CCt  Thermostat override: (0.0 to 23h50min, res. 10 min) allows to set the length of the continuous 

cycle. It can be used, for instance, when the room is filled with new products. 

CCS Set point for continuous cycle: (-55 to 150°C, -67 to 302°F) it sets the set point used during 

the continuous cycle. 

Con  Compressor  ON  time  with  faulty  probe:  (0 to  255  min)  time  during  which  the  compressor  is 

active in case of faulty thermostat probe. With Con=0 compressor is always OFF. 

COF Compressor OFF time with faulty probe: (0 to 255 min) time during which the compressor is 

off in case of faulty thermostat probe. With CoF=0 compressor is always active. 

CH  Type of action: CL = cooling; Ht = heating. 

DISPLAY 

CF  Temperature measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is 

changed the SET point and the values of the regulation parameters have to be modified 

rES  Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. 

dE = 0.1°C; in = 1 °C. 

rEd  Remote  display:  select  which  probe  is  displayed  by  the  remote  display  (T620or  CX620  or 

V620) (P1; P2, P3, P4,  SET, dtr): it selects which probe  is displayed by the instrument:  P1 = 
Thermostat  probe;  P2  =  Evaporator  probe;  P3  =  Third  probe(only  for  model  with  this  option 
enabled); P4 = Fourth probe, SET = set point; dtr = percentage of visualization. 

dLy  Display delay: (0.0 to 20min00sec; res. 10 sec) when the temperature increases, the display is 

updated of 1°C or 1°F after this time. 

DEFROST 

dFP  Probe  selection  for  defrost  termination:  nP  =  no  probe;  P1  =thermostat  probe;  P2  = 

evaporator probe; P3 =Third probe; P4 = Fourth probe. 

dtE   Defrost  termination  temperature:  (-55.0  to  150.0°C;  -67  to  302°F)  (Enabled  only  when  the 

evaporator  probe  is  present)  sets  the  temperature  measured  by  the  evaporator  probe  which 
causes the end of defrost. 

idF  Interval between defrosts: (1 to 120 h) determines the time interval between two defrost cycles. 
MdF  (Maximum) duration of defrost: (0 to 255 min) When P2P = n, no evaporator probe, it sets the 

defrost duration, when P2P = y, defrost end based on temperature, it sets the maximum length 
for defrost. 

dFd  Display during defrost:  
 

rt = real temperature;  
it = temperature reading at the defrost start; 
Set = set point; 
dEF = “dEF” label. 

dAd  Defrost display time out: (0 to 255 min) sets the maximum time between the end of defrost and 

the restarting of the real room temperature display. 

OA3 = AUS: AUXILIARY THERMOSTAT CONFIGURATION (terms. 22-23)  

ACH  Kind of regulation for auxiliary relayHt = heating; CL = cooling 
SAA  Set Point for auxiliary relay: (-55.0 to 150.0°C; -67 to 302°F) it defines the room temperature 

setpoint to switch auxiliary relay. 

SHy  Differential for auxiliary relay: (0.1 to 25.5°C; 1 to 45°F) differential for auxiliary relay set point, 

always positive.  

ArP  Probe selection for auxiliarynP = aux relay is switched by digital input with i1F=AUSP1 = 

Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe);  
P4 = Probe 4. 

Sdd  Auxiliary output status during defrost:  

n = the auxiliary output is switched off during defrost; 
y = the auxiliary output goes on working during defrost.  

ALARMS 

ALP  Probe  for  temperature  alarm  setting:  P1  =  thermostat  probe;  P2  =  evaporator  probe;  P3  = 

condenser 1 probe; P4 = condenser 2 probe. 

ALC  Temperature alarm configuration: 

rE = High and Low alarms related to Set Point  
Ab = High and low alarms related to the absolute temperature. 

ALU  High temperature alarm setting:  
 

ALC = rE, 0 to 50°C or 0 to 90°F. 

 

ALC = Ab, ALL to 150°C or ALL to 302°F. 

 

When this temperature is reached and after the ALd delay time the HA alarm is enabled. 

ALL  Low temperature alarm setting:  

ALC = rE, 0 to 50°C or 0 to 90°F;    
ALC = Ab, -55°C to ALU or -67°F to ALU.  
When this temperature is reached and after the ALd delay time, the LA alarm is enabled. 

AFH  Temperature alarm and fan differential: (0.1 to 25.5°C; 1 to 45°F) differential for temperature 

alarm set point and fan regulation set point, always positive. 

ALd  Temperature  alarm  delay:  (0  to  255  min)  time  interval  between  the  detection  of  an  alarm 

condition and the corresponding alarm signalling. 

dAo Delay of temperature alarm at start-up: (0.0 to 23h50min, res. 10 min) time interval between 

the detection of the temperature alarm condition after the instrument power on and the alarm 
signalling. 

CONDENSER TEMPERATURE ALARM 

AP2  Probe selection for temperature alarm of condenser: nP = no probe; P1 = thermostat probe; 

P2 = evaporator probe; P3 = third probe; P4 = fourth probe. 

AL2 Low temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this temperature is 

reached the LA2 alarm is signalled (after the Ad2 delay). 

Au2 High temperature alarm of condenser: (-55 to 150°C; -67 to 302°F) when this temperature is 

reached the HA2 alarm is signalled (after the Ad2 delay). 

AH2 Differential for temperature condenser alarm recovery: (0.1 to 25.5°C; 1 to 45°F). 
Ad2 Condenser temperature alarm delay: (0 to 255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2  Condenser temperature alarm exclusion at start up: (0.0 to 23h50min, res. 10 min). 
bLL  Compressor  off  with  low  temperature  alarm  of  condenser:  n  =  compressor  keeps  on 

working; Y = compressor is switched off till the alarm is present, in any case regulation restarts 
after AC time at minimum. 

AC2  Compressor  off  with  high  temperature  alarm  of  condenser:  n  =  compressor  keeps  on 

working; Y = compressor is switched off till the alarm is present, in any case regulation restarts 
after AC time at minimum. 

RELAY OA3 (22-23) CONFIGURATION 

tbA  Alarm relay silencing (with oA3=ALr):  

= silencing disabled: alarm relay stays on till alarm condition lasts; 
= silencing enabled: alarm relay is switched OFF by pressing a key during an alarm. 

oA3 Fourth relay configuration (22-23): dEF = do not select it; FAn = do not select it; ALr = alarm; 

Lig = light; AuS = Auxiliary relay; onF = always on with instrument on; db = heating element for 
neutral zone regulation; cP2 = second compressor; dF2 = do not select it. 

AoP  Alarm relay polarity:  it set if the alarm relay  is open or closed when  an  alarm happens. CL

terminals 1-2 closed during an alarm; oP = terminals 1-2 open during an alarm. 

DIGITAL INPUT  

i1P  Digital input polarity: oP = the digital input is activated by opening the contact; CL = the digital 

input is activated by closing the contact. 

i1F   Digital input configuration: EAL = external alarm: “EA” message is displayed; bAL = serious 

alarm “CA” message is displayed. PAL = pressure switch alarm, “CA” message is displayed; dor 
= door switch function; dEF = activation of a defrost cycle; AUS =to switch on and off the 22-23 
relay with oA3 = AUS; Htr = kind of action inversion (cooling – heating); FAn = not set it;  
ES 
= Energy saving. 

did   Digital input delay: (0 to 255 min)  

With  i1F=  EAL  or  i1F  =  bAL  digital  input  alarm  delay:  delay  between  the  detection  of  the 
external alarm condition and its signalling.  
With i1F= dor: door open signalling delay. 
With i1F = PAL: time for pressure switch function: 
time interval to calculate the number of the 
pressure switch activation. 

nPS Pressure switch number: (0 to 15) number of activation of the pressure switch, during the did 

interval, before signalling the alarm event (i2F=PAL).  
If the nPS activation in the did time is reached, switch off and on the instrument to restart 
normal regulation. 

odC  Compressor  and  fan  status  when  open  door:  no  =  normal;  FAn  =  Fan  OFF;  CPr  

Compressor OFF; F_C = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no = outputs not affected by the doA alarm;  YES = outputs 

restart with the doA alarm. 

HES  Temperature increase during the Energy Saving cycle: (-30.0 to 30.0°C; -54 to 54°F) it sets 

the increasing value of the set point during the Energy Saving cycle. 

OTHER 

Adr   RS485  serial  address:  (1  to  247)  identifies  the  instrument  address  when  connected  to  a 

ModBUS compatible monitoring system. 

PbC Type of probe: it allows to set the kind of probe used by the instrument. PtC = PTC probe, ntC = 

NTC probe. 

onF  on/off key enabling: nu = disabled; oFF = enabled; ES = to start a energy saving cycle. 
dP3  Third probe displayoptional
dP4  Fourth probe display
rSE  Real  set  point:  it  shows  the  set  point  used  during  the  energy  saving  cycle  or  during  the 

continuous cycle. 

rEL   Release software: (read only) Software version of the microprocessor. 
Ptb   Parameter table: (read only) it shows the original code of the parameter map. 

 

9

 

DIGITAL INPUT 

The free voltage digital input is programmable in different configurations by the “i1F” parameter. 

9.1

 

DOOR SWITCH INPUT  (I1F = DOR) 

It signals the door status and the corresponding relay output status through the odC parameter: no = 
normal (any change); Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF. 
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, 
the display shows the message  “dA”  and the regulation restarts is rtr = yES. The alarm stops as 
soon as the external digital input is disabled again. With the door open, the high and low temperature 
alarms are disabled. 

9.2

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for did time delay before signalling the “EAL” 
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated. 

9.3

 

SERIOUS ALARM MODE (I1F = BAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  did  delay  before  signalling  the  “CA”  alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

9.4

 

PRESSURE SWITCH (I1F = PAL) 

If  during  the  interval  time  set  by  did  parameter,  the  pressure  switch  has  reached  the  number  of 
activation of the nPS parameter, the “CA” pressure alarm message will be displayed. The compressor 
and  the  regulation  are  stopped.  When  the  digital  input  is  ON  the  compressor  is  always  OFF.  If  the 
nPS  activation in  the  did  time  is  reached,  switch  off  and on  the  instrument  to  restart  normal 
regulation. 

9.5

 

AUXILIARY OUTPUT SWITCHING  (I1F =AUS) 

With oA3=AUS and i1F=AUX it switches the fourth relay (22-23). 

9.6

 

START DEFROST (I1F = DFR) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 
restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is 
expired. 

9.7

 

KIND OF ACTION: HEATING OR COOLING (I1F = HTR) 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

9.8

 

ENERGY SAVING (I1F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+HES 
(parameter) sum. This function is enabled until the digital input is activated. 

Содержание XW20K

Страница 1: ...mpressor with a possible delay set in the AC1 parameter Both the compressors are switched off at the same time 3 2 FAST FREEZING When defrost is not in progress it can be activated by holding the UP key pressed for about 3 sec The compressor operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same ac...

Страница 2: ... To exit Press SET UP or wait for 15 sec without pressing any key NOTE1 if no parameter is present in the Pr1 level after the first 3 sec the noP message will be displayed Keep SET DOWN keys pushed till the Pr2 message will be displayed NOTE2 the new set value will be stored even if the procedure is exited by waiting for the time out to expire 7 7 2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO ...

Страница 3: ...m is present in any case regulation restarts after AC time at minimum AC2 Compressor off with high temperature alarm of condenser n compressor keeps on working Y compressor is switched off till the alarm is present in any case regulation restarts after AC time at minimum RELAY OA3 22 23 CONFIGURATION tbA Alarm relay silencing with oA3 ALr n silencing disabled alarm relay stays on till alarm condit...

Страница 4: ...10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation 14 ALARM SIGNALS Message Cause Outputs P1 Thermostat probe failure Alarm output ON Compressor output according to paramet...

Страница 5: ...y nP P1 P2 P3 nP Pr2 Sdd Aux output working during defrost n Y n Pr2 ALARMS ALP Probe setting for temperature alarm P1 P2 P3 P4 P1 Pr2 ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 ALL minimum temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 AFH Temperature alarm and fan differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr2 ALd Te...

Отзывы: