dIXEL

Installing and Operating Instructions

R1.0 1592007271

1592007271 XR80C-D GB r1.0 20.05.2005.doc

XR80C – XR80D

3/4

Instrument 

XR80D

 shall be

mounted on a DIN rail.
The temperature range
allowed for correct operation
is 0

÷

60 °C. Avoid places

subject to strong vibrations,
corrosive gases, excessive
dirt or humidity. The same
recommendations apply to
probes. Let air circulate by the
cooling holes.

9.

 

ELECTRICAL CONNECTIONS

The instrument is provided with screw terminal block to connect cables with a cross
section up to 2,5 mm

2

. Before connecting cables make sure the power supply complies

with the instrument’s requirements. Separate the probe cables from the power supply
cables, from the outputs and the power connections. Do not exceed the maximum current
allowed on each relay, in case of heavier loads use a suitable external relay.

9.1

 

PROBE CONNECTION

The probes shall be mounted with the bulb upwards to prevent damages due to casual
liquid infiltration.

10.

 

HOW TO USE THE HOT KEY

10.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)

1.

 

Program one controller with the front keypad.

2.

 

When the controller is ON, insert the “

Hot key

” and push 

o

 key; the  

"uPL"

message appears followed a by flashing 

“End”

3.

 

Push “

SET”

 key and the 

End

 will stop flashing.

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again.

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

o

key if you want to restart the upload again or remove the “

Hot key

” to abort the operation.

10.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)

1.

 

Turn OFF the instrument.

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the

Controller ON.

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller

memory, the “

doL

” message is blinking followed a by flashing 

“End”.

4.

 

After 10 seconds the instrument will restart working with the new parameters.

5.

 

Remove the 

“Hot Key”.

.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off

and then on if you want to restart the download again or remove the “

Hot key

” to abort the

operation.

11.

 

ALARM SIGNALS

Message

Cause

Output

“EE”

Data or memory failure

“P1”

Probe  failure

Output according to par. “Con” and “COF”

“HA”

Maximum temp. alarm Output unchanged.

“LA”

Minimum temp. alarm

Output unchanged.

11.1

 

ALARM “EE”

The instrument is provided with an internal check verifying memory integrity. Alarm “

EE

flashes when a failure in the internal memory is detected. In such case call the service.

11.2

 

ALARM RECOVERY

Probe alarm “

P1

” start some seconds after the fault in the related probe; it automatically

stops some seconds after the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat

temperature returns to normal values and when defrost starts.

12.

 

TECHNICAL DATA

Housing: 

self extinguishing ABS.

Case: XR80C 

frontal 32x74 mm; depth 60mm;

XR80D 

4 DIN modules 70x85 mm; depth 61mm

Mounting: XR80C 

panel mounting in a 71x29mm panel cut-out

XR80D

 DIN RAIL mounted in a omega (3) din rail

Protection: 

IP20;

Frontal protection:

 

XR80C 

IP65 with frontal gasket RG-C (optional).

Connections: 

Screw terminal block 

 2,5 mm

2

 wiring.

Power supply:

 according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%;  230Vac

±

10%, 50/60Hz, 110Vac 

±

10%, 50/60Hz

Power absorption: 

3VA max

Display

: 3 digits, red LED, 14,2 mm high; 

Inputs

: 1 PTC or NTC probe.

Relay outputs: compressor 

SPST relay 8(3) A, 250Vac or  SPST relay 20(8)A; 250Vac

agitator: 

SPDT relay 8(3) A, 250Vac or

Kind of action: 

1B; 

Pollution grade: 

normal; 

Software class: 

A.

Data storing

: on the non-volatile memory (EEPROM).

Operating temperature: 

0÷60 °C; 

Storage temperature: 

-30÷85 °C.

Relative humidity:

 20

÷

85% (no condensing)

Measuring and regulation range: PTC probe: 

-50÷150°C (-58÷302°F)

NTC probe: 

-40÷110°C (-58÷230°F)

Resolution: 

0,1 °C or 1°C or 1 °F (selectable).

Accuracy (ambient temp. 25°C)

:  ±0,7 °C ±1 digit

13.

 

CONNECTIONS

13.1

 

XR80C: COMPRESSOR 8A

N.C.

1 2 3 4 5

6

7

9 10

11 12

Comp

Th

er

mo

st

.

8

Hot Key

8(3)A250V

8(3)A250V

Line

12Vac/dc supply

: connect to the terminals 7 and 8.

24Vac/dc supply

: connect to the terminals 7 and 8.

120Vac supply

: connect to the terminals 7 and 8.

13.2

 

XR80C: COMPRESSOR 20A

N.C.

1 2 3 4 5

6

7

9 10

11 12

Comp

Th

er

mo

st

.

8

Hot Key

8(3)A250V

20(8)A250V

Line

12Vac/dc supply

: connect to the terminals 7 and 8.

24Vac/dc supply

: connect to the terminals 7 and 8.

120Vac supply

: connect to the terminals 7 and 8.

13.3

 

XR80D: 8A COMPRESSOR

Power 

Supply

230Vac

Line

8(3)A/250Vac

8(3)A/250Vac

13 14 15 16 17 18 19 

Comp

n.c.

11 12

 

 3 4

n.c.

HO

T KE

Y

24Vac/dc supply

: connect to the terminals 11 and 12.

120Vac supply

: connect to the terminals 11 and 12.

230Vac supply

: connect to the terminals 11 and 12.

Содержание XR80C

Страница 1: ...al parameters that can be easily programmed through the keypad 3 CONTROLLING LOADS 3 1 THE COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point va...

Страница 2: ...le value for the set point US Maximum set point SET 150 C SET 302 F Set the maximum acceptable value for set point Ot Thermostat probe calibration 12 0 12 0 C 120 120 F allows the adjustment of possible offset of the thermostat probe OdS Outputs activation delay at start up 0 255min This function is enabled at the initial start up of the instrument and inhibits any output activation for the period...

Страница 3: ...emp alarm Output unchanged LA Minimum temp alarm Output unchanged 11 1 ALARM EE The instrument is provided with an internal check verifying memory integrity Alarm EE flashes when a failure in the internal memory is detected In such case call the service 11 2 ALARM RECOVERY Probe alarm P1 start some seconds after the fault in the related probe it automatically stops some seconds after the probe res...

Страница 4: ...ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty probe 0 255 min 30 CF Temperature measurement unit C F C rES Resolution in dE dE AgC Agitator configuration EL with compressor in independent EL tIC Resolution for the Agt parameter nP minutes Pb seconds nP IAg Interval between agitation cycle 1 120min 15 Agt Length for agitation cycle 0 255min 3 APO First agitation cycle a...

Отзывы: