domat R560 

11/2018 Subject to technical changes. 

Standards conformity 

EMC EN 61000-6-2 ed.3:2005, EN 61000-6-4 ed.2:2006 + 
A1:2010  (industrial environment) 

Electrical safety EN 60950-1 ed.2:2006 + A11:2009 + 
A12:2011 + A1:2010 + A2:2014 + Opr.1:2012 + Z1:2016 

Hazardous substances reduction EN 50581:2012 

 

 

Terminals 

 

 

Terminals and 
connectors: 

 

RS485 K+ 

port COM1 - serial link RS485, terminals K+ 

RS485 K- 

port COM1 - serial link RS485, terminals K- 

G power supply 

G0 

G0 power supply 

TE 

optional connection for shielding, technical ground

 

AIC 

common terminals for AI1

…A

I8

 

AI1 … AI8

 

input 1 … 8

 

 

 

LED indication: 

 

RUN 

orange LED 

 system cycle (OK: LED flashes periodically 1 

s ON, 1 s OFF; ERROR: LED flashes in other pattern, LED is 
still ON or OFF)

 

TxD

 

 

red  LED 

  RS485  transmitting  data  at  COM1  (flashing: 

transmitting data; OFF: no data traffic)

 

PWR 

green LED 

 power supply (ON: power OK; OFF: no power 

applied, weak or damaged power supply, …)

 

 

 

DIP switches: 

 

ADR 
 

AUTO 

 if all switches are OFF, the address is used 

according to Modbus register 4 LSB 
USER 

 address is set by DIP switches configuration 

INIT - if are all switches ON at power-up, configuration 
parameters are set to defaults  

DIP 8 = bit 0; switches increase their bit weight from 
right to left, see below 

BUS END 

Switch  for  bus  RS485  termination  (located  at  the  RS485 
connector);  ON  =  bus  end;  the  first  and  last  devices  on 
bus should have bus end ON 

Содержание R560

Страница 1: ... to 20 mA current measurement inputs if the corresponding DIP switch is activated The module communicates by means of RS485 data bus The Modbus RTU communication protocol ensures smooth and easy integration in a variety of control and data acquisition systems It connects to process stations PLCs directly or through the M012 interface RS485 to RS232 converter with galvanic isolation Removable conne...

Страница 2: ...may be used for temperature measurement with Pt100 Pt1000 Ni1000 5000 and Ni100 6180 passive sensors Linearisation must be done in controllers Domat PLC for example just like at e g MCIO2 module In the R560 module there is recalculation to C for the Pt1000 sensor only Sampling 10 samples s Effective resolution 16 bit Measurement error The measurement deviation for all measured variables is 0 25 of...

Страница 3: ...dication RUN orange LED system cycle OK LED flashes periodically 1 s ON 1 s OFF ERROR LED flashes in other pattern LED is still ON or OFF TxD red LED RS485 transmitting data at COM1 flashing transmitting data OFF no data traffic PWR green LED power supply ON power OK OFF no power applied weak or damaged power supply DIP switches ADR AUTO if all switches are OFF the address is used according to Mod...

Страница 4: ... to technical changes domat R560 0 20 mA For current measurement 0 20 mA on individual channels switch the particular DIP switch to ON The 0 20 mA range must be also set over Modbus e g using Domat ModComTool Connection ...

Страница 5: ... 3 Addressing The Modbus address can be set as follows hardwarewise using DIP switches The switches increase their bit weight from right to left see image with example where address of 21 is set by activation of switches 4 6 and 8 with bit weight of 16 4 and 1 respectively Valid settable range is 1 to 254 Address 0 all switches OFF means that the address is set as entered in the Modbus table Addre...

Страница 6: ...s set to 0 All changes apply after the module is switched off and on again Safety note The device is designed for monitoring and control of heating ventilation and air conditioning systems It must not be used for protection of persons against health risks or death as a safety element or in applications where its failure could lead to physical or property damage or environmental damage All risks re...

Страница 7: ...domat R560 11 2018 Subject to technical changes 7 Changes in versions 07 2017 First datasheet version 10 2017 Added measurement error value new image 02 2018 Added Safety note 11 2018 Minor changes ...

Отзывы: