dixell XW20K Скачать руководство пользователя страница 5

 

1592026000 XW20K GB R2.0 08.06.2011.doc 

                       

XW60K 

5/5 

 

17

 

Default setting values 

 

Label 

Name 

Range 

Default  Level 

REGULATION 

Set  Set point 

LS; US 

-5.0 

- - - 

Hy  Differential 

[0.1 to 25.5°C] 

[1 to 45°F] 

2.0 

Pr1 

LS  Minimum set point 

[-55.0°C to SET] 

[-67°F to SET] 

-50.0 

Pr2 

US  Maximum set point 

[SET to 150°C] 
[SET to 302°F] 

110 

Pr2 

Ot 

Thermostat probe calibration 

[-12 to 12°C] 

[-21 to 21°F] 

0.0 

Pr1 

P3P 

Third probe presence (1st cond. 
probe) 

n=not present; Y=pres. 

Pr2 

O3  Third probe calibration 

[-12 to 12°C] 

[-21 to 21°F] 

Pr2 

P4P 

Fourth probe presence (2nd  cond. 
probe) 

n=not present; Y=pres. 

Pr2 

O4  Fourth probe calibration 

[-12 to 12°C] 

[-21 to 21°F] 

Pr2 

odS  Outputs activation delay at start up 

0 to 255 min 

Pr2 

AC  Anti-short cycle delay 

0 to 30 min 

Pr1 

Ac1  Second compressor delay 

0 to 255 sec 

Pr2 

CCt 

Compressor ON time during fast 
freezing 

0.0 to 23h50min, res. 10 min 

0.0 

Pr2 

CCS  Set point for continuous cycle 

[-55.0 to 150.0°C] 

[-67 to 302°F] 

-5 

Pr2 

Con  Compressor ON time with faulty probe 

0 to 255 min 

15 

Pr2 

CoF 

Compressor OFF time with faulty 
probe 

0 to 255 min 

30 

Pr2 

CH  Kind of regulation 

CL; Ht 

CL 

Pr1 

DISPLAY 

CF  Temperature measurement unit 

°C; °F 

°C 

Pr2 

rES  Resolution (integer/decimal point) 

in; dE 

dE 

Pr1 

rEd  Remote display 

P1; 1r2 

P1 

Pr2 

dLy  Display temperature delay 

0.0 to 20min00sec, res. 10 sec 

Pr2 

DEFROST 

dFP  Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

Pr2 

dtE  Defrost termination temperature 

[-50.0 to 150°C]  

[-58 to 302°F] 

8.0 

Pr1 

idF  Interval between defrost cycles 

1 to 120 h 

Pr1 

MdF  (Maximum) length for 1° defrost 

0 to 255 min 

30 

Pr1 

dFd  Displaying during defrost 

rt; it; SEt; dEF; dEG 

it 

Pr2 

dAd  MAX display delay after defrost 

0 to 255 min 

30 

Pr2 

AUXILIARY THERMOSTAT 

ACH  Kind of action for auxiliary relay 

CL; Ht 

CL 

Pr2 

SAA  Set Point for auxiliary relay 

[-55.0 to 150°C]  

[-67 to 302°F] 

0.0 

Pr2 

SHy  Differential for auxiliary relay 

[0.1 to 25.5°C] 

[1 to 45°F] 

2.0 

Pr2 

ArP  Probe selection for auxiliary relay 

nP; P1; P2; P3 

nP 

Pr2 

Sdd  Aux.output working during defrost 

n; Y 

Pr2 

ALARMS 

ALP  Probe setting for temperature alarm 

P1; P2; P3; P4 

P1 

Pr2 

ALC  Temperature alarms configuration 

rE; Ab 

rE 

Pr2 

ALU  MAXIMUM temperature alarm 

[-55.0 to 150.0°C] 

[-67 to 302°F] 

10.0 

Pr1 

ALL  minimum temperature alarm 

[-55.0 to 150.0°C] 

[-67 to 302°F] 

10.0 

Pr1 

AFH  Temperature alarm and fan differential 

[0.1 to 25.5°C] 

[1 to 45°F] 

2.0 

Pr2 

ALd  Temperature alarm delay 

0 to 255 min 

15 

Pr2 

dAo  Delay of temperature alarm at start up 

0.0 to 23h50min, res. 10 min 

1.3 

Pr2 

AP2 

Probe for temperat. alarm of 
condenser 

nP; P1; P2; P3; P4 

P4 

Pr2 

AL2  Condenser for low temperat. alarm 

[-55.0 to 150.0°C] 

[-67 to 302°F] 

-40 

Pr2 

AU2  Condenser for high temperat. alarm 

[-55.0 to 150.0°C] 

[-67 to 302°F] 

110 

Pr2 

AH2 

Differential for condenser temperature 
alarm recovery 

[0.1 to 25.5°C] 

[1 to 45°F] 

Pr2 

Ad2  Condenser temperature alarm delay 

0 to 254 min , 255=nU 

15 

Pr2 

dA2 

Delay of cond. temper. alarm at start 
up 

0.0 to 23h50min, res. 10 min 

1.3 

Pr2 

bLL 

Compressor off because of condenser 
low temperature alarm 

n(0); Y(1) 

Pr2 

AC2 

Compr. off for condenser high 
temperature alarm 

n(0); Y(1) 

Pr2 

AUXILIARY OUTPUT 

tbA  Alarm relay disabling 

n=no; Y=yes 

Pr2 

oA3  Fourth relay configuration 

ALr = alarm; dEF = do not select it; 

Lig =Light; AUS =AUX; onF=always 

on; Fan= do not select it; db = do 

not select it; dF2 = do not select it 

Lig 

Pr2 

AoP  Alarm relay  polarity  (oA3=ALr) 

oP; CL 

CL 

Pr2 

DIGITAL INPUT 

i1P  Digital input polarity 

oP=opening;CL=closing 

CL 

Pr1 

i1F  Digital input configuration 

EAL; bAL; PAL; dor; dEF; Htr; AUS 

dor 

Pr1 

did  Digital input alarm delay 

0 to 255 min 

15 

Pr1 

Label 

Name 

Range 

Default  Level 

nPS 

Number of activation of pressure 
switch 

0 to 15 

15 

Pr2 

odC 

Compress and fan status when open 
door 

no; FAn; CPr; F_C 

F-C 

Pr2 

rrd 

Regulation restart with door open 
alarm 

n; Y 

Pr2 

HES  Differential for Energy Saving 

[-30 to 30°C]  

[-54 to 54°F] 

Pr2 

OTHER 

Adr  Serrial address 

1 to 247 

Pr1 

PbC  Kind of probe 

PtC; ntC 

ntC 

Pr2 

onF  on/off key enabling 

nu, oFF; ES 

oFF 

Pr2 

dP3  Third probe display 

-- 

Pr1 

dP4  Fourth probe display 

-- 

Pr1 

rSE  Current set point 

 

Pr1 

rEL  Software release 

- - - 

Pr2 

Ptb  Map code 

- - - 

Pr2 

 
 

Содержание XW20K

Страница 1: ...mpressor with a possible delay set in the AC1 parameter Both the compressors are switched off at the same time 3 2 FAST FREEZING When defrost is not in progress it can be activated by holding the UP key pressed for about 3 sec The compressor operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same ac...

Страница 2: ... To exit Press SET UP or wait for 15 sec without pressing any key NOTE1 if no parameter is present in the Pr1 level after the first 3 sec the noP message will be displayed Keep SET DOWN keys pushed till the Pr2 message will be displayed NOTE2 the new set value will be stored even if the procedure is exited by waiting for the time out to expire 7 7 2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO ...

Страница 3: ...m is present in any case regulation restarts after AC time at minimum AC2 Compressor off with high temperature alarm of condenser n compressor keeps on working Y compressor is switched off till the alarm is present in any case regulation restarts after AC time at minimum RELAY OA3 22 23 CONFIGURATION tbA Alarm relay silencing with oA3 ALr n silencing disabled alarm relay stays on till alarm condit...

Страница 4: ...10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation 14 ALARM SIGNALS Message Cause Outputs P1 Thermostat probe failure Alarm output ON Compressor output according to paramet...

Страница 5: ...y nP P1 P2 P3 nP Pr2 Sdd Aux output working during defrost n Y n Pr2 ALARMS ALP Probe setting for temperature alarm P1 P2 P3 P4 P1 Pr2 ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 ALL minimum temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 AFH Temperature alarm and fan differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr2 ALd Te...