controls in general monitoring of room temperature and humidity Function The units acquire temperature and optionally relative humidity in the room temperature correction knob and required operation status which is set by p...

Страница 2: ...isplay If user make some action with knob display and knob will shine for defined time All of the backlight functions could be set from Modbus master The unit Modbus address and functionality is defined over the RS485 interface with service software ModComTool which is free for download at http domat int com en downloads software To interface the room unit to the computer use the USB 485 converter...

Страница 3: ...014 Opr 1 2012 Restriction of hazardous substances EN 50581 2012 EU legislation Council Directive 2014 35 EC The Low Voltage Directive LVD Council Directive 2014 30 EC Electromagnetic Compatibility EMC Directive Council Directive 2011 65 EC RoHS2 Directive Terminals 1 2 3 4 5 6 7 8 9 As seen when removing the display part The wiring goes towards the center of the unit so that the cable can be brou...

Страница 4: ...output 1 24 V AC against G0 4 DO2 output 2 24 V AC against G0 5 G0 power outputs inputs common point 6 G0 power outputs inputs common point 7 G power 8 K communication RS485 9 K communication RS485 Type table Typ LCD Backlight Knob DI DO t rH RTC UI010 UI010BL UI011 UI011BL UI012 2 1 UI012BL 2 1 UI020 2 2 UI020BL 2 2 UI051 UI051BL UI052 2 1 UI052BL 2 1 UI055 2 2 UI055BL 2 2 UI071 UI072 2 1 ...

Страница 5: ...al block and top cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm There is an aperture for cabling in the back of the bottom part The bottom should be installed and cabling connected first and the upper part inserted after the construction works have been finished to prevent damage to the unit Seal the conduits ...

Страница 6: ...is possible to set reset the complete symbol set except for the 7 segmentdigits Error and Setting texts and symbols of C F and rH Those are partof the configurable menuprofiles The register description is available in a separate document Room units UI Communication description LCD symbol set see in the picture ...

Страница 7: ...ler window click the Init button in the tool remove and apply power RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations Safety note The device is designed for monitoring and control of heating ventilation and air...

Страница 8: ... domat UI0xx Changes in version 01 2017 The first datasheet version 03 2017 Added picture and description of the installation Corrected information in table types 07 2017 Added non backlight types summary datasheet 10 2017 Added Safety note ...

Отзывы: