Installing and Operating Instructions
Installing and Operating Instructions
Installing and Operating Instructions
Installing and Operating Instructions
1598001822
1598001822 XW562K LND GB R3.0 10.11.2007.doc
XW562K
4/6
have a Faston connection (6,3mm). Heat-resistant cables have to be used. Before
connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the
outputs and the power connections. Do not exceed the maximum current allowed on
each relay, in case of heavier loads use a suitable external relay.
N.B.
Maximum current allowed for all the loads is 20A.
9.1
PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to
casual liquid infiltration. It is recommended to place the thermostat probe away from
air streams to correctly measure the average room temperature. Place the defrost
termination probe among the evaporator fins in the coldest place, where most ice is
formed, far from heaters or from the warmest place during defrost, to prevent
premature defrost termination.
10
TTL SERIAL LINE
The TTL connector allows, by means of the external module TTL/RS485, to connect
the unit to a network line
ModBUS-RTU
compatible as the
dIXEL
monitoring system
XJ500 (Version 3.0). The same TTL connector is used to upload and download the
parameter list of the “
HOT KEY
“. These instruments can be ordered with direct serial
output
RS485
(Optional).
11
USE OF THE PROGRAMMING “HOT KEY “
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2
internal memory to the
“Hot Key”
and vice-versa.
11.1
DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
1.
Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial
cable if present, insert the
“Hot Key”
and then turn the Wing ON.
2.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Wing
memory, the “
DoL
” message is blinking. After 10 seconds the instrument will
restart working with the new parameters.
3.
Turn OFF the instrument remove the
“Hot Key”,
plug in the TTL serial cable,
then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
“
end
“ for right programming. The instrument starts regularly with the new
programming.
“
err
” for failed programming. In this case turn the unit off and then on if you want to
restart the download again or remove the “
Hot key
” to abort the operation.
11.2
UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
1.
Turn OFF the instrument by means of the ON/OFF key and remove the TTL
serial cable if present; then turn it ON again.
2.
When the Wing unit is ON, insert the “
Hot key
” and push
o
key; the
"uPL"
message appears.
3.
Push “
SET”
key to start the UPLOAD; the “
uPL
” message is blinking.
4.
Turn OFF the instrument remove the
“Hot Key”,
plug in the TTL serial cable,
then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
“
end
“ for right programming.
“
err
” for failed programming. In this case push “SET” key if you want to restart the
programming again or remove the not programmed “
Hot key
”.
12
ALARM SIGNALS
Message Cause
Outputs
“P1”
Thermostat probe failure
Alarm
output
ON;
Compressor
output
according to parameters “COn” and “COF”
“P2”
Evaporator probe failure
Alarm output ON; Defrost ended by time
“P3”
Second evaporator probe
failure
Alarm output ON; Defrost ended by time
“tAL”
Max. temperature alarm
Alarm output ON; Other outputs unchanged
“EA”
Digital input 1 activated:
external alarm
Alarm relay depends on the ArE par.
Output unchanged.
“PAL”
Pressure switch alarm
Compressors off
Alarm relay on
“dEA”
Safety thermostat for
defrost alarm
Defrost stopped. Alarm relay on. Start cooling
„COO“
Cooling down
-
„DEF“
Defrost is running
-
„POF“
*
Keyboard locked
-
“rtc”
Real time clock alarm
Alarm output ON; Other outputs unchanged;
Defrosts according to par. “
IdF
”
To erase the alarm enter the Clock setting
menu by pushing the DOWN key for few
second, see. par. 5.2
The alarm message is displayed until the alarm condition is recovery.
All the alarm messages are showed alternatively.
12.1
SILENCING BUZZER / ALARM RELAY OUTPUT
If “
tbA = yES
”, once the alarm signal is detected the buzzer and the relay are is
silenced by pressing any key.
If “
tbA
=
no
”, only the buzzer is silenced while the alarm relay is on until the alarm
condition recovers.
12.2
ALARM RECOVERY
Probe alarms : “
P1
” (probe1 faulty), “
P2
” and “
P3
” automatically stop 10s after the
probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms “
tAL
” automatically stop as soon as the thermostat temperature
returns to normal values.
Temperature alarm “
tAL
” automatically stops as soon as the thermostat temperature
returns to normal values and when defrost is started.
Alarms “
EA”, “PAL”
and
“dEA”
recover as soon as the digital input is disabled.
13
TECHNICAL DATA
V650 keyboard
Housing:
self extinguishing ABS.
Case:
V650
facia 64x164 mm; depth 23mm
Mounting:
V650:
panel mounting in a 56x72 mm panel cut-out with two screws.
∅
3x2mm.
Distance between the holes 40mm
Protection:
IP20;
Frontal protection:
IP65
Power supply:
from
XW562K
power module
Display
: 3 digits, red LED, 14,2 mm high;
Optional output:
buzzer
CX650 keyboard
Housing:
self extinguishing ABS.
Case:
CX
650
facia 35x77 mm; depth 23mm
Mounting:
panel mounting in a 29x71 mm panel cut-out
Protection:
IP20;
Frontal protection:
IP65
Power supply:
from
XW562K
power module
Display
: 3 digits, red LED, 14,2 mm high;
Optional output:
buzzer
XW562K main board
Housing:
self extinguishing ABS.
Mounting:
by screw
Protection:
IP20.
Frontal protection:
IP65 with frontal gasket mod RG-L. (optional)
Connections:
Screw terminal block
≤
2,5 mm
2
heat-resistant wiring and tab terminal
6,3x0,8mm for load and supply and tab terminal 6,3x0,8mm for digital inputs and
probes
Power supply:
230Vac or. 110Vac
±
10%
Rated impulsive voltage
: 2500V
Overvoltage Category
: II
Power absorption:
7VA max.
Inputs
: 3 NTC probes
Digital inputs
: 2 free voltage
Relay outputs:
Total current on loads MAX. 20A
compressor 1&2 :
relay SPST 20(8) A, 250Vac
evaporator fans:
relay SPST 8(3) A, 250Vac
defrost:
relay SPST 8A, 250Vac
alarm:
SPDT relay 8(3) A, 250Vac
condenser fans:
SPST relay 8(3) A, 250Vac
Serial output :
TTL standard
Communication protocol:
Modbus - RTU
Data storing
: on the non-volatile memory (EEPROM).
Kind of action:
1B.
Pollution degree: 2
Software class:
A.
Operating temperature:
0÷50 °C.
Storage temperature:
-25÷60 °C.
Relative humidity:
20
÷
85% (no condensing)
Measuring and regulation range: NTC probe:
-40÷110°C (-58÷230°F)
ADDITIONAL INFORMATION, FURNISHED BY MANUFACTURER
Frontal protection:
IP65 with frontal gasket mod RGW-V. (optional)
Accuracy (ambient temp. 25°C)
: ±0,5 °C ±1 digit
Internal clock back-up:
5 years
Resolution:
0,1 °C or 1°C or 1 °F (selectable).