The typical plumbing diagram illustrates the standard plumbing layout with a single heat pump unit. Following the diagram
from left to right, the plumbing sequence is as follows:
Pool Pool Pump Filter Heat Pump Check Valve Chemical Loop Chlorinator Pool
A detachable connection (union) must be utilized immediately adjacent to heater to facilitate servicing and winterizing of
the unit.
Installation
A:
Chlorinator
B:
Chemical Loop or Optional Chlorine Generation System
C:
Check Valve
D:
Pool Heater
E: E:
3 Manual Bypass Valve
(Recommended installation)
F:
Filter
G:
Pool Pump
C/-&%0()0'%,/10),7'31+'%00%1%00+2'+.%20$6A
DBBDF<DB0F5DDB
30HPRA-E-410
50HPRA-E-410
80HPRA-E-410
100HPRA-E-410
Capacidad
50HPRA-E-410
80HPRA-E-410
100HPRA-E-410
(3 PH)
(3 PH)
(3 PH)
Características eléctricas
> El aparato ha de ser instalado por una persona calificada en conformidad a las ordenanzas y códigos nationales
(NFC - 15 - 100).
> Los cables de suministro de energía deben contar con una certificación YZW, y su peso no debe ser inferior al establecido por
el código de designación 60245 IEC 57.
> La alimentación de la bomba de calor debe efectuarse mediante un circuito eléctrico exclusivo.
> Examine en el cuadro de abajo las características eléctricas, principalmente el voltaje, la capacidad
del dispositivo de protección máxima contra la irrupción de corriente y la dimensión de los conductores de alimentación.
> La unidad de condensación de la bomba de calor debe conectarse con una fuente de alimentación eléctrica
debidamente puesta a tierra. Procure que la conexión a tierra de esta unidad sea correcta.
> Consulte los códigos y normas eléctricas de su localidad antes de adquirir los cables.
> Utilice sólo cables de alimentación con hilos de cobre.