dixell XW562K Скачать руководство пользователя страница 2

dIXEL

 

Installing and Operating Instructions

Installing and Operating Instructions

Installing and Operating Instructions

Installing and Operating Instructions    

1598001822

 

 

1598001822 XW562K LND GB R3.0 10.11.2007.doc  

XW562K 

2/6

 

Function of the LEDs placed on the left top side of buttons 

(V650)

 

BUTTON 

MODE 

FUNCTION 

Prg1

 

ON

 

Prg1 is running 

Prg2

 

ON 

Prg2 is running 

 
 

4.2 

HOW TO SEE AND MODIFY THE SET POINT 

 

 

1. 

Push  for  2sec  the 

SET 

key:  the  display  will  show  the  Set  point 

value; 

2. 

To change the Set value push the 

or 

n

 arrows within 10s. 

3. 

To  memorise  the  new  set  point  value  push  the 

SET

  key  again  or 

wait 10s. 

4.3 

TO START A MANUAL DEFROST  

 

 
Push the 

DEF 

key for more than 2 seconds and a manual defrost will start. 

Manually defrost has higher priority than min. compressor running time (on- 
parameter). 

4.4 

TO ENTER IN PARAMETERS LIST  

To enter the parameter list (user accessible parameters) operate as follows: 
 

 

 
1.  Enter  the  Programming  mode  by  pressing  the  Set  and 

DOWN key for 5s (Pr2 appears) 

2.  Release the keys

 

 and 

 start blinking 

3.  Select the required parameter. 
4.  Press the “

SET

” key to display its value . 

5.  Use “

UP

” or “

DOWN

” to change its value. 

6.  Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 30s without pressing a key. 

NOTE

: the set value is stored even when the procedure is exited by waiting the time-

out to expire.

 

 
 
 

4.5 

HOW TO CHANGE THE PARAMETER VALUE 

1.  Enter the Programming mode. 
2.  Select the required parameter with 

o

 or 

n

3.  Press the “

SET

” key to display its value (

 and 

 LED starts blinking). 

4.  Use 

o

 or 

n

 to change its value. 

5.  Press “

SET

” to store the new value and move to the following parameter. 

To exit

: Press 

SET + UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting 

the time-out. 

4.6 

HOW TO LOCK THE KEYBOARD 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 

keys. 

2.  

The  “POF”  message  will  be  displayed  and  the  keyboard  is  locked.  At 
this  point  it  is  only  possible  the  viewing  of  the set point or the MAX o 
Min  temperature  stored  and  to  switch  ON  and  OFF  the  light,  the 
auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

 
Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

4.7 

TO SEE THE PROBE VALUES 

1. 

Enter in “

Pr2

” level. 

2. 

Select “

Prd

” parameter with 

o

 or 

n

3. 

Press the “

SET

” key to display “

Pb1” 

label alternate with Pb1 value. 

4. 

Use 

and 

n

 keys to display the other probe values.  

5. 

Press “

SET

” to move to the following parameter. 

 

REAL TIME CLOCK FUNCTIONS 

5.1 

TO SEE AND SET THE CURRENT TIME AND DAY 

 

 

 

1.  Push the 

DOWN 

key for more than 3 seconds  

2.  The following messages are displayed in sequence: 

 

Hur

 (hour) followed by the hour;  

 

Min

 (Minute) followed by the minutes 

 

dAY

 (day) followed by the day of the week 

3.  By pushing the SET key, the setting of current hour, minutes, day will 

be possible 

4.  To exit: push 

SET+ UP

 key or wait 15 seconds 

 

5.2 

TO SET THE DEFROST TIMES  

 

 

 
1.  Push the 

DOWN 

key for more than 3 seconds  

2.  The current time is displayed as written above  
3.  By pushing 

DEF

 key, the setting defrost time will be possible.   

4.  To exit, press 

SET + UP 

or wait 15s without pressing any key. 

 

5.3 

STAND BY FUNCTION 

1. 

Enter the programming. 

2. 

Select the 

onF 

parameter 

3. 

Change its value from “no” to “yES”. 

4. 

Exit the programming and the instrument will be palced in stanby mode. 

 

To revert to the normal working push for some seconds the SET key. 

PARAMETER LIST 

REGULATION 
Set1 

Set point 1 (LS÷US) 

Is the target set point 1

 

Set2 

Set point 2 (LS2÷US2) 

Is the target set point 2

 

Hy  Differential  for  the  set1: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set 

point1,  always  positive.  Compressor  Cut  IN  is  Set  Point  Plus  Differential  (Hy). 
Compressor Cut OUT is when the temperature reaches the set point. 

Hy2 Differential  for  the  set2: 

(0,1÷25,5°C;  1÷45°F):  Intervention  differential  for  set 

point2,  always  positive.  Compressor  Cut  IN  is  Set  Point  Plus  Differential  (Hy). 
Compressor Cut OUT is when the temperature reaches the set point. 

LS  Minimum  set  point  1  limit: 

(-50,0°C

÷

÷

÷

÷

SET1;  -58°F÷SET1)  Sets  the  minimum 

acceptable value for the set point1. 

