- Do not send DALI data in idle mode
Address: 893
DALI Data are output only when DMX data contents change.
- DMX HOLD
Address: 894
The last setting is retained at loss of DMX signal.
- GOTO ON
Address: 895
At data loss, all outputs go to 100% intensity
- GOTO OFF
Address: 896
At data loss, all outputs to to the „off“ state
- ARC LEVEL*
Address: 897
„off“ (0% intensity) will be sent as ARC LEVEL command
- OFF COMMAND*
Address: 898
„off“ (0% intensity) will be sent as „OFF“ command
- Set maximum DALI adress or group number
Address: 804-864 Tens and Ones represent the number of DALI addresses supported
(min. value 4, max. value 16, default value: 4)
804: set to enable 4 address mode
805: set to enable 5 address mode
etc
864: set to enable 64 address mode
NOTE:
Pls note that converting more than 4 adresses simultaneously
may cause significant delays due to the limited DALI bus speed.
TECHNICAL DATA
Dimensions:
65 mm x 105 mm x 65 mm
Power supply:
230V AC
DALI OUT:
optically isolated, potential.free, polarity independent
DALI Devices:
4-16 Addresses, single adressing or group addressing
DMX IN:
according to USITT DMX512 / DIN56930-2 / ANSI E1-11 compatible
DMX channels:
4...64 (8...128)
Mounting:
DIN rail 35mm
IP rating:
IP 20
Temperature range:
0...50C
Humidity:
non-condensing
Order code:
7044B-H
DISTURBANCES
If a trouble-free operation cannot be guaranteed, disconnect the interface and secure it against un-
wanted operation. This is especially necessary, when
- the unit has visible damages;
- the unit does not operate;
- internal parts are loose;
- connection cables show visible damages.