XW562K 

4/6

 

have  a  Faston  connection  (6,3mm).  Heat-resistant  cables  have  to  be  used.  Before 
connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 
requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the 
outputs and the power connections. Do not exceed the maximum current allowed on 
each relay, in case of heavier loads use a suitable external relay. 

N.B.

 Maximum current allowed for all the loads is 20A. 

 

9.1 

PROBE CONNECTIONS 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to 
casual  liquid  infiltration.  It is recommended to place the thermostat probe away from 
air  streams  to  correctly  measure  the  average  room  temperature.  Place  the  defrost 
termination  probe  among  the  evaporator  fins  in  the  coldest  place, where most ice is 
formed,  far  from  heaters  or  from  the  warmest  place  during  defrost,  to  prevent 
premature defrost termination. 
 

10 

TTL SERIAL LINE 

The TTL connector allows, by means of the external module TTL/RS485, to connect 
the  unit  to  a  network  line 

ModBUS-RTU

 compatible as the 

dIXEL 

monitoring system 

XJ500  (Version  3.0).  The  same  TTL  connector  is  used  to  upload  and  download  the 
parameter list of the “

HOT KEY

“. These instruments can be ordered with direct serial 

output 

RS485

 (Optional). 

 

11 

USE OF THE PROGRAMMING “HOT KEY “ 

The  Wing  units  can  UPLOAD  or  DOWNLOAD  the  parameter  list  from  its  own  E2 
internal memory to the 

“Hot Key” 

and vice-versa. 

11.1 

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT) 

1. 

Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial 
cable if present, insert the 

“Hot Key” 

and then turn the Wing ON. 

2. 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Wing 

memory,  the  “

DoL

”  message  is  blinking.  After  10  seconds  the  instrument  will 

restart working with the new parameters. 

3. 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, 

then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

  “  for  right  programming.  The  instrument  starts  regularly  with  the  new 

programming. 

err

”  for  failed  programming.  In  this  case turn the unit off and then on if you want to 

restart the download again or remove the “

Hot key

” to abort the operation. 

11.2 

UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”) 

1. 

Turn  OFF  the  instrument  by  means  of  the  ON/OFF  key  and  remove  the  TTL 
serial cable if present; then turn it ON again. 

2. 

When  the  Wing  unit    is  ON,  insert  the  “

Hot  key

”  and push 

o

 

key; the  

"uPL" 

message appears. 

3. 

Push “

SET”

 key to start the UPLOAD; the “

uPL

” message is blinking. 

4. 

Turn OFF the instrument remove the 

“Hot Key”, 

plug in  the TTL serial cable, 

then turn it ON again. 

At the end of the data transfer phase the instrument displays the following messages: 

end

 “ for right programming. 

err

”  for  failed  programming.  In  this  case  push  “SET”  key  if  you  want  to  restart  the 

programming again or remove the not programmed “

Hot key

”. 

12 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm 

output 

ON; 

Compressor 

output 

according to parameters “COn” and “COF” 

“P2” 

Evaporator probe failure 

Alarm output ON; Defrost ended by time 

“P3” 

Second evaporator probe 
failure 

Alarm output ON; Defrost ended by time 

“tAL” 

Max. temperature alarm 

Alarm output ON; Other outputs unchanged 

“EA” 

Digital input 1 activated: 
external alarm 

Alarm relay depends on the ArE par. 
Output unchanged. 

“PAL” 

Pressure switch alarm 

Compressors off 
Alarm relay on 

“dEA” 

Safety thermostat for 
defrost alarm 

Defrost stopped. Alarm relay on. Start cooling 

„COO“ 

Cooling down 

„DEF“ 

Defrost is running 

-  

„POF“

*

 

Keyboard locked 

“rtc” 

Real time clock alarm 

Alarm  output  ON;  Other  outputs  unchanged; 
Defrosts according to par. “

IdF

” 

To  erase  the  alarm  enter  the  Clock  setting 
menu  by  pushing  the  DOWN  key  for  few 
second, see. par. 5.2 

 
The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternatively. 

12.1 

SILENCING BUZZER / ALARM RELAY OUTPUT 

If  “

tbA  =  yES

”,  once  the  alarm  signal  is  detected  the  buzzer  and  the  relay  are  is 

silenced by pressing any key.  
If  “

tbA 

no

”,  only  the  buzzer  is  silenced  while  the  alarm  relay  is  on  until  the  alarm 

condition recovers. 

12.2 

ALARM RECOVERY 

Probe  alarms  :  “

P1

”  (probe1  faulty),  “

P2

”  and  “

P3

”  automatically  stop  10s  after  the 

probe restarts normal operation. Check connections before replacing the probe. 
Temperature alarms “

tAL

” automatically stop as soon as the thermostat temperature 

returns to normal values. 
Temperature alarm “

tAL

” automatically stops as soon as the thermostat temperature 

returns to normal values and when defrost is started. 
Alarms “

EA”, “PAL” 

and 

“dEA”

 recover as soon as the digital input is disabled. 

 

13 

TECHNICAL DATA 

V650 keyboard 
Housing: 

self extinguishing ABS.

 

Case:

 

V650 

facia 64x164 mm; depth 23mm 

Mounting:

  

V650:

 panel mounting in a 56x72 mm panel cut-out with two screws. 

 3x2mm. 

Distance between the holes 40mm 

Protection: 

IP20; 

Frontal protection: 

IP65 

Power supply: 

from

 XW562K 

power module

 

Display

: 3 digits, red LED, 14,2 mm high;  

Optional output: 

buzzer 

 

CX650 keyboard 
Housing: 

self extinguishing ABS.

 

Case:

 CX

650 

facia 35x77 mm; depth 23mm 

Mounting:

 panel mounting in a 29x71 mm panel cut-out  

Protection: 

IP20; 

Frontal protection:

 IP65 

Power supply: 

from

 XW562K 

power module

 

Display

: 3 digits, red LED, 14,2 mm high;  

Optional output: 

buzzer

 

 
XW562K main board 
Housing: 

self extinguishing ABS.

 

Mounting:

 by screw  

Protection: 

IP20.

 

Frontal protection:

 IP65 with frontal gasket mod RG-L. (optional) 

Connections: 

Screw terminal block 

 2,5 mm

2

 heat-resistant wiring and tab terminal 

6,3x0,8mm  for  load  and  supply  and  tab  terminal    6,3x0,8mm  for  digital  inputs  and 
probes 

Power supply: 

230Vac or. 110Vac 

±

 10%  

Rated impulsive voltage

: 2500V 

Overvoltage Category

: II

 

Power absorption: 

7VA max.

 

Inputs

: 3 NTC probes 

Digital inputs

: 2 free voltage 

Relay outputs: 

Total current on loads MAX. 20A

 

compressor 1&2 :

 relay SPST 20(8) A, 250Vac  

 

evaporator fans:

 relay SPST 8(3) A, 250Vac

 

 

defrost:

 relay SPST 8A, 250Vac  

 

alarm: 

SPDT relay 8(3) A, 250Vac 

 

condenser fans:

 SPST relay 8(3) A, 250Vac 

Serial output :

 TTL standard  

Communication protocol:

 Modbus - RTU

 

Data storing

: on the non-volatile memory (EEPROM). 

Kind of action: 

1B. 

Pollution degree: 2

 

Software class: 

A.

 

Operating temperature: 

0÷50 °C. 

Storage temperature: 

-25÷60 °C.  

Relative humidity:

 20

÷

85% (no condensing) 

Measuring and regulation range: NTC probe: 

-40÷110°C (-58÷230°F) 

 
ADDITIONAL INFORMATION, FURNISHED BY MANUFACTURER 
Frontal protection:

 IP65 with frontal gasket mod RGW-V. (optional) 

Accuracy (ambient temp. 25°C)

:  ±0,5 °C ±1 digit 

Internal clock back-up:

 5 years 

Resolution: 

0,1 °C or 1°C or 1 °F (selectable). 

 