US  Maximum  set  point  1  limit: 

(SET1

÷

÷

÷

÷

110°C;  SET1÷230°F)  Set  the  maximum 

acceptable value for set point1. 

LS2  Minimum  set  point  2  limit: 

(-50,0°C

÷

÷

÷

÷

SET2;  -58°F÷SET2)  Sets  the  minimum 

acceptable value for the set point2. 

US2  Maximum  set  point  2  limit: 

(SET2

÷

÷

÷

÷

110°C;  SET2÷230°F)  Set  the  maximum 

acceptable value for set point2. 

odS  Outputs  activation  delay  at  start  up:

  (0÷255  min)  This  function  is  enabled  at 

the  initial  start  up  of  the  instrument  and  inhibits  any  output  activation  for  the 
period of time set in the parameter. (AUX and Light can work) 

AC  Anti-short  cycle  delay: 

(0÷30  min)  interval  between  the  compressor  stop  and 

the following restart. 

AC1  2

nd

  compressor  delay  at  start  up,  program  1 

(0÷255sec)  Time  interval 

between the switching on of the first compressor and the second one. 

AC2  2

nd

  compressor  delay  at  start  up,  program  2 

(0÷255sec)  Time  interval 

between the switching on of the first compressor and the second one. 

on  minimum compressor running time 

(0÷30min) 

Mon  Maximum  compressor  running  time 

(0÷120min,  with  0  the  function  is 

disabled)  If  this  time  is  reached  the  compressor  is  switched  off  for  the  Ac  time, 
then if there are the conditions it restarts. 

cP2 Second compressor enabled with program 2 

(yES, no) 

Con  Compressor  ON  time  with  faulty  probe: 

(0÷255  min)  time  during  which  the 

compressor is active in case of faulty thermostat probe. With COn=0 compressor 
is always OFF. 

COF  Compressor  OFF  time  with  faulty  probe: 

(0÷255  min)  time  during  which  the 

compressor is off in case of faulty thermostat probe. With COF=0 compressor is 
always active. 

S2E  Second  program  enabled:  no=

the  second  set  point  is  disabled  and  not 

selectable; 

yES = 

the second set point can be selected. 

DISPLAY 
CF  Temperature  measurement  unit:

  °C  =  Celsius;  °F  =  Fahrenheit  .  When  the 

measurement  unit  is  changed  the  SET  point  and  the  values    of  the  regulation 
parameters have to be modified

 

rES Resolution (for °C)

: (in = 1°C; de = 0,1°C) allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

dot Display offset 

for program 1

(0÷25.5 °C) it is used for the special visualisation  

LINDE’s algorithm. 

do2 Display offset

 for program 2

(0÷25.5 °C) it is used for the special visualisation  

LINDE’s algorithm. 

dHy  Display  histeresys:

  (0÷25.5 °C) it is used for the special visualisation LINDE’s 

algorithm.  

When  the  temperature  measured  by  the  room  probe  is  less  then 

Setpoint  +  Hysteresis,  the  displayed  temperature  must  be  calculated  by  the 
microprocessor according to the following formula: 

 

if  

Tm

 > SEt + Hy  -> 

Td

 = SEt + dot +  dHy 

if 

Tm

 

 SEt + Hy  -> 

Td

 = (SEt + dot) +  {[( Tm – SEt ) x dHy ] / Hy } 

 
 

where 

Tm

 = temperature measured by room probe 

 

 

Td

 = temperature displayed by the controller 

DEFROST 
MdF  enabling the defrost key

:  

yES

= defrost key enabled;  

no

 = defrost key disabled. 

tdF  Defrost type: rE

 = electrical heater (Compressor OFF) 

in

 = hot gas (Compressor and defrost relays ON) 

EdF Defrost mode:

    

 

rtc 

Real  Time  Clock  mode

.  Defrost  time  follows 

Ld1÷Ld8

  parameters  on 

workdays  and 

Sd1÷Sd8

  on  holidays  for  program  1, 

2L1÷2L8

  parameters  on 

workdays and 

2S1÷2S8

 on holidays for program 1 

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired. 

dtE  Defrost  termination  temperature  fro  program  1:

  (-50,0÷110,0°C;  -58÷230°F) 

(Enabled  only  when  the  evaporator  probe  is  present)  sets  the  temperature 
measured by the evaporator probe which causes the end of defrost. 

dt2  Defrost  termination  temperature  fro  program  2:

  (-50,0÷110,0°C;  -58÷230°F) 

(Enabled  only  when  the  evaporator  probe  is  present)  sets  the  temperature 
measured by the evaporator probe which causes the end of defrost. 

IdF  Interval between defrosts for program 1: 

(1÷120h) It is used as safety time in 

case of RTC problem. Determines the time interval between the beginning of two 
defrost cycles, when the RTC is broken. 

Id2  Interval between defrosts for program 2: 

(1÷120h) It is used as safety time in 

case of RTC problem. Determines the time interval between the beginning of two 
defrost cycles, when the RTC is broken. 

Mtd  (Maximum) duration of defrost for program 1: 

(0÷255 min) When 

P2P = n

, no 

evaporator probe, it sets the defrost duration, when 

P2P = y

, defrost end based 

on temperature, it sets the maximum length for defrost. 

Отзывы: