CellCom‑LTE Programming and Installation Guide 

Digital

 

Monitoring

 

Products

33

Arming/Disarming Ademco Vista Panels

The following steps describe how to configure the communicator to arm and disarm an Ademco Vista control panel 

from a schedule or remotely from the Virtual Keypad App, VirtualKeypad.com, or Remote Link™ using the remote 

arming output.

1.  Connect output 17 (far left pin on the 7 pin header located in the middle of the PCB) to zone 1 (Z1) on the 

communicator. Connect a 1k ohm EOL resistor from zone 1 to ground (G).

2.  Connect output 1 (O1) on the communicator to zone 3 (terminal 12) on the Vista control panel.
3.  Begin programming by entering the installer code followed by 

800

. Press 

*

 and 

Field ?

 displays.

4.   Program zone 3 as an arming zone. Enter 

56

 and program the following:

a. 

Set to Confirm?

 ‑ Enter 

0

.

b. 

Enter Zn Num.

 ‑ Enter 

03

. Press 

*

 to continue.

c. 

Summary Screen:  Zn ZT P RC HW:RT

 ‑ Press 

*

 to continue.

d. 

Zone Type

 ‑ Enter 

77

. Press 

*

 to continue.

e. 

Report Code 1st 01 2nd 00 10

 ‑ Press 

*

 to continue.

f. 

Hardware Type

 ‑ Enter 

0

. Press 

*

 to continue.

g. 

Resp Time

 ‑ Enter 

1

. Press 

*

 to continue.

h. 

Summary Screen: Zn ZT P RC HW:RT

 ‑ Press 

*

 to continue.

i. 

Program Alpha

 ‑ Enter 

0

.

j. 

Enter ZN Num

 displays. Enter 

00

 to exit.

5.  Program output 17. 

Enter * or #

 displays. Press 

*

 and 

Field?

 displays. Enter 

79

 and program the following:

a. 

Enter output No

 ‑ Enter 

17

. Press 

*

 to continue.

b. 

Output Normally Low

 ‑ Enter 

0

. Press 

*

 to continue.

c. 

Enter Output No

 displays. Enter 

00

 to exit.

6.  Define output 17 actions. 

Enter * or #

 displays. Press 

*

 and 

Field?

 displays. Enter 

80

 and program the following:

a.  Program output 17 to turn on when armed Stay. 

Output Funct#

  ‑ Enter 

01

. Press 

*

 to continue.

• 

Summary Screen: 01  A E P  Trig

 ‑ Press 

*

 to continue.

• 

Activated by: - Enter 2

. Press 

*

 to continue.

• 

Enter Zn Type

 ‑ Enter 

20

. Press 

*

 to continue.

• 

Output Action

 ‑ Enter 

2

. Press 

*

 to continue.

• 

Enter Output No.

 ‑ Enter 

17

. Press 

*

 to continue.

• 

Summary Screen: 01  A E P  Trig

 ‑ Press 

*

 to continue.

b.  Program output 17 to turn on when armed Away. 

Output Funct#

 ‑ Enter 

02

. Press 

*

 to continue.

• 

Summary Screen: 02  A E P  Trig

 ‑ Press 

*

 to continue.

• 

Activated by: 

‑ Enter 

2

. Press 

*

 to continue.

• 

Enter Zn Type

 ‑ Enter 

21

. Press 

*

 to continue.

• 

Output Action 

‑ Enter 

2

. Press 

*

 to continue.

• 

Enter Output No.

 ‑ Enter 

17

. Press 

*

 to continue.

• 

Summary Screen: 02  A E P  Trig

 ‑ Press 

*

 to continue.

c.  Program output 17 to turn off when Disarmed. 

Output Funct# 

‑ Enter 

03

. Press 

*

 to continue.

• 

Summary Screen: 03  A E P  Trig 

‑ Press 

*

 to continue.

• 

Activated by: 

‑ Enter 

2

. Press 

*

 to continue.

• 

Enter Zn Type 

‑ Enter 

22

. Press 

*

 to continue.

• 

Output Action 

‑ Enter 

0

. Press 

*

 to continue.

• 

Enter Output No.

 ‑ Enter 

17

. Press 

*

 to continue.

• 

Summary Screen: 03  A E P  Trig 

‑ Press 

*

 to continue.

d. 

Output Funct# 

‑ Enter 

00

. Press 

*

 to continue.

7. 

Enter * or # 

displays. Press 

*

 and 

Field?

 displays. Enter 

99

 to exit programming.

8.  Programming the communicator.

a.  Reset the communicator. Enter 

6653

.

b.  Press 

CMD

 to output options. Press any select area.

c.  Program output 1 in remote arming output. Press 

CMD

 to 

RMT ARMG OUT

. Enter 

1

, then press

 CMD

.

d.  Press 

CMD

 to zone information. Press any select area and 

Zone No

 displays.

e.  Enter 

1

. Press 

CMD

.

f.  Enter a zone name. Press 

CMD

.

g.  Program zone 1 as an arming zone. 

Zone Type

 displays. Choose arming zone type 

AR

. Press 

CMD

.

h. 

Area: 1------

 displays. Press 

CMD

.

i. 

Style: TOGGLE

 displays. Choose 

MNT

.

j.  Go to 

STOP

 then press and select key to save and exit programming.

Содержание CellCom LTE Series

Страница 1: ...CellCom LTE V Series Communicator Digital Monitoring Products Inc 2020 PROGRAMMING AND INSTALLATION GUIDE...

Страница 2: ...n 14 Programming 15 Before You Begin 15 Getting Started 15 Programming Menu 15 Reset Timeout 16 Special Keys 16 Letters and Special Characters 17 Current Programming 17 Initialization 18 Clear All Cod...

Страница 3: ...Message To Transmit 27 Output Number 27 Output Action 28 Swinger Bypass 28 Cross Zone 28 Receiver Routing 28 Zone Number 28 Stop 29 Set Lockout Code 29 Stop 29 Set Lockout Code 29 Appendix 30 ECP Pass...

Страница 4: ......

Страница 5: ...COMPONENTS Terminals Power Connection Terminals The communicator may be powered from the 12 VDC or 24 VDC auxiliary output of the control panel Observe polarity and use 18 22 AWG wire to connect the c...

Страница 6: ...tion information type to direct with a baud rate of 38400 and choose the appropriate COM port 4 Select Panel Remote Update then select the correct RU file for the communicator 5 Press and hold the loa...

Страница 7: ...IVITY OPERATION Green Steady Communicator Disarmed Primary Power OK No Light No Power Red Steady Communicator Armed Primary Power OK ECP and DSC Passthru Perform an ECP or DSC Passthru and communicate...

Страница 8: ...place to protect the communicator from damage due to tampering or the elements It is not necessary to remove the PCB when installing the communicator Figure 1 System Components DC Z1 Z2 Z3 G T R Z4 O1...

Страница 9: ...nnect the Antenna Place the antenna onto the SMA connector Refer back to Figure 1 Twist the antenna until it is securely tightened Replace the housing cover on the mounted base Be sure to not damage a...

Страница 10: ...y Use a normally closed output on a burglary control panel to indicate a burglary alarm The communicator zone should be programmed with a zone name and burglary zone type When the output on the contro...

Страница 11: ...adence type zone number and type of message sent to the receiver The communicator generates zones 5 and 6 using the zone name of zone 4 to send to the central station Zones 5 and 6 cannot be preprogra...

Страница 12: ...O1 O2 Use 18 22 AWG for Power Supply connection 1k Z4 DMP Panel 12 VDC Aux Output ADEMCO Panel 12 VDC Aux Output BELL 12 VDC BELL NAPCO Panel 12VDC Aux Output BELL 12 VDC BELL DSC Panel 12 24 VDC Aux...

Страница 13: ...n about configuring ECP Passthru refer to COM Series How To Guide ECP Passthru LT 2209 PROG B R RESET LOAD DC Z1 Z2 Z3 G T R Z4 O1 O2 DualCom 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 2...

Страница 14: ...on 2 0 or higher VISTA 15 Yes No No No No VISTA 15P Yes Yes Yes Yes Firmware version 5 2 or higher VISTA 20SE Rev 12 or higher No No No No VISTA 20P Yes Yes Yes Yes Firmware version 5 2 or higer VISTA...

Страница 15: ...nnection Model 330 DSC PC LINK 1 CON 4 YELLOW GREEN YELLOW GREEN TAB UP Figure 9 DSC Passthru Wiring COMMUNICATOR TO DSC WIRING Communicator Terminal DSC Terminal DC RED DC BLK Z4 YEL Z4 GRN T or T1 T...

Страница 16: ...tput or remote arming output in output options when programming the communicator See Armed Output or Remote Arming Output The communicator output connections can be used with any of the applications l...

Страница 17: ...minal 23 on the control panel 4 Connect the R ring terminal on the communicator to terminal 24 on the control panel 5 Power the communicator by connecting its terminal 12V to terminal 5 on the control...

Страница 18: ...o the panel Press Yes 13 Configure additional options as needed then press Save Tech APP Activation 1 Go to the Customer Summary Systems 2 Tap the Add icon 3 Enter the System Name 4 In System Type sel...

Страница 19: ...ed or deleted in panel programming To revert the default code to 99 use the Clear All Codes option found in the Initialization menu Panels ship with the master code on the serial number label in paren...

Страница 20: ...ress CMD to advance to the next step CMD is also used to enter information into the communicator s memory such as an IP address or a zone name Press CMD after entering information Back Arrow Use the b...

Страница 21: ...er character or press CMD if finished NUMBER SELECT KEY 1 SELECT KEY 2 SELECT KEY 3 SELECT KEY 4 1 A B C 2 D E F 3 G H I 4 J K L 5 M N O 6 P Q R 7 S T U 8 V W X 9 Y Z space _ 0 Standard Keyboard Press...

Страница 22: ...NG Choose NO to leave existing zone information intact Choose YES to set all zones in the system to UNUSED CLEAR COMMUNICATION Choose NO to leave existing communication programming intact Choose YES t...

Страница 23: ...ly if this option is used FAIL TIME MINUTES Fail time allows the SCS 1R or SCS VR receivers to miss a defined number of check ins before logging that the panel is missing For example if cell check in...

Страница 24: ...the receiver The default is NO Supervisory Trouble Reports Choose YES to enable Supervisory Trouble Trouble Restoral Force Armed Late to Close and Fault reports to be sent to this receiver Choose NO...

Страница 25: ...remotely The default is YES Choose NO to disable remote disarming REMOTE OPTIONS RMT KEY DISARM NO YES SYSTEM REPORTS This option allows you to select which reports the communicator sends to the rece...

Страница 26: ...zone time can be from 4 250 seconds in one second increments Enter 0 to disable the cross zone time feature See Cross Zoning POWER FAIL DELAY Enter the time allowed for a power failure to occur befor...

Страница 27: ...to enable communication between the communicator and an Ademco Honeywell panel using the Z4 terminals Using the Ademco Honeywell ECP Bus the communicator can add delete and change user codes as well a...

Страница 28: ...e can be 1 15 minutes Enter 0 to provide continuous output Note The output is cutoff within 60 seconds of the programmed cutoff time The cutoff timer is shared by all outputs If a second output trips...

Страница 29: ...bad zones If a closing report is sent the user number is indicated as SCH on the SCS 1R or SCS VR receivers Choose NO to disable automatic arming for this area The default is NO Bad Zones At the time...

Страница 30: ...e responses are made automatically for the zone There are 12 zone types to choose from including Blank To select a new zone type press any select area The display lists the four zone types shown below...

Страница 31: ...when ZONE NO appears on the display Choose NO to make changes to the alarm action for a zone ALARM ACTION Change the default alarm characteristics of a zone type If you selected the non 24 hour zone t...

Страница 32: ...he receiver if bypass reports is set to YES CROSS ZONE Choose YES to enable cross zoning for this zone Cross zoning requires this zone to trip twice or this zone and another cross zoned zone to trip w...

Страница 33: ...Code You can change this code at any time to any combination of numbers from 1 5 digits long 1 65535 Do not use leading zeros for the lockout code 1 Press any select area The keypad displays ENTER COD...

Страница 34: ...eports are enabled in the Ademco Honeywell panel a duplicate message will also be sent to the central station Note Communicators with Version 194 and higher do not require you to log in to the VISTA p...

Страница 35: ...P SETUP and press any select key or area 2 At ECP SETUP VISTA 128 If the panel is a VISTA 128 select YES If the panel is a different model select NO 3 At INST CODE enter the ECP panel installer code a...

Страница 36: ...eypad buzzes END Press this select area to stop the walk test When the walk test ends or a 20 minute timeout expires a final sensor reset occurs The system test end message is sent to the receiver alo...

Страница 37: ...owing a Program output 17 to turn on when armed Stay Output Funct Enter 01 Press to continue Summary Screen 01 A E P Trig Press to continue Activated by Enter 2 Press to continue Enter Zn Type Enter 2...

Страница 38: ...HI HI HI LO LO LO LO HI HI LO LO HI HI LO LO HI TIP BROWN RING GRAY TIP GREEN RING RED BLACK RED SYNC COM DATA USE SA4120XM 1 CABLE 1 2 3 4 5 6 7 8 OUT 17 12 AUX GND OUT 18 VISTA 20P ONLY Ademco Vista...

Страница 39: ...gital Monitoring Products 35 Bosch Control Panel Option Bus to CellCom LTE for Reduced Noise Disturbance Option Bus CellCom LTE V PROG 12 G Z1 Z2 Z4 Z4 G Z3 R T O2 O1 R B Control Panel R B G Y Figure...

Страница 40: ...ed radio TV technician for help Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment If necessary the instal...

Страница 41: ...hite 685 R Surface Mount Conduit Backbox red 383 Replacement Dual Band Cellular Antenna 330 DSC DSC Remote Programming Harness Compatibility ECP Passthru VISTA 15 VISTA 20 VISTA 21 VISTA 128 DSC Passt...

Отзывы: