background image

SETUP

For a easy DALI bus setup we recommend our SOUNDLIGHT USB-DALI adapter. Con-
nect these items to the DALI bus:

- a DALI PSU
- the USB DALI adapter
- the DALI bus participants (excluding the 7044B-H)

Addressing a DALI system consists of multiple steps:
1. 

The bus will be searched for pre-addressed units first. A device is considered being 
adressed when a DALI short adress (1...64) has been assigned to that unit. If already pro-
grammed participants can be found, you may decide
- to leave that adressing as is
- or erase existing programming.

2. 

Then all new (unprogrammed) devices are searched and then a short adress is assigned to
each participant in increasing order, beginning from address 1.

When all devices have been programmed, all devices are read out completely (group assignments,
pre-defined settings, min/max-levels, group assignments) and the data are displayed.

Please note:
New devices may not show any group assignments yet. To assign to a group, select the device
and then assign the desired group(s).  By default, the 7044B-H can address groups 1...4*.

Set the group assignment of each DALI participant to meet your individual needs.

More information regarding DALI programming and the USB-DALI interface can be found in the
USB-DALI manual.

It is not necessary to use the USB-DALI programmer. Any DALI programmer which allows free
user interaction can be used. A programmer which runs only automated pre-defined programming
sequences does not match the needs of user-specific settings.

Please note, that  the level value range transmitted by DMX consists of values 000...255, whereas
the maximum DALI level is 254**. (255 is the special value "MASK" used within DALI programm-
ing). "MASK" means: "do nothing".

You may select to use or not use MASK values at your option (see SETUP).

*= Default setting is 4 single addresses resp. 4 group addresses. This can be reconfigured from 4...64 addresses or
4...16 group addresses at your option. Note that more addresses may result in delays on the DALI bus due to the slow
communication speed of DALI devices.

**= pre-configured to 254 as maximum value (100%) . User-reprogrammable zo 255 (MASK) (see chapter „SETUP“
below).

DALI COMMANDS

All data output on the DALI bus are Direct Arc Level commands. Normally, no other commands will
be issued. In newer models (from Mk4.6 onward), the Zero Arc Level command can be substituted
with the „OFF“ command ti increase compatibility with certain DALI responders.

Содержание soundlight 7044B-H

Страница 1: ...CKED CAREFULLY AND ARE BELIEVED TO BE ACCURATE HOWEVER SOUNDLIGHT DOES NOT ASSUME ANY RESPONSIBI LITY FOR ERRORS OR OMISSIONS THE USER HAS TO CHECK THE SUITABILITY OF THE EQUIP MENT FOR THE INTENDED U...

Страница 2: ...mpatible The 7044B H is compatible to DALI bus systems simple supply The power supply is from standard mains voltage 230V AC signal loss In the case of a loss of the drive signal a pre definable actio...

Страница 3: ...u re do ne Cage clamp connectors accept both stranded and so lid wires We recommend to use ferrules with stranded wi res whenever poosible The decoder 7044B H consits of connectors for these inputs an...

Страница 4: ...to re program connected DALI responders to a fade time of at least 0 7 sec fade time parameter set to 1 or 2 to allow a smooth response You may do so using your preferred DALI programmer or our USB D...

Страница 5: ...o meet your individual needs More information regarding DALI programming and the USB DALI interface can be found in the USB DALI manual It is not necessary to use the USB DALI programmer Any DALI prog...

Страница 6: ...programmed into the interface both status LEDs are blinking alternatively several times As soon as the programming sequence is completed upower the decoder re set the desired DMX start address and re...

Страница 7: ...5 address mode etc 864 set to enable 64 address mode NOTE Pls note that converting more than 4 adresses simultaneously may cause significant delays due to the limited DALI bus speed TECHNICAL DATA Dim...

Страница 8: ...ace in a closed conductive e g metal housing which must be connected to GND Please make sure that shielded data cable is used and the shield is connected properly to the GND pin Shield must never make...

Страница 9: ...ign manuals are available from www ma nuals soundlight de Additional RDM information for RDM enabled devices only is available from www rdm soundlight de If you have any comments which may be worth co...

Отзывы: