background image

736V INSTALLATION GUIDE   |     DIGITAL MONITORING PRODUCTS 

3

PROGRAM THE PANEL

Set the 736V Address

On XR550 panels, connect a 736V to any LX‑Bus. V‑Plex devices are addressed on one LX‑Bus per loop. On 

XR150 panels, address 501 is reserved for the 736V. 
Unused zones on an LX‑Bus connected to a 736V can be used for any non‑polling loop devices except access 

control devices. See Table 1 for more information about device addresses and zones.
After completing each of the following steps, press 

CMD

 to advance to the next option.

1.  Reset the panel. Enter 

6653

 (PROG) at the panel keypad and go to 

DEVICE SETUP

.

2.  At 

DEVICE NO

, enter the device number of the LX‑Bus slot taken up by the module.

3.  If the LX‑Bus already has zones programmed, 

ZONES PROGRAMMED CONTINUE? NO YES

 displays. To 

continue programming, select 

YES

Note:

 Selecting 

YES

 at 

ZONES PROGRAMMED CONTINUE?

 does not overwrite existing 

programming.

4.  At 

DEVICE NAME

, enter a name for the module.

5.  (XR550 only) At 

DEVICE TYPE

, select 

VPX

.

XR150/XR550

XR550 Only

Device

Zones

Device

Zones

Device

Zones

Device

Zones

Device

Zones

501

500‑595

601

600‑695

701

700‑795

801

800‑895

901

900‑995

Table 1: Device Addresses and V-Plex Zone Numbers

Note:

 Zones 96‑99 on any LX‑Bus that is connected to a 736V are diagnostic zones. For more information 

refer to the 736V V‑Plex Advanced Settings Guide (LT‑1934).

Program V‑Plex Zones

After completing each of the following steps, press 

CMD

 to advance to the next option.

1.  Go to 

ZONE INFORMATION

.

2.  At 

ZONE NO

, enter the device zone that corresponds to the LX‑Bus.

3.  At 

*UNUSED*

, enter the zone name.

4.  At 

ZONE TYPE

, select the zone type.

5.  At the Area Assignment section, select the area.

6.  At the 

NEXT ZN?

 prompt, select 

NO

.

7.  At the 

DMP WLS? NO YES

 prompt, select 

NO

.

8.  At 

VPLEX DEVICE SERIAL#

, enter 

A

 followed by the 7‑digit serial number.

9.  At the 

NEXT ZN?

 prompt, select 

YES

.

10.  Repeat steps 2 through 10 for the remaining devices.

11.  To save panel programming, go to 

STOP

 and press 

CMD

.

Turn on Outputs

Smoke and PIR motion detector zones require that the output corresponding to the programmed zone are 

turned on to report the status correctly. For example, if you have a PIR on zone 503, output 503 will need to 

be toggled on for the zone to report correctly.
Go to the User Menu, enter a valid code that has output authority. Go to 

OUTPUTS ON/OFF? 

and enter the 

output number that corresponds to the zone. Select top row key 3 to toggle the output 

ON

.

Note:

 Do not program smoke or PIR motion detector zones as outputs in 

OUTPUT INFO

.

4

Отзывы: