background image

dIXEL

 

Installing and Operating Instructions 

PRELIMINARY

 

 

MANUAL  RNC 2007 053  PRELIMINARY T66 + XW60K.doc 

T66 – XW60K 

2/4 

HAL

” for high temperature alarm (“

LAL

” fot the minimum allarm), followed 

by the 

Maximum (minimum) temperature. 

Then the “

tiM

” (

tiM

e) message is displayed, followed by the 

“Duration” 

in 

h.mm. 

3. 

Then the instrument displays the temperature once again. 

 

NOTE1: 

if an alarm is still occurring the “

tim

” shows the partial duration. 

NOTE2:

 the alarm is recorded when the temperature come back to normal values 

5.2  HOW TO RESET A RECORDED ALARM OR ONE THAT IS 
STILL OCCURRING 

1.  Hold the SET key pressed for more than 3s, while the recorded alarm is 

displayed. (the rSt message will be displayed) 

2.  To confirm the operation, the “rSt” message starts blinking and the normal 

temperature will be displayed. 

6. MAIN FUNCTIONS 

6.1  HOW TO SEE THE SETPOINT 

 

1.  Push and immediately release the 

SET 

key: the display will 

show the Set point value; 

2.  Push and immediately release the 

SET 

key or wait for 5 seconds to display 

the probe value again. 

6.2  HOW TO CHANGE THE SETPOINT 

1. Push 

the 

SET 

key for more than 2 seconds to change the Set point value; 

2.  The value of the set point will be displayed and the 

 LED starts blinking; 

3.  To change the Set value push the 

or 

n

 arrows within 10s. 

4.  To memorise the new set point value push the 

SET

 key again or wait 10s. 

6.3  HOW TO START A MANUAL DEFROST 

 

Push the 

DEF 

key for more than 2 seconds and a manual 

defrost will start. 

6.4  HOW TO CHANGE A PARAMETER VALUE 

To change the parameter’s value operate as follows: 

 

1. Enter the Programming mode by pressing the Set and 

DOWN key for 3s (

 and 

 start blinking). 

2. Select the required parameter. 
3. Press the “

SET

” key to display its value (now only the 

 

LED is blinking). 

4. Use “

UP

” or “

DOWN

” to change its value. 

5. Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the 

time-out to expire. 

6.5  THE HIDDEN MENU 

The hidden menu Includes all the parameters of the instrument. 

6.5.1  HOW TO ENTER THE HIDDEN MENU 

 

1.  Enter the Programming mode by pressing the Set + 

n

 

key for 3s (LED 1 and 

 start blinking). 

2.  When a parameter is displayed keep pressed the Set+

n

 

for more than 7s. The Pr2 label will be displayed 
immediately followed from the HY parameter.  

NOW YOU ARE IN THE HIDDEN MENU. 

3. Select the required parameter. 
4. Press the “

SET

” key to display its value (Now only the 

 LED is blinking). 

5. Use 

or 

n

 to change its value. 

6. Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + 

or wait 15s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the 

time-out to expire. 
 

6.5.2  HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE 
FIRST LEVEL AND VICEVERSA. 

Each parameter present in the HIDDEN MENU can be removed or put into “THE 
FIRST LEVEL” (user level) by pressing 

“SET + 

n

.  

In HIDDEN MENU when a parameter is present in First Level the decimal point is 
on. 

6.6  HOW TO LOCK THE KEYBOARD 

 

1. 

 

Keep pressed for more than 3 s the 

and 

n

 keys. 

2. 

 

The “

POF

” message will be displayed and the keyboard will be locked. At this 

point it will be possible only to see the set point or the MAX o Min temperature 
stored 

3. 

 

If a key is pressed more than 3s the “POF” message will be displayed. 

6.7  TO UNLOCK THE KEYBOARD 

Keep pressed together for more than 3s the 

and 

n

 keys, till the 

“Pon” 

message will be displayed. 

6.8  THE CONTINUOUS CYCLE 

 

When defrost is not in progress, it can be activated by 
holding the “

o

” key pressed for about 3 seconds. 

The compressor operates in continuous mode for the time set through the “

CCt

” 

parameter. The cycle can be terminated before the end of the set time using the 
same activation key “

o

” for 3 seconds. 

7. PARAMETERS 

REGULATION 
Hy  

Differential

: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point. 

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut 
OUT is when the temperature reaches the set point. 

LS    Minimum  set  point

: (- 50°C÷SET/-58°F÷SET): Sets the minimum 

acceptable value for the set point. 

US 

  Maximum set point

: (SET÷110°C/ SET÷230°F). Set the maximum 

acceptable value for set point. 

Ot    Thermostat  probe  calibration

: (-12.0÷12.0°C; -120÷120°F) allows to 

adjust possible offset of the thermostat probe. 

P2P  Evaporator probe presence: n

= not present: the defrost stops by time;  

y=

 present: the defrost stops by temperature. 

OE   Evaporator probe calibration

: (-12.0÷12.0°C; -120÷120°F). allows to 

adjust possible offset of the evaporator probe. 

OdS   Outputs activation delay at start up: 

(0÷255min) This function is enabled 

at the initial start up of the instrument and inhibits any output activation for 
the period of time set in the parameter. 

 

AC    Anti-short  cycle  delay

: (0÷50 min) minimum interval between the 

compressor stop and the following restart. 

CCt   Compressor ON time during continuous  cycle

: (0.0÷24.0h; res. 10min) 

Allows to set the length of the continuous cycle: compressor stays on 
without interruption for the CCt time. Can be used, for instance, when the 
room is filled with new products. 

Con  Compressor ON time with faulty probe

: (0÷255 min) time during which 

the compressor is active in case of faulty thermostat probe. With COn=0 
compressor is always OFF. 

COF   Compressor OFF time with faulty probe

: (0÷255 min) time during which 

the compressor is OFF in case of faulty thermostat probe. With COF=0 
compressor is always active. 

CH  Type of action: 

CL = cooling; Ht = heating.

 

DISPLAY 
CF   Temperature measurement unit

°C

=Celsius; 

°F

=Fahrenheit. 

WARNING

When the measurement unit is changed the SET point and the values  of 
the parameters Hy, LS, US, Ot, ALU and ALL have to be checked and 
modified if necessary). 

rES  Resolution (for °C)

: (in = 1°C; dE = 0.1 °C) allows decimal point display. 

Lod Display : 

select which probe is displayed by the instrument:

 P1

 = 

Thermostat probe; 

P2

 = Evaporator probe 

dLy display 

delay: 

(0-15 minutes) when the temperature increases, the display 

is updated of 1 °C after this time. 

DEFROST 
tdF   Defrost type

: EL = electrical heater; in = hot gas 

dtE  Defrost termination temperature

: (-50÷50 °C/ -58÷122°F) (Enabled only 

when EdF=Pb) sets the temperature measured by the evaporator probe, 
which causes the end of defrost. 

IdF   Interval between defrost cycles

: (0÷120h) Determines the time interval 

between the beginning of two defrost cycles. 

MdF   (Maximum) length for defrost

: (0÷255min) When 

P2P = n

, (not 

evaporator probe: timed defrost) it sets the defrost duration, when 

P2P = y

 

(defrost end based on temperature) it sets the maximum length for defrost. 

dSd   Start defrost delay

: ( 0÷99min) This is useful when different defrost start 

times are necessary to avoid overloading the plant.  

dFd   Temperature displayed during defrost

: (

rt

 = real temperature; 

it

 = 

temperature at defrost start; 

SEt

 = set point; 

dEF

 = “dEF” label) 

dAd   MAX display delay after defrost

: (0÷255min). Sets the maximum time 

between the end of defrost and the restarting of the real room temperature 
display. 

Fdt Drip 

time

: (0

÷

120 min) time interval between reaching defrost termination 

temperature and the restoring of the control’s normal operation. This time 
allows the evaporator to eliminate water drops that might have formed due 
to defrost. 

dPo  First defrost after start-up

: y = immediately; n = after the IdF time 

dAF  Defrost delay after continuous cycle

: (0

÷

23.5h) time interval between the 

end of the fast freezing cycle and the following defrost related to it. 

FANS 
FnC   Fans operating mode

C-n

= runs with the compressor, OFF during 

defrost;  

o-n

 = continuous mode, OFF during defrost; 

C-Y

 = runs with the 

compressor, ON during defrost; 

o-Y

 = continuous mode, ON during defrost;  

Fnd   Fans delay after defrost:

 (0÷255min) Time interval between end of defrost 

and evaporator fans start.

 

FSt 

  Fans stop temperature

: (-50÷50°C/122°F) setting of temperature, 

detected by evaporator probe, above which fans are always OFF. 

ALARMS 
ALc    Temperature alarms configuration

: (Ab; rE) 

Ab

= absolute 

temperature: alarm temperature is given by the ALL or ALU values. 

rE

 = 

temperature alarms are referred to the set point. Temperature alarm is 
enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” 
values. 

ALu   MAXIMUM  temperature alarm

: (SET÷110°C; SET÷230°F) when this 

temperature is reached  the alarm is enabled, after the “ALd” delay time. 

Содержание XW60K

Страница 1: ...ordt aangeraden ook op de voeding van het toestel zelf een dergelijke RC keten te plaatsen 2 ALGEMENE BESCHRIJVING De XW60K afmeting 32x74 mm is een door een microprocessor gestuurde regelaar die geschikt is voor toepassing bij zowel positieve als negatieve koelkamers De regelaar is voorzien van 3 uitgangsrelais om compressor ontdooisysteem elektrisch of heetgas en verdamperventilatoren te sturen ...

Страница 2: ... EN VICEVERSA Elke parameter in het VERBORGEN MENU kan verplaatst worden naar HET EERSTE NIVEAU gebruikersniveau door op de SET n te drukken Als een parameter naar gebruikersniveau is verplaatst wordt dit in het VERBORGEN MENU aangegeven door een decimale punt 6 6 HET TOETSENBORD BLOKKEREN 1 Hou de o en n toetsen gedurende 3 seconden tegelijk ingedrukt 2 De melding POF wordt weergegeven en het toe...

Страница 3: ...werken CPr F_C compressor UIT Nadat de deur is geopend en een vertraging ingesteld via did is het deuralarm geactiveerd worden het scherm geeft de melding dA en de regelaar herstart Het alarm stopt zodra de digitale invoer gedeactiveerd is Met open deur is het alarm hoge en lage temperatuur uitgeschakeld 8 2 GENERIC ALARM i1F EAL Als de digitale invoer geactiveerd is wacht het toestel gedurende de...

Страница 4: ...ONNECTIES 14 1 XW60K BEDRADING SCHEMA MET JUMPER 14 2 XW60K BEDRADINGSCHEMA ZONDER JUMPER 15 FABRIEKSINSTELLINGEN PARAMETERS Label Beschrijving Bereik C F Set Afstelling LS US 5 0 Hy Differential 0 1 25 5 C 1 255 F 2 0 LS Minimum afstelling 50 C SET 58 F SET 40 0 US Maximum afstelling SET 110 C SET 230 F 110 Ot CalibratieThermostaat sonde 12 12 C 120 120 F 0 0 P2P Verdamper sonde aanwezig n not pr...

Страница 5: ... NTC or PTC probe inputs one for temperature control the other to be located onto the evaporator to control the defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard NOTE on the keyboard is present a jumper enabling or disabling the digital input Please refer to wiring diagrams to see how the connections a...

Страница 6: ...he set point LS Minimum set point 50 C SET 58 F SET Sets the minimum acceptable value for the set point US Maximum set point SET 110 C SET 230 F Set the maximum acceptable value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n not present the defrost stops by time y present the defrost stops...

Страница 7: ...h off and on the instrument to restart normal regulation 8 5 START DEFROST I1F DFR It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING I1F HTR This function allows to inve...

Страница 8: ...n 15 COF Compressor OFF time with faulty probe 0 255 min 30 CH Kind of action CL cooling Ht heating cL CF Temperature measurement unit C F C rES Resolution in integer dE dec point dE dLy Display delay 0 15 min P1 Lod Probe displayed P1 P2 0 tdF Defrost type EL el heater in hot gas EL dtE Defrost termination temperature 50 50 C 8 IdF Interval between defrost cycles 1 120 ore 6 MdF Maximum length fo...

Страница 9: ...ées sonde NTC ou PTC la première pour le contrôle de la température la seconde placée près de l évaporateur pour contrôler la température de fin de dégivrage Ce régulateur est entièrement configurable grâce à ses paramètres facilement programmables à partir du clavier NOTE sur le clavier est present un switch qui permet d activer ou de désactiver le vérouillage Se referrer aux diagrames de connexi...

Страница 10: ...igurée au paramètre CCt Le cycle peut être terminé avant la fin du temps programmé en appuyant sur la même touche o pendant 3 secondes 7 LISTE DES PARAMETRES REGULATION Hy Différentiel 0 1 25 5 C 1 255 F Différentiel du point de consigne toujours positif Le compresseur fonctionne lorsque point de consigne différentiel Hy Le compresseur s arrête lorsque la température atteint le point de consigne L...

Страница 11: ...on de l entrée digitale 8 3 MODE ALARME SERIEUSE i1F bAL Quand l entrée digitale est activée le régulateur attend la temporisation did avant de signaler le message d alarme CA Les sorties relais sont désactivées L alarme sera arrêtée juste après la désactivation de l entrée digitale 8 4 SWITCH PRESSION i1F PAL Si durant l intervalle de temps paramétré en did le switch pression atteint le nombre d ...

Страница 12: ...e 0 255 min 0 AC Temporisation anti court cycle 0 50 min 1 Code Désignation Gamme Par défaut CCt Durée cycle continu 0 24 0h 0 0 Con Compresseur ON en cas de défaut de sonde 0 255 min 15 CoF Compresseur OFF en cas de défaut de sonde 0 255 min 30 CH Type d action CL froid Ht chaud CL CF Unité de mesure de la température C F C rES Résolution sans avec point décimal dE in dE dLy Temporisation afficha...

Страница 13: ...IBUNG Aktualisierung Das Tafeleinbaugerät XW60K T66 mit dem Frontmass 74x32mm ist ein Mikroprozessors Gesteuerter Kühlstellenregler für Normal und Tiefkühltemperaturen Mit drei Relais Ausgängen für die Regelung des Verdichter Abtauungen welche elektrisch oder Heissgas sein kann und Verdampfer Gebläse Abhängig von der Ausführung können zu drei Fühler NTC oder PTC gleichzeitig angeschlossen werden J...

Страница 14: ...FRIEREN Kann nur aktiviert werden wenn nicht gerade eine Abtauung aktiv ist Die HOCH Taste mind 3s gedrückt halten Der Verdichter bleibt für die Zeit CCt kontinuierlich eingeschaltet Solange bis der Sollwert ccS erreicht wurde Zum Schockgefrieren zu beenden nochmals mind 3s HOCH Taste gedrückt halten 7 PARAMETER BESCHREIBUNG REGELUNG Hy Schalthysterese 0 1 C 25 5 C Zur Regelung des Verdichters EIN...

Страница 15: ...dampfer Fühler rEL Software Version Release Ptb Parameter Tabelle Werksnummer 8 DIGITALER EINGANG Digital Eingang ist vorhanden nur wenn der überbrücker Geschenk in der Tastatur nicht eingesetzt wird Wenn der überbrücker eingesetzt wird stellen Sie bitte i1P OP ein Ein potentialfreier digitaler Eingang steht zur Verfügung Diese kann via Parameter i1F konfiguriert werden Nur wenn Par P3P n 8 1 TÜRK...

Страница 16: ...ur für Betrieb 0 60 C Lager Temperatur 25 60 C Rel Feuchte 20 85 ohne Kondensierung Mess Bereich NTC Fühler 40 bis 110 C Auflösung 0 1 K oder 1 K oder 1 F vorgebbar Genauigkeit bei 25 C 0 5 C 1 Ziffer 14 ANSCHLUSS PLAN 14 1 XW60K ELEKTRISCHE ANSCHLÜSSE MIT DEM ÜBERBRÜCKER EINGESETZT 14 2 XW60K ELEKTRISCHE ANSCHLÜSSE MIT DEM ÜBERBRÜCKER NICHT EINGESETZT 15 PARAMETER WERKSVORGABEN Label Beschreibung...

Отзывы: