DIGITAL INPUTS POLARITY  

The digital input polarity depends on the i1P parameter: 
i1P=CL: the input is activated by closing the contact. 
i1P=OP
: the input is activated by opening the contact 

10

 

INSTALLATION AND MOUNTING 

T620 keyboard shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws 

 3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L).  

V620 keyboard shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using two screws 

 

3 x 2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V). 
CX620 keyboard shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special 
bracket supplied.  
The controller XW20K shall be mounted in a din rail 
It must be connected to the keyboard by means of a two-wire cable (

 1mm). The temperature range 

allowed for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to  probes.  Let  the  air  circulate  by  the 
cooling holes. 

 

10.1

 

XW20K – 8 DIN CASE - DIMENSIONS 

 

 

11

 

ELECTRICAL CONNECTIONS 

XW20K is provided with screw terminal blocks to connect cables with a cross section up to 2.5 mm

for 

the RS485 (optional) and the keyboard. Connecting other inputs, power supply and relays, XW20K is 
provided with Faston connections (6.3mm). Heat-resistant cables have to be used. Before connecting 
cables make sure the power supply complies with the instrument’s requirements. Separate the probe 
cables from the power supply cables, from the outputs and the power connections. Do not exceed the 
maximum current allowed on each relay, in case of heavier loads use a suitable external relay. 
NOTE: the maximum current allowed for all the loads is 20A. 

11.1

 

PROBE CONNECTIONS 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room  temperature.  Place  the  defrost  termination  probe  among  the  evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

12

 

TTL/RS485 SERIAL LINE 

The TTL connector allows, by means  of the external module TTL/RS485 (XJ485CX), to connect the 
unit  to  a  network  line  ModBUS-RTU  compatible  as  the 

dIXEL 

monitoring  system  XJ500  (Version 

3.0). The same TTL connector is used to upload and download the parameter list of the  “HOT-KEY”. 
The instruments can be ordered wit the serial output RS485 (Optional). 

13

 

HOW TO: USE OF THE PROGRAMMING “HOT KEY” 

PROGRAM A HOT-KEY FROM AN INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “HOT-KEY”  and  push  UP  button;  the  “uPL  message 
appears followed a by a flashing “End” label. 

3.

 

Push SET button and the “End” will stop flashing. 

4.

 

Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again. 

 
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again 
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation. 

PROGRAM AN INSTRUMENT BY USING A HOT-KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a pre-programmed HOT-KEY into the 5-PIN receptacle and then turn the Controller 
ON. 

3.

 

The  parameter  list  of  the  “HOT-KEY”  will  be  automatically  downloaded  into  the  Controller 
memory. The “doL” message will blink followed a by a flashing “End” label. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “HOT-KEY”. 
 

NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then on 
if you want to restart the download again or remove the “HOT-KEY” to abort the operation. 

 

14

 

ALARM SIGNALS 

Message  Cause 

Outputs 

“P1” 

Thermostat probe failure 

Alarm  output  ON;  Compressor  output  according  to 
parameters Con and CoF

“P3” 

Probe 3 probe failure 

Alarm output ON; Other outputs unchanged 

“P4” 

Probe 4 probe failure 

Alarm output ON; Other outputs unchanged 

“HA” 

Maximum temperature alarm 

Alarm output ON; Other outputs unchanged 

“LA” 

Minimum temperature alarm 

Alarm output ON; Other outputs unchanged 

"HA2" 

Condenser high temperature 

It depends on the AC2 parameter 

"LA2" 

Condenser low temperature 

It depends on the bLL parameter 

“dA” 

Door open 

Compressor and fans restarts  

“EA” 

External alarm 

Output unchanged. 

“CA” 

Serious external alarm (i1F=bAL)  All outputs OFF. 

“CA” 

Pressure switch alarm (i1F=PAL)  All outputs OFF 

“EE” 

Data or memory failure 

Alarm output ON; Other outputs unchanged 

 
The alarm message is displayed until the alarm condition is recovery. 
All the alarm messages are showed alternating with the room temperature except for the “P1” which is 
flashing. 
To  reset  the  “EE”  alarm  and  restart  the  normal  functioning  press  any  key,  the  “rSt”  message  is 
displayed for about 3 sec. 

14.1

 

SILENCING BUZZER  

Once the alarm signal is detected the buzzer can be silenced by pressing any key. Buzzer is mounted 
in the keyboard and it is an option. 

14.2

 

“EE” ALARM 

The 

dIXEL

 instruments are provided with an internal check for the data integrity. Alarm “EE” flashes 

when a failure in the memory data occurs. In such cases the alarm output is enabled. 

14.3

 

ALARM RECOVERY 

Probe alarms: “P1” (probe1 faulty), “P3” and “P4”; they automatically stop 10s after the probe restarts 
normal operation. Check connections before replacing the probe. 
Temperature  alarms  “HA”,  “LA”  “HA2”  and  “LA2”  automatically  stop  as  soon  as  the  temperature 
returns to normal values. 
Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input is disabled. 
Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument. 

 

15

 

Technical data 

Keyboards 
Housing: 
self extinguishing ABS 
Case: T620 and T620T: 
facia 38x185 mm; depth 23mm 
 

V620: facia 72x56 mm; depth 23mm 

 

CX620: facia 75x36 mm; depth 23mm 

Mounting: T620T panel mounting in a 150x31 mm panel cut-out with the 2 metal brackets supplied. 
 

T620:  panel  mounting  in  a  150x31  mm  panel  cut-out  with  two  screws. 

  3  x  2mm.  Distance 

between the holes 165mm 
V620:  panel  mounting  in  a  56x72  mm  panel  cut-out  with  two  screws. 

  3x2mm.  Distance 

between the holes 40mm 

 

CX620: panel mounting in a 71x29mm panel cut-out 

Protection: IP20; Frontal protection: IP65 with frontal gasket 
Connections: Screw terminal block 

 2.5 mm

2

  

Power supply: from XW20K power module 
Display
: 3 digits, red LED, 14.2 mm high 
Optional output: buzzer 
Power module XW20K  
Case: 8 DN:
 140X176X148 
Connections: Screw terminal block 

 2.5 mm

2

 heat-resistant wiring and 6.3mm Faston 

Power supply: 230Vac or. 110Vac 

 10% or 24Vac 

Power absorption: 10VA max 
Inputs
: 3 NTC or PTC probes 
Digital inputs: 1 free voltage 
Relay outputs: Total current on loads MAX. 20A 

Compressor: relay SPST 20(8) A, 250Vac 

 

Light (oA3): relay SPST 16(5) A, 250Vac 

Serial output: TTL standard 
Communication protocol: Modbus - RTU 
Data storing
: on the non-volatile memory (EEPROM) 
Kind of action: 1B 
Pollution degree: normal 
Software class: A 
Operating temperature: 
0 to 60°C (32 to 140°F) 
Storage temperature: -25 to 60°C (-13 to 140°F)  
Relative humidity: 20 to 85% (no condensing) 
Measuring and regulation range:  

NTC probe: -40 to 110°C (-58 to 230°F) 
PTC probe: -50 to 150°C (-58 to 302°F) 

Resolution: 0.1°C or 1°C or 1°F (selectable) 
Accuracy (ambient temp. 25°C): ±0.5°C ±1 digit 

16

 

CONNECTIONS 

16.1

 

XW20K 

 

Содержание XW20K

Страница 1: ...mpressor with a possible delay set in the AC1 parameter Both the compressors are switched off at the same time 3 2 FAST FREEZING When defrost is not in progress it can be activated by holding the UP key pressed for about 3 sec The compressor operates to maintain the CCS set point for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same ac...

Страница 2: ... To exit Press SET UP or wait for 15 sec without pressing any key NOTE1 if no parameter is present in the Pr1 level after the first 3 sec the noP message will be displayed Keep SET DOWN keys pushed till the Pr2 message will be displayed NOTE2 the new set value will be stored even if the procedure is exited by waiting for the time out to expire 7 7 2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO ...

Страница 3: ...m is present in any case regulation restarts after AC time at minimum AC2 Compressor off with high temperature alarm of condenser n compressor keeps on working Y compressor is switched off till the alarm is present in any case regulation restarts after AC time at minimum RELAY OA3 22 23 CONFIGURATION tbA Alarm relay silencing with oA3 ALr n silencing disabled alarm relay stays on till alarm condit...

Страница 4: ...10 seconds the instrument will restart working with the new parameters 5 Remove the HOT KEY NOTE the message Err is displayed for failed programming In this case turn the unit off and then on if you want to restart the download again or remove the HOT KEY to abort the operation 14 ALARM SIGNALS Message Cause Outputs P1 Thermostat probe failure Alarm output ON Compressor output according to paramet...

Страница 5: ...y nP P1 P2 P3 nP Pr2 Sdd Aux output working during defrost n Y n Pr2 ALARMS ALP Probe setting for temperature alarm P1 P2 P3 P4 P1 Pr2 ALC Temperature alarms configuration rE Ab rE Pr2 ALU MAXIMUM temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 ALL minimum temperature alarm 55 0 to 150 0 C 67 to 302 F 10 0 Pr1 AFH Temperature alarm and fan differential 0 1 to 25 5 C 1 to 45 F 2 0 Pr2 ALd Te...

Отзывы: