1592026000 XW20K GB R2.0 08.06.2011.doc
XW60K
5/5
17
Default setting values
Label
Name
Range
Default Level
REGULATION
Set Set point
LS; US
-5.0
- - -
Hy Differential
[0.1 to 25.5°C]
[1 to 45°F]
2.0
Pr1
LS Minimum set point
[-55.0°C to SET]
[-67°F to SET]
-50.0
Pr2
US Maximum set point
[SET to 150°C]
[SET to 302°F]
110
Pr2
Ot
Thermostat probe calibration
[-12 to 12°C]
[-21 to 21°F]
0.0
Pr1
P3P
Third probe presence (1st cond.
probe)
n=not present; Y=pres.
n
Pr2
O3 Third probe calibration
[-12 to 12°C]
[-21 to 21°F]
0
Pr2
P4P
Fourth probe presence (2nd cond.
probe)
n=not present; Y=pres.
n
Pr2
O4 Fourth probe calibration
[-12 to 12°C]
[-21 to 21°F]
0
Pr2
odS Outputs activation delay at start up
0 to 255 min
0
Pr2
AC Anti-short cycle delay
0 to 30 min
1
Pr1
Ac1 Second compressor delay
0 to 255 sec
5
Pr2
CCt
Compressor ON time during fast
freezing
0.0 to 23h50min, res. 10 min
0.0
Pr2
CCS Set point for continuous cycle
[-55.0 to 150.0°C]
[-67 to 302°F]
-5
Pr2
Con Compressor ON time with faulty probe
0 to 255 min
15
Pr2
CoF
Compressor OFF time with faulty
probe
0 to 255 min
30
Pr2
CH Kind of regulation
CL; Ht
CL
Pr1
DISPLAY
CF Temperature measurement unit
°C; °F
°C
Pr2
rES Resolution (integer/decimal point)
in; dE
dE
Pr1
rEd Remote display
P1; 1r2
P1
Pr2
dLy Display temperature delay
0.0 to 20min00sec, res. 10 sec
0
Pr2
DEFROST
dFP Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2
dtE Defrost termination temperature
[-50.0 to 150°C]
[-58 to 302°F]
8.0
Pr1
idF Interval between defrost cycles
1 to 120 h
6
Pr1
MdF (Maximum) length for 1° defrost
0 to 255 min
30
Pr1
dFd Displaying during defrost
rt; it; SEt; dEF; dEG
it
Pr2
dAd MAX display delay after defrost
0 to 255 min
30
Pr2
AUXILIARY THERMOSTAT
ACH Kind of action for auxiliary relay
CL; Ht
CL
Pr2
SAA Set Point for auxiliary relay
[-55.0 to 150°C]
[-67 to 302°F]
0.0
Pr2
SHy Differential for auxiliary relay
[0.1 to 25.5°C]
[1 to 45°F]
2.0
Pr2
ArP Probe selection for auxiliary relay
nP; P1; P2; P3
nP
Pr2
Sdd Aux.output working during defrost
n; Y
n
Pr2
ALARMS
ALP Probe setting for temperature alarm
P1; P2; P3; P4
P1
Pr2
ALC Temperature alarms configuration
rE; Ab
rE
Pr2
ALU MAXIMUM temperature alarm
[-55.0 to 150.0°C]
[-67 to 302°F]
10.0
Pr1
ALL minimum temperature alarm
[-55.0 to 150.0°C]
[-67 to 302°F]
10.0
Pr1
AFH Temperature alarm and fan differential
[0.1 to 25.5°C]
[1 to 45°F]
2.0
Pr2
ALd Temperature alarm delay
0 to 255 min
15
Pr2
dAo Delay of temperature alarm at start up
0.0 to 23h50min, res. 10 min
1.3
Pr2
AP2
Probe for temperat. alarm of
condenser
nP; P1; P2; P3; P4
P4
Pr2
AL2 Condenser for low temperat. alarm
[-55.0 to 150.0°C]
[-67 to 302°F]
-40
Pr2
AU2 Condenser for high temperat. alarm
[-55.0 to 150.0°C]
[-67 to 302°F]
110
Pr2
AH2
Differential for condenser temperature
alarm recovery
[0.1 to 25.5°C]
[1 to 45°F]
5
Pr2
Ad2 Condenser temperature alarm delay
0 to 254 min , 255=nU
15
Pr2
dA2
Delay of cond. temper. alarm at start
up
0.0 to 23h50min, res. 10 min
1.3
Pr2
bLL
Compressor off because of condenser
low temperature alarm
n(0); Y(1)
n
Pr2
AC2
Compr. off for condenser high
temperature alarm
n(0); Y(1)
n
Pr2
AUXILIARY OUTPUT
tbA Alarm relay disabling
n=no; Y=yes
Y
Pr2
oA3 Fourth relay configuration
ALr = alarm; dEF = do not select it;
Lig =Light; AUS =AUX; onF=always
on; Fan= do not select it; db = do
not select it; dF2 = do not select it
Lig
Pr2
AoP Alarm relay polarity (oA3=ALr)
oP; CL
CL
Pr2
DIGITAL INPUT
i1P Digital input polarity
oP=opening;CL=closing
CL
Pr1
i1F Digital input configuration
EAL; bAL; PAL; dor; dEF; Htr; AUS
dor
Pr1
did Digital input alarm delay
0 to 255 min
15
Pr1
Label
Name
Range
Default Level
nPS
Number of activation of pressure
switch
0 to 15
15
Pr2
odC
Compress and fan status when open
door
no; FAn; CPr; F_C
F-C
Pr2
rrd
Regulation restart with door open
alarm
n; Y
Y
Pr2
HES Differential for Energy Saving
[-30 to 30°C]
[-54 to 54°F]
0
Pr2
OTHER
Adr Serrial address
1 to 247
1
Pr1
PbC Kind of probe
PtC; ntC
ntC
Pr2
onF on/off key enabling
nu, oFF; ES
oFF
Pr2
dP3 Third probe display
--
-
Pr1
dP4 Fourth probe display
--
-
Pr1
rSE Current set point
-
Pr1
rEL Software release
- - -
-
Pr2
Ptb Map code
- - -
-
Pr2