3
11.01.16 en / 627
Operating
Further Setting Parameter
Adjustable Parameter
Limit values for Rel.1 and Rel.2
Selectable with buttons
.
Factory
setting
U
min
:
Response value undervoltage,
Lowest phase to phase voltage
(Undervoltage relay)
OFF
U
max
:
Response value overvoltage,
Highest phase to phase voltage L1, L2 or L3
(Overvoltage relay)
440 V
Asym:
Response value voltage asymmetry,
Percentage of highest to lowest phase to
phase voltage
(Asymmetry relay)
20 %
I:
Response value current at current path L1
(< under- / > overcurrrent)
> 8.00 A
Cos-
j
:
Response value phase displacement between
current and voltage
(< under- / > overload monitor)
OFF
P:
Response value effective power 3-phase
Independent of phase sequence switches at
adjusted value also at reverse power
(< under- / > overload)
OFF
S:
Response value apparent power 3-phase (< / > )
OFF
Q:
Response value reactive power (< / >)
OFF
f:
Response value frequency (range 1 ... 400 Hz)
( < under / > overfrequency)
OFF
Hyst: Hysteresis 0.2 ... 50 % of response value
4.0 %
t
v
:
On delay for relays ( 0 ... 10 sec )
0 s
Phseq: Monitoring phase sequence (ON / OFF)
ON
A / R: Seting open- / closed circuit operation
R
Sp:
Error storage ( ON / OFF )
OFF
Response values can be deactivated. (OFF)
Selectable with buttons
.
Factory
setting
t
a
:
Start up delay, when auxiliary voltage connected
( 0.2 ... 10 sec) in steps of 0.1 s
0.2 s
Restore Factory Settings
(Auslieferungszustand wiederherstellen)
Before auxiliary voltage connected press button
Esc
.
During start press and hold.
UP /
DOWN
Display (Run) - Mode
After power up the relay is in display (Run) mode.
Scrolls the display to show one of the 10 possible values.
If a values exceeds the setting, the values is indicated flashing on inverted
display. In the case of a fault display the display always returns to the fault
value after pressing
. If voltage is missing on the measuring input
some values cannot be calculated and a no value is shown.
Input-Mode
The measurement is interrupted, the relays are in failure state and the
indicator LED has orange color
Selection of parameters and setting of thresholds.
ENTER
Display (Run) - Mode:
Manual reset, when manual reset is selected for output relay
Reset works only when fault is removed
Input-Mode:
- Shifts cursor to the right
- Saves the value no-voltage safe
- Pressing for more than 3 sec: Change to display (Run) mode.
Esc
Esc
Display (Run) - Mode
- Pressing for more than 3 sec: Change to input mode
Input-Mode:
- Shifts cursor to the left
- Leave setting without saving
LCD-Display
Rel.1 Rel.2 Sp1 Sp2
Rel.1 Rel.2 Sp1 Sp2
<f
Rel.1 Rel.2 Sp1 Sp2
>f
Rel.1 Rel.2 Sp1 Sp2
U
min
Setting of response values
< Fault, when value drops under set point
> Fault, when value exceeds set point
OFF measurement disabled
If the adjusted threshold of at least one measuring function is exceeded,
the corresponding relay output switches after the selected time delay tv
and the fault is indicated on the display.
Manual reset can be activated or de-activated and is operated with
on the unit.
Indicator output
Monitoring parameters can be set independently.
The MK9300N has 1 relay output.
The MH 9300 has 2 relay outputs.
Each monitoring function can be assigned to Relay 1 and/or to Relay 2. The
switching mode energized or de-energized on trip can be set in input mode.