DIMENSIONS 

 
 

15 

CONNECTIONS 

 

 

 

 

16 

DEFAULT SETTING VALUES 

 

Label  Name 

  Range 

Default 

 

REGULATION 

 

 

Set1  Set point1 

LS÷US 

40,0 

Set2  Set point2 

LS2÷US2 

40,0 

Hy 

Differential for set1 

0,1÷25,5 °C  

2,0 

Hy2  Differential for set2 

0,1÷25,5 °C  

2,0 

LS 

Minimum set point1 

 -50,0°C÷SET1  

-40,0 

US 

Maximum set point1 

SET1 ÷ 110°C  

50,0 

LS2  Minimum set point2 

 -50,0°C÷SET2 

-40,0 

US2  Maximum set point2 

SET2 ÷ 110°C  

60,0 

OdS  Outputs activation delay at start up 

0÷255 min. 

AC 

Anti-short cycle delay 

0÷30 min. 

AC1  Second compressor start delay 

0÷255s 

10 

Ac2 

Second compressor start delay progr.2 

0 ÷ 255s 

10 

on 

Minimum time a compressor remains on (it’s used both 
for compr. 1 and 2) 

0÷30 minutes 

Mon 

Maximum  time  compressor  is  continuously  on 
(permanent run monitoring) 

0÷120min 

cP2 

Compressor 2 enabled with program 2 

y = yES; n = no 

yES 

COn  Compressor ON time with faulty probe 

0÷255 min. 

15 

COF  Compressor OFF time with faulty probe 

0÷255 min. 

30 

S2F  Second set point enabling  

yES÷no 

yES 

 

DISPLAY 

 

 

CF 

Temperature measurement unit 

°C ÷ °F 

°C 

Label  Name 

  Range 

Default 

rES 

Resolution (integer/decimal point) 

in ÷ dE 

dE 

dot 

Display offset, 

program 1

 

0÷25.5 °C 

2.0 

do2 

Display offset, program 2 

0÷25.5 °C 

2.0 

dHy  Display histeresys 

0÷25.5 °C 

2.0 

 

DEFROST 

 

 

MdF  Defrost key enabling 

yES= enabled 

no= disabled 

YES 

tdF 

Defrost type 

rE,   in  

rE 

EdF  Kind of defrost 

rtc, in 

rtc 

dtE 

Defrost termination temperature (1°Evaporator) 

-50,0÷110°C  

8,0 

dt2 

Defrost termination temperature for program 2 

-50.0°C o –58°F ÷ 110°C o 

230°F  

8,0 

IdF 

Interval between defrost cycles 

1÷120h 

12 

id2 

Interval between defrost cycles for the program 2 

1 ÷ 120 hours 

12 

Mtd 

(Maximum) length for 1° defrost 

0÷255 min. 

30 

Mt2 

(Maximum) length of defrost for the program 2 

0 ÷ 255 minuts 

30 

dFd 

Display during defrost 

dEG; dEF 

dEF 

dSd 

Defrost delay 

0÷255min 

Fdt 

Draining time 

0÷60 min. 

dPO  First defrost after start up 

n ÷ y 

no 

 

FANS 

 

 

CFE  Condenser fan working during defrost 

yES÷no 

YES 

FnC  Fans operating mode 

C-n, C-y, O-n, O-y  

o-n 

Fc2 

Fans operating mode with program 2 

c_n

 / 

c_Y 

o_n

 / 

o_Y

 

o-n 

Fnd 

Fans delay after defrost 

0÷255 min. 

FSt 

Fans stop temperature 

-50,0÷110°C  

2.0 

 

ALARMS 

 

 

ALU  MAXIMUM temperature alarm for set1 

-50,0÷110°C 

50.0 

Au2  MAXIMUM temperature alarm for set2 

-50,0÷110°C 

50.0 

ALd  Temperature alarm delay 

0÷255 min. 

15 

dAO  Delay of temperature alarm at start up 

0 ÷ 23h 50 min. 

1,3 

tBA 

Alarm relay silencing 

yES÷no 

no 

oAP  Alarm relay polarity 

oP, cL 

oP 

ArE 

Digital input 1 actives the alarm relay 

yES÷no

 

no 

 

ANALOGUE INPUTS 

 

 

Ot 

Thermostat probe calibration 

-12,0÷12,0°C  

0.0 

P2P  Evaporator probe presence 

no ÷ yES 

yES 

OE 

Evaporator probe calibration 

-12,0÷12,0°C  

0.0 

P3P  Second evaporator probe presence 

no ÷ yES 

no 

O3 

Second evaporator probe calibration 

-12,0÷12,0°C  

0.0 

 

DIGITAL INPUTS 

 

 

I1P 

Door switch polarity 

CL÷OP 

cL 

I2P 

Pressure switch  digital input polarity 

CL÷OP 

oP 

I3P 

Defrost end digital input polarity 

CL÷OP 

oP 

dId 

Digital input alarm delay 

0÷255 min. 

 

Label  Name 

  Range 

Default 

 

TIME AND WEEKLY HOLIDAYS

 

 

 

Hur 

Current hour 

0 ÷ 23 

- - - 

Min 

Current minute 

0 ÷ 59 

- - - 

dAY 

Current day 

Sun ÷ SAt 

- - - 

Hd1 

First weekly holiday 

Sun÷ SAt – nu 

nu 

Hd2 

Second weekly holiday 

Sun÷ SAt – nu 

nu 

Hd3 

Third weekly holiday 

Sun÷ SAt – nu 

nu 

 

DEFROST TIMES 

 

 

Ld1 

1

st

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

3,0 

Ld2 

2

nd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Ld3 

3

rd

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Ld4 

4

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Ld5 

5

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Ld6 

6

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Ld7 

7

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Ld8 

8

th

 workdays defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd1 

1

st

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd2 

2

nd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd3 

3

rd

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd4 

4

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd5 

5

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd6 

6

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

Sd7 

7

th

 holiday defrost start 

0 ÷ 23h 50  min. - nu 

nu 

Sd8 

8

th

 holiday defrost start 

0 ÷ 23h 50 min. - nu 

nu 

2L1 

1st workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

7,0 

2L2 

2nd workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

19,0 

2L3 

3rd workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2L4 

4th workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2L5 

5th workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2L6 

6th workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2L7 

7th workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2L8 

8th workdays defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2S1 

1st holiday defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2S2 

2nd holiday defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2S3 

3rd holiday defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 

2S4 

4th holiday defrost start program 2 

0 ÷ 23h 50 min. - nu 

nu 