Installing and Operating Instructions 

PRELIMINARY

 

 

MANUAL  RNC 2007 053  PRELIMINARY T66 + XW60K.doc 

T66 – XW60K 

4/4 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm  

Power supply: 

from

 XW60K 

power module

 

Display

: 3 digits, red LED, 14,2 mm high.  

 
Power module XW60K  
Case: 
“OS”

: open board 132x 94 mm; height: 40mm. 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and 6,3mm 

Faston 

Power supply: 

230Vac

 

Power absorption: 

10VA max.

 

Inputs

: 2 NTC or PTC probes 

Digital inputs

: 1 free voltage 

Relay outputs: 

Total current on loads MAX. 20A

 

 compressor:

   relay SPST 20(8) A, 250Vac  

 defrost:

  

relay SPST 8(3) A, 250Vac 

 fan: 

relay SPST 8(3) A, 250Vac  

 light: 

relay SPST 8(3) A, 250Vac  

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B. 

Pollution grade: 

normal 

Software class: 

A.

 

Operating temperature: 

0÷60 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range:  
 NTC 

probe: 

-40÷110°C (-58÷230°F) 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

 

14. CONNECTIONS 

14.1  XW60K WIRING CONNECTIONS WITH JUMPER NOT 
INSERTED 

 

 

14.2  XW60K WIRING CONNECTIONS WITH JUMPER 
INSERTED 

 

 

 

15.  DEFAULT SETTING VALUES  

Label Name Range 

Default

Set 

Set point 

LS÷US 

-5.0 

Hy 

Differential 

0,1

÷

25.5°C/ 1

÷

 255°F 

2.0 

LS 

Minimum set point 

-50°C

÷

SET/-58°F

÷

SET 

-40.0

US 

Maximum set point 

SET

÷

110°C/ SET 

÷

 230°F 

110

Ot 

Thermostat probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 

P2P

Evaporator probe presence 

n=not present; Y=pres. 

OE 

Evaporator probe calibration 

-12

÷

12°C /-120

÷

120°F 

0.0 

OdS

Outputs delay at start up 

0÷255 min 

AC 

Anti-short cycle delay 

÷

 50 min 

CCt 

Continuos cycle duration 

0.0÷24.0h 

0.0 

COn

Compressor ON time with faulty 
probe 

÷

 255 min 

15 

COF

Compressor OFF time with faulty 
probe 

÷

 255 min 

30 

CH 

Kind of action 

CL=cooling; Ht= heating 

cL 

CF 

Temperature measurement unit 

°C 

÷

 °F 

°C 

rES 

Resolution 

in=integer; dE= dec.point

 

dE 

dLy 

Display delay  

÷

 15 min

 

P1 

Lod 

Probe displayed 

P1;P2 

tdF 

Defrost type 

EL=el. heater;  in= hot gas 

EL 

dtE 

Defrost termination temperature 

-50 

÷

 50 °C 

IdF 

Interval between defrost cycles 

÷

 120 ore 

MdF

(Maximum) length for defrost 

÷

 255 min 

30 

dSd

Start defrost delay 

0÷99min 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

dAd

MAX display delay after defrost 

0 ÷ 255 min 

30 

Fdt 

Draining time 

0÷120 min 

dPo

 

First defrost after startup 

n=after IdF; y=immed. 

dAF

Defrost delay after fast freezing 

0 ÷ 23h e 50’ 

0.0 

Fnc 

Fan operating mode 

C-n, o-n, C-y, o-Y 

o-n 

Fnd 

Fan delay after defrost 

0÷255min 

10 

FSt 

Fan stop temperature -50÷50°C/-58÷122°F 

ALc 

Temperat. alarms configuration 

rE= related to set; 

Ab = absolute 

Ab 

ALU

MAXIMUM temperature alarm 

Set

÷

110.0°C; Set÷230°F 

110

ALL

Minimum temperature alarm 

-50.0°C

÷

Set/ -58°F

÷

Set 

-40 

ALd

Temperature alarm delay 

÷

 255 min 

15 

dAO

Delay of temperature alarm at 
start up 

÷

 23h e 50’ 

1.3 

oA2 

Relay 5-6 configuration 

ALr= alarm; dEF=no select it; 

LHt=auxiliary; onF=always on; 

Fan= no select it 

LHt 

i1P 

Digital input polarity 

oP=opening;CL=closing 

oP 

i1F 

Digital input configuration 

EAL=extern. alarm; bAL=lock 

regulation; PAL=press. switch; 

dor=door switch; dEF=defrost; 

LHt=disabled; Htr = Cooling - 

heating 

EAL

did 

Digital input alarm delay 

0÷255min 

Lio 

Light on with door switch 
activated 

n, y 

Nps

Number of activation of pressure 
switch 

0 ÷15 

15 

odc 

Compressor status with open 
door: 

no; Fan; CPr; F_C

 

no 

PbC

Kind of probe 

Ptc; ntc 

ntc 

dP1 

Room probe display 

-- 

- - - 

dP2 

Evaporator probe display 

-- 

- - - 

rEL 

Software release 

-- 

- - - 

Ptb 

Map code 

-- 

- - - 

 
Hidden parameters 
 

 

 

 

dIXEL

 S.p.a. 

Z.I. Via dell’Industria, 27  -  32010 Pieve d’Alpago (BL) ITALY 
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13 

http://www.dixell.com

 E-mail: 

[email protected]

 

Содержание XW60K

Страница 1: ...ordt aangeraden ook op de voeding van het toestel zelf een dergelijke RC keten te plaatsen 2 ALGEMENE BESCHRIJVING De XW60K afmeting 32x74 mm is een door een microprocessor gestuurde regelaar die geschikt is voor toepassing bij zowel positieve als negatieve koelkamers De regelaar is voorzien van 3 uitgangsrelais om compressor ontdooisysteem elektrisch of heetgas en verdamperventilatoren te sturen ...

Страница 2: ... EN VICEVERSA Elke parameter in het VERBORGEN MENU kan verplaatst worden naar HET EERSTE NIVEAU gebruikersniveau door op de SET n te drukken Als een parameter naar gebruikersniveau is verplaatst wordt dit in het VERBORGEN MENU aangegeven door een decimale punt 6 6 HET TOETSENBORD BLOKKEREN 1 Hou de o en n toetsen gedurende 3 seconden tegelijk ingedrukt 2 De melding POF wordt weergegeven en het toe...

Страница 3: ...werken CPr F_C compressor UIT Nadat de deur is geopend en een vertraging ingesteld via did is het deuralarm geactiveerd worden het scherm geeft de melding dA en de regelaar herstart Het alarm stopt zodra de digitale invoer gedeactiveerd is Met open deur is het alarm hoge en lage temperatuur uitgeschakeld 8 2 GENERIC ALARM i1F EAL Als de digitale invoer geactiveerd is wacht het toestel gedurende de...

Страница 4: ...ONNECTIES 14 1 XW60K BEDRADING SCHEMA MET JUMPER 14 2 XW60K BEDRADINGSCHEMA ZONDER JUMPER 15 FABRIEKSINSTELLINGEN PARAMETERS Label Beschrijving Bereik C F Set Afstelling LS US 5 0 Hy Differential 0 1 25 5 C 1 255 F 2 0 LS Minimum afstelling 50 C SET 58 F SET 40 0 US Maximum afstelling SET 110 C SET 230 F 110 Ot CalibratieThermostaat sonde 12 12 C 120 120 F 0 0 P2P Verdamper sonde aanwezig n not pr...

Страница 5: ... NTC or PTC probe inputs one for temperature control the other to be located onto the evaporator to control the defrost termination temperature The instrument is fully configurable through special parameters that can be easily programmed through the keyboard NOTE on the keyboard is present a jumper enabling or disabling the digital input Please refer to wiring diagrams to see how the connections a...

Страница 6: ...he set point LS Minimum set point 50 C SET 58 F SET Sets the minimum acceptable value for the set point US Maximum set point SET 110 C SET 230 F Set the maximum acceptable value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows to adjust possible offset of the thermostat probe P2P Evaporator probe presence n not present the defrost stops by time y present the defrost stops...

Страница 7: ...h off and on the instrument to restart normal regulation 8 5 START DEFROST I1F DFR It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is expired 8 6 INVERSION OF THE KIND OF ACTION HEATING COOLING I1F HTR This function allows to inve...

Страница 8: ...n 15 COF Compressor OFF time with faulty probe 0 255 min 30 CH Kind of action CL cooling Ht heating cL CF Temperature measurement unit C F C rES Resolution in integer dE dec point dE dLy Display delay 0 15 min P1 Lod Probe displayed P1 P2 0 tdF Defrost type EL el heater in hot gas EL dtE Defrost termination temperature 50 50 C 8 IdF Interval between defrost cycles 1 120 ore 6 MdF Maximum length fo...

Страница 9: ...ées sonde NTC ou PTC la première pour le contrôle de la température la seconde placée près de l évaporateur pour contrôler la température de fin de dégivrage Ce régulateur est entièrement configurable grâce à ses paramètres facilement programmables à partir du clavier NOTE sur le clavier est present un switch qui permet d activer ou de désactiver le vérouillage Se referrer aux diagrames de connexi...

Страница 10: ...igurée au paramètre CCt Le cycle peut être terminé avant la fin du temps programmé en appuyant sur la même touche o pendant 3 secondes 7 LISTE DES PARAMETRES REGULATION Hy Différentiel 0 1 25 5 C 1 255 F Différentiel du point de consigne toujours positif Le compresseur fonctionne lorsque point de consigne différentiel Hy Le compresseur s arrête lorsque la température atteint le point de consigne L...

Страница 11: ...on de l entrée digitale 8 3 MODE ALARME SERIEUSE i1F bAL Quand l entrée digitale est activée le régulateur attend la temporisation did avant de signaler le message d alarme CA Les sorties relais sont désactivées L alarme sera arrêtée juste après la désactivation de l entrée digitale 8 4 SWITCH PRESSION i1F PAL Si durant l intervalle de temps paramétré en did le switch pression atteint le nombre d ...

Страница 12: ...e 0 255 min 0 AC Temporisation anti court cycle 0 50 min 1 Code Désignation Gamme Par défaut CCt Durée cycle continu 0 24 0h 0 0 Con Compresseur ON en cas de défaut de sonde 0 255 min 15 CoF Compresseur OFF en cas de défaut de sonde 0 255 min 30 CH Type d action CL froid Ht chaud CL CF Unité de mesure de la température C F C rES Résolution sans avec point décimal dE in dE dLy Temporisation afficha...

Страница 13: ...IBUNG Aktualisierung Das Tafeleinbaugerät XW60K T66 mit dem Frontmass 74x32mm ist ein Mikroprozessors Gesteuerter Kühlstellenregler für Normal und Tiefkühltemperaturen Mit drei Relais Ausgängen für die Regelung des Verdichter Abtauungen welche elektrisch oder Heissgas sein kann und Verdampfer Gebläse Abhängig von der Ausführung können zu drei Fühler NTC oder PTC gleichzeitig angeschlossen werden J...

Страница 14: ...FRIEREN Kann nur aktiviert werden wenn nicht gerade eine Abtauung aktiv ist Die HOCH Taste mind 3s gedrückt halten Der Verdichter bleibt für die Zeit CCt kontinuierlich eingeschaltet Solange bis der Sollwert ccS erreicht wurde Zum Schockgefrieren zu beenden nochmals mind 3s HOCH Taste gedrückt halten 7 PARAMETER BESCHREIBUNG REGELUNG Hy Schalthysterese 0 1 C 25 5 C Zur Regelung des Verdichters EIN...

Страница 15: ...dampfer Fühler rEL Software Version Release Ptb Parameter Tabelle Werksnummer 8 DIGITALER EINGANG Digital Eingang ist vorhanden nur wenn der überbrücker Geschenk in der Tastatur nicht eingesetzt wird Wenn der überbrücker eingesetzt wird stellen Sie bitte i1P OP ein Ein potentialfreier digitaler Eingang steht zur Verfügung Diese kann via Parameter i1F konfiguriert werden Nur wenn Par P3P n 8 1 TÜRK...

Страница 16: ...ur für Betrieb 0 60 C Lager Temperatur 25 60 C Rel Feuchte 20 85 ohne Kondensierung Mess Bereich NTC Fühler 40 bis 110 C Auflösung 0 1 K oder 1 K oder 1 F vorgebbar Genauigkeit bei 25 C 0 5 C 1 Ziffer 14 ANSCHLUSS PLAN 14 1 XW60K ELEKTRISCHE ANSCHLÜSSE MIT DEM ÜBERBRÜCKER EINGESETZT 14 2 XW60K ELEKTRISCHE ANSCHLÜSSE MIT DEM ÜBERBRÜCKER NICHT EINGESETZT 15 PARAMETER WERKSVORGABEN Label Beschreibung...

Отзывы: