XWEB 3000 – rel.1.3–
the same modifications in these menus. This is very important because all the values stored inside
XWEB 3000 devices section must be the same as the ones stored inside the EEPROM of the
instrument. A common error for example is to modify “Generic Alarm” to some other values inside the
instrument, than leave the value marked inside Advanced section. XWEB 3000 will send you an alarm
every time the switch changes status, even if it is not an alarm input.
“Status/Alarms” section allows you to customize your instruments, of course the same values have to
be set both on XWEB 3000 and the instruments themselves.
“Commands” row is very important. You have to mark same values that you have marked before in the
other section. In order to give Xweb 3000 the possibility to send commands to the instruments. This is
necessary because for example if you have changed “Generic Alarm” to “Ausiliary” in “digital
Resources” section, then you have to mark “Aux on” and “Aux off” in “Commands” section to be able
to turn on/off the output by means of the Xweb 3000. Of course you have to do this kind of changes
every time you have made some modifications to the instruments.
98/111
1592010600