![dixell XW562K Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/dixell/xw562k/xw562k_installation-and-operating-instructions-manual_2511102002.webp)
dIXEL
Installing and Operating Instructions
Installing and Operating Instructions
Installing and Operating Instructions
Installing and Operating Instructions
1598001822
1598001822 XW562K LND GB R3.0 10.11.2007.doc
XW562K
2/6
Function of the LEDs placed on the left top side of buttons
(V650)
:
BUTTON
MODE
FUNCTION
Prg1
ON
Prg1 is running
Prg2
ON
Prg2 is running
4.2
HOW TO SEE AND MODIFY THE SET POINT
1.
Push for 2sec the
SET
key: the display will show the Set point
value;
2.
To change the Set value push the
o
or
n
arrows within 10s.
3.
To memorise the new set point value push the
SET
key again or
wait 10s.
4.3
TO START A MANUAL DEFROST
Push the
DEF
key for more than 2 seconds and a manual defrost will start.
Manually defrost has higher priority than min. compressor running time (on-
parameter).
4.4
TO ENTER IN PARAMETERS LIST
To enter the parameter list (user accessible parameters) operate as follows:
1. Enter the Programming mode by pressing the Set and
DOWN key for 5s (Pr2 appears)
2. Release the keys
and
start blinking
3. Select the required parameter.
4. Press the “
SET
” key to display its value .
5. Use “
UP
” or “
DOWN
” to change its value.
6. Press “
SET
” to store the new value and move to the following parameter.
To exit
: Press
SET + UP
or wait 30s without pressing a key.
NOTE
: the set value is stored even when the procedure is exited by waiting the time-
out to expire.
4.5
HOW TO CHANGE THE PARAMETER VALUE
1. Enter the Programming mode.
2. Select the required parameter with
o
or
n
.
3. Press the “
SET
” key to display its value (
and
LED starts blinking).
4. Use
o
or
n
to change its value.
5. Press “
SET
” to store the new value and move to the following parameter.
To exit
: Press
SET + UP
or wait 15s without pressing a key.
NOTE
: the new programming is stored even when the procedure is exited by waiting
the time-out.
4.6
HOW TO LOCK THE KEYBOARD
1.
Keep the
o
and
n
keys pressed together for more than 3 s the
o
and
n
keys.
2.
The “POF” message will be displayed and the keyboard is locked. At
this point it is only possible the viewing of the set point or the MAX o
Min temperature stored and to switch ON and OFF the light, the
auxiliary output and the instrument.
TO UNLOCK THE KEYBOARD
Keep the
o
and
n
keys pressed together for more than 3s.
4.7
TO SEE THE PROBE VALUES
1.
Enter in “
Pr2
” level.
2.
Select “
Prd
” parameter with
o
or
n
.
3.
Press the “
SET
” key to display “
Pb1”
label alternate with Pb1 value.
4.
Use
o
and
n
keys to display the other probe values.
5.
Press “
SET
” to move to the following parameter.
5
REAL TIME CLOCK FUNCTIONS
5.1
TO SEE AND SET THE CURRENT TIME AND DAY
1. Push the
DOWN
key for more than 3 seconds
2. The following messages are displayed in sequence:
Hur
(hour) followed by the hour;
Min
(Minute) followed by the minutes
dAY
(day) followed by the day of the week
3. By pushing the SET key, the setting of current hour, minutes, day will
be possible
4. To exit: push
SET+ UP
key or wait 15 seconds
5.2
TO SET THE DEFROST TIMES
1. Push the
DOWN
key for more than 3 seconds
2. The current time is displayed as written above
3. By pushing
DEF
key, the setting defrost time will be possible.
4. To exit, press
SET + UP
or wait 15s without pressing any key.
5.3
STAND BY FUNCTION
1.
Enter the programming.
2.
Select the
onF
parameter
3.
Change its value from “no” to “yES”.
4.
Exit the programming and the instrument will be palced in stanby mode.
To revert to the normal working push for some seconds the SET key.
6
PARAMETER LIST
REGULATION
Set1
Set point 1 (LS÷US)
Is the target set point 1
Set2
Set point 2 (LS2÷US2)
Is the target set point 2
Hy Differential for the set1:
(0,1÷25,5°C; 1÷45°F): Intervention differential for set
point1, always positive. Compressor Cut IN is Set Point Plus Differential (Hy).
Compressor Cut OUT is when the temperature reaches the set point.
Hy2 Differential for the set2:
(0,1÷25,5°C; 1÷45°F): Intervention differential for set
point2, always positive. Compressor Cut IN is Set Point Plus Differential (Hy).
Compressor Cut OUT is when the temperature reaches the set point.
LS Minimum set point 1 limit:
(-50,0°C
÷
÷
÷
÷
SET1; -58°F÷SET1) Sets the minimum
acceptable value for the set point1.
US Maximum set point 1 limit:
(SET1
÷
÷
÷
÷
110°C; SET1÷230°F) Set the maximum
acceptable value for set point1.
LS2 Minimum set point 2 limit:
(-50,0°C
÷
÷
÷
÷
SET2; -58°F÷SET2) Sets the minimum
acceptable value for the set point2.
US2 Maximum set point 2 limit:
(SET2
÷
÷
÷
÷
110°C; SET2÷230°F) Set the maximum
acceptable value for set point2.
odS Outputs activation delay at start up:
(0÷255 min) This function is enabled at
the initial start up of the instrument and inhibits any output activation for the
period of time set in the parameter. (AUX and Light can work)
AC Anti-short cycle delay:
(0÷30 min) interval between the compressor stop and
the following restart.
AC1 2
nd
compressor delay at start up, program 1
(0÷255sec) Time interval
between the switching on of the first compressor and the second one.
AC2 2
nd
compressor delay at start up, program 2
(0÷255sec) Time interval
between the switching on of the first compressor and the second one.
on minimum compressor running time
(0÷30min)
Mon Maximum compressor running time
(0÷120min, with 0 the function is
disabled) If this time is reached the compressor is switched off for the Ac time,
then if there are the conditions it restarts.
cP2 Second compressor enabled with program 2
(yES, no)
Con Compressor ON time with faulty probe:
(0÷255 min) time during which the
compressor is active in case of faulty thermostat probe. With COn=0 compressor
is always OFF.
COF Compressor OFF time with faulty probe:
(0÷255 min) time during which the
compressor is off in case of faulty thermostat probe. With COF=0 compressor is
always active.
S2E Second program enabled: no=
the second set point is disabled and not
selectable;
yES =
the second set point can be selected.
DISPLAY
CF Temperature measurement unit:
°C = Celsius; °F = Fahrenheit . When the
measurement unit is changed the SET point and the values of the regulation
parameters have to be modified
rES Resolution (for °C)
: (in = 1°C; de = 0,1°C) allows decimal point display.
dE
= 0,1°C;
in
= 1 °C
dot Display offset
for program 1
:
(0÷25.5 °C) it is used for the special visualisation
LINDE’s algorithm.
do2 Display offset
for program 2
:
(0÷25.5 °C) it is used for the special visualisation
LINDE’s algorithm.
dHy Display histeresys:
(0÷25.5 °C) it is used for the special visualisation LINDE’s
algorithm.
When the temperature measured by the room probe is less then
Setpoint + Hysteresis, the displayed temperature must be calculated by the
microprocessor according to the following formula:
if
Tm
> SEt + Hy ->
Td
= SEt + dot + dHy
if
Tm
≤
SEt + Hy ->
Td
= (SEt + dot) + {[( Tm – SEt ) x dHy ] / Hy }
where
Tm
= temperature measured by room probe
Td
= temperature displayed by the controller
DEFROST
MdF enabling the defrost key
:
yES
= defrost key enabled;
no
= defrost key disabled.
tdF Defrost type: rE
= electrical heater (Compressor OFF)
in
= hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
rtc
=
Real Time Clock mode
. Defrost time follows
Ld1÷Ld8
parameters on
workdays and
Sd1÷Sd8
on holidays for program 1,
2L1÷2L8
parameters on
workdays and
2S1÷2S8
on holidays for program 1
in
=
interval mode
. The defrost starts when the time “
Idf
” is expired.
dtE Defrost termination temperature fro program 1:
(-50,0÷110,0°C; -58÷230°F)
(Enabled only when the evaporator probe is present) sets the temperature
measured by the evaporator probe which causes the end of defrost.
dt2 Defrost termination temperature fro program 2:
(-50,0÷110,0°C; -58÷230°F)
(Enabled only when the evaporator probe is present) sets the temperature
measured by the evaporator probe which causes the end of defrost.
IdF Interval between defrosts for program 1:
(1÷120h) It is used as safety time in
case of RTC problem. Determines the time interval between the beginning of two
defrost cycles, when the RTC is broken.
Id2 Interval between defrosts for program 2:
(1÷120h) It is used as safety time in
case of RTC problem. Determines the time interval between the beginning of two
defrost cycles, when the RTC is broken.
Mtd (Maximum) duration of defrost for program 1:
(0÷255 min) When
P2P = n
, no
evaporator probe, it sets the defrost duration, when
P2P = y
, defrost end based
on temperature, it sets the maximum length for defrost.