Digital Monitoring Products, Inc. | 736P Installation and Programming Guide
9
Convert Zonex Points to DMP Zones
When powered up, the 736P communicates with the Radionics POPEX or OctoPOPIT
module and creates a table of equivalent DMP zone addresses. The current zone states
are received from the Radionics module and transmitted to the DMP panel (Normal, Open,
Shorted). The conversion tables show the Radionics point number and the corresponding
DMP zone number for the LX‑Bus and Keypad Bus. Once the corresponding DMP zone is
determined from the tables, it must be programmed into the panel.
How to Use the Tables
The conversion tables on the following pages provide the Radionics ZONEX module switch
setting and the expanded 119‑point Radionics ZONEX Bus #1 and ZONEX Bus #2 numbers.
1.
To find a corresponding DMP zone from either table, select the Radionics ZONEX
point, the appropriate DMP bus type, and the appropriate DMP panel type. Table
1 lists the Keypad Bus numbers for all DMP panels. Tables 2 and 3 list LX‑Bus
numbers for XR150/XR550 Series panels.
2.
Find the ZONEX Bus point number in Table 1 and the corresponding DMP Keypad
Bus zone number is listed in one of the columns to the right.
3.
For Tables 2 and 3, find the ZONEX Bus point number and the corresponding DMP
LX‑Bus zone number is listed in one of the columns to the right.
Example:
ZONEX Bus #1 point 022 on the expanded 119‑point ZONEX Bus connected
to a DMP LX‑Bus 1 corresponds to DMP zone 513 on an XR150/XR550 panel.
Note:
Radionics points 109‑127 and 229‑247 are not supported. Those ZONEX Bus
points can be reassigned to any available unused zones on the DMP panel.