17
RK 5942 / 28.01.20 en / 184A
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
Troubleshooting
Maintenance and repairs
RK 5942.01 DC 24 V
Article number:
0058689
•
Output:
1 NO contact, 1 semiconductor
•
Nominal voltage U
N
:
DC 24 V
•
Width:
17.5 mm
RK 5942.02 DC 24 V
Article number:
0058690
• Output: 1
NO contact, 1 semiconductor
• Nominal voltage U
N
:
DC 24 V
• Width:
17.5 mm
Standard Types
Continouos current limit curve output contacts
Continouos current limit curve semiconductor outputs
Characteristics
Failure
Potential cause
LED "Power" does not light up
- Power supply not connected
Device cannot be activated
- Start button defective e. g. ST1-ST2
or S12-S34 not bridged
- A safety relay is welded
(replace device)
M9719
10
25
20
0
10
20
30
40
60
50
15
T ( C)
5
0
°
device mounted on distance with air circulation.
max. current at 55°C = 3A
9A
2
device mounted without distance heated by
devices with same load,
max. current at 55°C = 1,5A
2,25A
2
I
2
(A )
2
M11188
40
100
80
0
10
20
30
40
60
50
60
T ( C)
20
0
°
I (mA)
Содержание SAFEMASTER RK 5924