domat UI0xx 

-

 

weekly scheduler: 7 days, up to 6 events per day 

-

 

another 5 variables (air quality, fan speed etc.) 

 each has a profile where max. 

and min. values, step, number of decimals, and symbol set are defined. 

 
It is also possible to set / reset any of the LCD symbols on the display over Modbus. 
 
The turn / push knob has three basic functions: 

 

instant  edit    (turning  the  knob) 

  settings  of  one  predefined  analogue  value, 

usually room temperature correction 

 

quick  edit (short push) 

  change  of predefined state, e.g. Presence  (Comfort  / 

Standby / Off), Air condition (Auto / Heating / Cooling / Fan only / Off) etc. 

 

long push 

 jump to menu where values are listed by turning the knob, short push 

selects  the  value  to  be  edited,  and  the  value  is  changed  by  turning  the  knob 
followed by short push for confirmation.  

 
After definable inactivity time, the display goes back to its basic state with rolling display 
of selected values (e.g. actual temperature and humidity). 
 

Backlight 
function  

UI0xxBL type contain knob and display blue colour backlight function. It is possible to set 
brightness 0-100 % separately for knob and display. If user make some action with knob, 
display and knob will shine for defined time. All of the backlight functions could be set 
from Modbus master.  
 

 

The  unit  Modbus  address  and  functionality  is  defined  over  the  RS485  interface  with 
service  software 

ModComTool

  which  is  free  for  download  at 

http://domat-

int.com/en/downloads/software.

 To interface the room unit to the computer use the 

USB/485 converter 

M080

, RS232/RS485 converter 

R012

, or any suitable RS485 converter. 

____________________________________________________________________ 

Technical data 
 

Power supply 

24 V AC +/- 20%, 1 W 

Temperature measuring range 

-20 ... 7

0 °C (accuracy ±1 ˚C)

 

Humidity measuring range  

digital sensor 10 ÷ 90 %rH accuracy ±3%

 

Protection 

IP20 (EN 60529) 

Inputs (specific types only, see table below) 

2x potential-free contact  (dry contact) against G0, 
24 V AC, 5 mA 

Outputs (specific types only, see table below) 

1x - 2x solid state relay, zero switching, for AC load 
24  V  AC,  max.  0.4  A,  AC1,  general  usage,  non-
inductive  load  according  to  EN  60947-4-1, 
galvanic isolation 1.5 kV 

Setpoint 

according to configuration, +/- 10 to +/- 1 K 

Communication 

RS485 - Modbus RTU, slave 

selectable speed 1200 ... 115200 bps, parity and 

bits are set in service SW 

default 9600/N/8/1 

The interface  is  optically separated  1  kV  (except 
for UI010 and UI010BL). 

Display 

LCD 60 x 60 mm, symbol set see above 

Содержание UI0 Series

Страница 1: ...x series have been replaced Application systems with fancoils convectors floor and radiator heating AHUs air conditioning units control of boilers DHW heating circuits building controls in general monitoring of room temperature and humidity Function The units acquire temperature and optionally relative humidity in the room temperature correction knob and required operation status which is set by p...

Страница 2: ...isplay If user make some action with knob display and knob will shine for defined time All of the backlight functions could be set from Modbus master The unit Modbus address and functionality is defined over the RS485 interface with service software ModComTool which is free for download at http domat int com en downloads software To interface the room unit to the computer use the USB 485 converter...

Страница 3: ...014 Opr 1 2012 Restriction of hazardous substances EN 50581 2012 EU legislation Council Directive 2014 35 EC The Low Voltage Directive LVD Council Directive 2014 30 EC Electromagnetic Compatibility EMC Directive Council Directive 2011 65 EC RoHS2 Directive Terminals 1 2 3 4 5 6 7 8 9 As seen when removing the display part The wiring goes towards the center of the unit so that the cable can be brou...

Страница 4: ...output 1 24 V AC against G0 4 DO2 output 2 24 V AC against G0 5 G0 power outputs inputs common point 6 G0 power outputs inputs common point 7 G power 8 K communication RS485 9 K communication RS485 Type table Typ LCD Backlight Knob DI DO t rH RTC UI010 UI010BL UI011 UI011BL UI012 2 1 UI012BL 2 1 UI020 2 2 UI020BL 2 2 UI051 UI051BL UI052 2 1 UI052BL 2 1 UI055 2 2 UI055BL 2 2 UI071 UI072 2 1 ...

Страница 5: ...al block and top cover containing PCB display and the knob The bottom part is fixed by 2 or 4 screws to any flat surface or a flush mounting box Ø 50 mm There is an aperture for cabling in the back of the bottom part The bottom should be installed and cabling connected first and the upper part inserted after the construction works have been finished to prevent damage to the unit Seal the conduits ...

Страница 6: ...is possible to set reset the complete symbol set except for the 7 segmentdigits Error and Setting texts and symbols of C F and rH Those are partof the configurable menuprofiles The register description is available in a separate document Room units UI Communication description LCD symbol set see in the picture ...

Страница 7: ...ler window click the Init button in the tool remove and apply power RoHS notice The device contains a non rechargeable battery which backups the real time clock and part of the memory After the device is not operable please return it to the manufacturer or dispose of it in compliance with local regulations Safety note The device is designed for monitoring and control of heating ventilation and air...

Страница 8: ... domat UI0xx Changes in version 01 2017 The first datasheet version 03 2017 Added picture and description of the installation Corrected information in table types 07 2017 Added non backlight types summary datasheet 10 2017 Added Safety note ...

Отзывы: